Plan Review Details - Permit 17110860
Plan Review Stops For Permit 17110860
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-04 Cont ID  
Sent By jwitmer Date 2018-04-04 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2018-04-04 Time 09:28 Sent To  
Notes
2018-04-04 11:04:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110860
 ADD: 1901 VILLAGE BLVD. / BEAR LAKES COUNTRY CLUB
 CONT: MOUW ASSOCIATES, INC.
 TEL: 561-276-9640
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. APRIL 4/2018
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTALS: PLEASE SUBMIT
 (3) COPIES OF EACH IF PAPER. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOFING: FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 4) BUILDING PROVISO/ DEFERRED SUBMITTALS: W. P. B.
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 5) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715/ FAX: 561-805-6676 /E-MAIL:
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By jwitmer Date 2018-03-08 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2018-03-08 Time 07:18 Sent To  
Notes
2018-03-08 11:00:122014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110860
 ADD: 1901 VILLAGE BLVD. / BEAR LAKES COUNTRY CLUB
 CONT: MOUW ASSOCIATES, INC.
 TEL: 561-276-9640
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MARCH 08/2018
 ACTION: DENIED
  
 1) COMPLIED THRESHOLD BUILDING / FL S. S. 553.71(7
  
 2)PROVISO: ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 3) COMPLIED.
  
 4) SEMI-COMPLIED. 2ND REVIEW A COPIED SOILS REPORT WAS
 SUBMITTED, BUT THE SIGNATURE AND SEAL ARE COPIED NOT
 ELECTRONICALLY SIGNED AND SEALED, YOU MAY WANT TO
 PROVIDE THE CITY WITH A PAPER ORIGINAL SIGNED AND
 SEALED SOILS REPORT, NOT A PHOTOCOPIED BLUE INK
 SIGNATURE, THEY SHOW AS A PIXILATED SIGNATURE.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 1ST REVIEW COMMENT. THIS REVIEW THERE WAS NO SOILS
 REPORT SUBMITTED. THE FOUNDATION PLAN 098_S1.2 THE
 FOUNDATION DETAIL # 1 SHOWS THE USE OF HELICAL PILES.
 FOUNDATION NOTE # 6 INDICATES THE HELICAL PILES SHALL
 HAVE A MINIMUM ALLOWABLE COMPRESSION CAPACITY OF 50K
 AND TENSION CAPACITY OF 10 K. THE SOILS REPORT WILL
 PROVIDE AN ANALYSIS OF THE SOILS AND COMPLIANCE WITH
 THE 2014 FBC-B 1810.3.3.1.9. THRESHOLD INSPECTOR TO BE
 ONSITE
 TO VERIFY THE INSTALLATION, INSPECT AND RECORD THE
 RESULTS OF THE HELICAL PILES AND CODE COMPLIANCE.
  
 5-6) COMPLIED.
  
 7) SEMI-COMPLAINED. SEE COMMENTS BELOW. SHEET
 003_G-102. THE CHART SHOWING THE VARIOUS ROOMS AND
 OCCUPANT LOADS THERE ARE QUESTIONS WHY CERTAIN ROOMS
 SHOW ZERO OCCUPANTS.
  
 7A-B) COMPLIED.
  
 7C) 2ND REQUEST. THE LIFE SAFETY ROOM 2063 MEMBERS
 GALLERY, FBC-B TABLE 1004.1.2. ASSEMBLY TABLES AND
 CHAIRS @15 SQ. FT./ OCCUPANT.
  
 7D) 2ND REQUEST. ROOM 2070 GOLF SHOP VESTIBULE, , FBC-B
 TABLE 1004.1.2. ASSEMBLY TABLES AND CHAIRS @15 SQ. FT./
 OCCUPANT.
  
 7E-F) COMPLIED.
  
 8-11) COMPLIED.
  
 12) SEMI-COMPLIED. NEW COMMENT. SHEET 028_A-506. THE
 MENS LOCKER ROOM HAS THE SAME SITUATION,
 SHEET 003.1 G-102 SHOWS AN OCCUPANT LOAD OF 70 PEOPLE
 BUT ONLY ONE MEANS OF EGRESS. THIS AREA WILL ALSO
 REQUIRE A 2ND MEANS OF EGRESS. THE NEW REVISED PLAN
 SHOWS THE 2ND EXIT REMOVED.
  
 1ST REVIEW COMMENTS. SHEET 031_A-603 SHOWS EXIT LIGHTS
 IN BOTH THE MENS AND LADIES LOCKER ROOMS. THE MENS
 LOCKER ROOM IS NOT REQUIRED TO HAVE A SECOND MEANS OF
 EGRESS BUT THE SAME SITUATION AS WITHIN THE LADIES
 LOCKER ROOM, 2014 FBC-B TABLE 1015.1.
 THERE IS A INTERVENING ROOM (2047) WHICH IS ALLOWED
 (1014.2) WITH THE EXCEPTION OF (4).
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 THE LOCKER ROOMS ARE USED FOR STORAGE.
  
 13A)2ND REQUEST. THE ORIGINAL REQUEST IS TO SHOW THE
 30X48 INCH CLEAR FLOOR SPACE FOR THE SHOWER, IT SHOULD
 COMPLY WITH ACC. CODE 608.2.1 TRANSFER SHOWER
 COMPARTMENTS.
 1ST ROUND COMMENT. . SHEET 028_A-506 IN BOTH THE LADIES
 AND MENS ACCESSIBLE SHOWERS, ROOMS 2060, 2061 & 2075
 THERE IS NO CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN.
 PLEASE REVIEW THE 2014 ACCESSIBILITY CODE 608.2.1
 TRANSFER TYPE SHOWER COMPARTMENTS. TRANSFER TYPE SHOWER
 COMPARTMENTS SHALL BE 36 INCHES (915 MM) BY 36 INCHES
 (915 MM) CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 36 INCH (915
 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT. CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED. SHOW THE CONTROLS ON WALL.
  
 13B-D) COMPLIED.
  
 14) 2ND REQUEST. THE FINISH SCHEDULE INDICATES TILE FOR
 THE FLOOR, BASE & WALLS BUT THE SCHEDULE DOES NOT SHOW
 COMPLIANCE WITH THE TILE BACKING.
 1ST ROUND COMMENTS. THE PLAN DOES NOT ADDRESS RESTROOM/
 BATHROOM FINISHES IN WET AREAS, PLEASE SHOW COMPLIANCE
 WITH FBC-B 2509.2 BASE FOR TILE & 2509.3 LIMITATIONS.
  
 15-16) COMPLIED.
  
 17) 2ND REQUEST. THE RESPONSE INDICATED THE STRUCTURAL
 SUPPORTS FOR THE FOLDING DOOR WERE ON SHEET S1.3.
 PLEASE NOTE THERE ARE NO REVISIONS TO SHEET S1.3.
 1ST ROUND OF COMMENTS. PLEASE SUBMIT THE FOLDING DOOR
 MANUFACTURED SPECS OF HOW IT IS TO BE HUNG, AND IF IT
 WOULD TAKE EXTRA SUPPORT NOT SHOWN ON THE STRUCTURAL
 SHEETS. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 18-19) COMPLIED.
  
 20A) COMPLIED. SEE MECH. COMMENT # 3. 2014 FBC-M 404.1.
  
 20B-C) COMPLIED.
  
  
  
 21)2ND REQUEST. SEMI-COMPLIED. THANK YOU FOR THE
 PRESSURES IN VASD. THE ISSUE IS WITH THE WALL
 PRESSURES. THE NEGATIVE WALL ZONE 5 PRESSURES ARE THE
 SAME AS FOR ZONE 4. IN THE ASCE 7-10 FIGURE 30.4-2B
 UNDER NOTE # 7, THERE IS A NOTE STATING THE ROOF ZONE 3
 WITH HIPS 0<25DEGREES THE ZONE 3 SHALL BE TREATED AS
 ZONE 2. THERE IS NO REDUCTION FOR WALL ZONE 5. PLEASE
 UPDATE BOTH THE VULT AND VASD NEGATIVE WALL PRESSURES
 FOR ZONE 5. FLAT ROOFS WITH PARAPETS GREATER THAN 3
 FEET ALSO GET A ROOF ZONE 3 REDUCTION TO ZONE 2
 PRESSURES.
 1ST ROUND OF SHEET 095_S0.2 PROVIDES THE COMPONENTS AND
 CLADDING PRESSURES IN VULT PRESSURES. PLEASE PROVIDE
 THE PRESSURES ALSO IN VASD SINCE THE PRODUCT APPROVALS
 ARE ALL IN VASD. FBC-B 1609.3.1 WIND SPEED CONVERSION
 VULT TO VASD.
  
 22) BUILDING PROVISO/ DEFERRED SUBMITTALS: PLEASE
 SUBMIT (3) COPIES OF EACH. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 23) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 24) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOFING: FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 25) BUILDING PROVISO/ DEFERRED SUBMITTALS: W. P. B.
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 26) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 27) COMPLIED. BUILDING TO BE FULLY ADA ACCESSIBLE.
  
 28) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 29) CLOSING. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jwitmer Date 2017-12-22 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2017-12-21 Time 07:45 Sent To  
Notes
2017-12-22 13:46:192014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110860
 ADD: 1901 VILLAGE BLVD. / BEAR LAKES COUNTRY CLUB
 CONT: MOUW ASSOCIATES, INC.
 TEL: 561-276-9640
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 22/2018
 ACTION: DENIED
  
 1) PLEASE NOTE THIS BUILDING IS CONSIDERED A THRESHOLD
 BUILDING. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 THE THRESHOLD INSPECTIONS FORMS WERE E-MAILED TO:
 [email protected] 12/21/17 01:20 PM.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 2) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 3) PLEASE NOTE THE ASSESSED VALUE OF THIS STRUCTURE BY
 THE P. B. C. PROPERTY APPRAISERS OFFICE FOR IMPROVED
 PROPERTY VALUE ONLY IS $2,636,538.00 DOLLARS. THE
 PROPOSED RENOVATION AND ADDITION VALUE IS
 $5,500.000.00 DOLLARS IN VALUE. THIS FIGURE IS WELL
 OVER THE 30% OF THE VALUE OF THE STRUCTURE, SEE
 DEFINITION OF RENOVATION 2014 FBC-ENERGY CODE.
 RENOVATED BUILDING. A RESIDENTIAL OR NONRESIDENTIAL
 BUILDING UNDERGOING ALTERATION THAT VARIES OR CHANGES
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS, OR
 EXTERIOR ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED
 COST OF RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED
 VALUE OF THE STRUCTURE.
  
 2014 FBC-ENERGY CODE C401.2 APPLICATION. COMMERCIAL
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
  
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 C401.2.1 APPLICATION TO EXISTING BUILDINGS.
 ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. SECTIONS C402, C403, C404 AND C405; OR
 2. ANSI/ASHRAE/IESNA 90.1.
  
 4) THIS REVIEW THERE WAS NO SOILS REPORT SUBMITTED. THE
 FOUNDATION PLAN 098_S1.2 THE FOUNDATION DETAIL # 1
 SHOWS THE USE OF HELICAL PILES. FOUNDATION NOTE # 6
 INDICATES THE HELICAL PILES SHALL HAVE A MINIMUM
 ALLOWABLE COMPRESSION CAPACITY OF 50K AND TENSION
 CAPACITY OF 10 K. THE SOILS REPORT WILL PROVIDE AN
 ANALYSIS OF THE SOILS AND COMPLIANCE WITH THE 2014
 FBC-B 1810.3.3.1.9. THRESHOLD INSPECTOR TO BE ONSITE
 TO VERIFY THE INSTALLATION, INSPECT AND RECORD THE
 RESULTS OF THE HELICAL PILES AND CODE COMPLIANCE.
  
 5) SHEET 003_G-101, UNDER THE HEADING APPLICABLE CODES
 MISSING THE5TH EDITION (2014) FLORIDA EXISTING
 BUILDING CODE. WHAT LEVEL OF ALTERATION? SEE 2014
 EXISTING BUILDING CODE CHAPTER 5 CLASSIFICATION OF
 WORK.
  
 6) SHEET 003_G-101. THE LOWER AND MAIN LEVEL LIFE
 SAFETY PLAN. THE MAIN LEVEL LIFE SAFETY PLAN DOES NOT
 INDICATE THE ACCUMULATIVE OCCUPANT LOAD FROM EACH ROOM
 AND WHAT LOADS ARE BEING ADDED THROUGH THE VARIOUS
 CORRIDORS AND OR EGRESS THROUGH INTERVENING ROOMS.
 WHERE THE OCCUPANT LOAD IS OVER 49 REQUIRING 2 EXITS,
 THE FLOOR PLAN DOES NOT PROVIDE HOW MANY OCCUPANTS ARE
 HEADING OUT WHAT DOOR AND AGAIN THE ACCUMULATIVE
 OCCUPANT LOADS FOR THE CORRIDOR AND OR INTERVENING
 ROOMS.
  
 2014 FBC-B 1004.1.1 CUMULATIVE OCCUPANT LOADS. WHERE
 THE PATH OF EGRESS TRAVEL INCLUDES INTERVENING ROOMS,
 AREAS OR SPACES, CUMULATIVE OCCUPANT LOADS SHALL BE
 DETERMINED IN ACCORDANCE WITH THIS SECTION.
  
 7) SHEET 003_G-101. THE CHART SHOWING THE VARIOUS ROOMS
 AND OCCUPANT LOADS THERE ARE QUESTIONS WHY CERTAIN
 ROOMS SHOW ZERO OCCUPANTS.
  
 7A) ROOM 2003 THE EXISTING LOBBY IS MORE THAN JUST A
 CORRIDOR, THE FLOOR PLANS SHOWS TABLES CHAIRS AND A
 PIANO. FBC-B TABLE 1004.1.2. ASSEMBLY TABLES AND CHAIRS
 @15 SQ. FT./ OCCUPANT.
  
 7B) ROOMS 2007 & 2008 COOLER/FREEZERS NO OCCUPANT LOAD.
 FBC-B TABLE 1004.1.2. STORAGE @ 300.
  
 7C) ROOM 2063 MEMBERS GALLERY, FBC-B TABLE 1004.1.2.
 ASSEMBLY TABLES AND CHAIRS @15 SQ. FT./ OCCUPANT.
  
 7D) ROOM 2070 GOLF SHOP VESTIBULE, , FBC-B TABLE
 1004.1.2. ASSEMBLY TABLES AND CHAIRS @15 SQ. FT./
 OCCUPANT.
  
 7E) IT APPEARS ROOMS LABELS NEED TO BE REVERSED. 2079 &
 2080. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 MENS ATTENDANT SHOULD HAVE AN OCCUPANT LOAD JUST AS THE
 WOMENS ATTENDANT ROOM 2049.
  
 7F) ROOM 2089 WHERE IS THIS VESTIBULE LOCATED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) SHEET 003_G-101. LIFE SAFETY GENERAL NOTES OCCUPANT
 LOAD SIGNAGE REFERENCES THE 2007 FBC 2007 1004.3.
 PLEASE CORRECT TO THE CURRENT CODE CYCLE. 2014 FBC-B
 2014.
  
 9) SHEET 003_G-101. LIFE SAFETY GENERAL NOTES STATE ALL
 BUILDING ENTRANCES SHALL BE ACCESSIBLE AND COMPLY WITH
 2014 FBC ADA CHAPTER 11. PLEASE SEE THERE ARE 3 MAIN
 ENTRANCES INTO THE BUILDING ONE IN THE FRONT WITH AN
 ACCESSIBLE ENTRANCE AND 2 IN THE BACK, BOTH STAIRS AND
 NOT AN ACCESSIBLE ENTRANCE. PLEASE REVIEW THE 2014
 FBC-ACCESSIBILITY CODE SECTION 206.4.1 PUBLIC
 ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2
 THROUGH 206.4.9, AT LEAST 60 PERCENT( 3 X 0.60 = 1.8 OR
 2 REQUIRED ACCESSIBLE ENTRANCES FOR THE PUBLIC) OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404. THE RAMP GOING
 INTO THE KITCHEN IS NOT ACCEPTABLE SINCE THE MEANS OF
 EGRESS CANNOT GO THROUGH THE KITCHEN. THE FUNDS SPENT
 TO MAKE A 2ND ACCESSIBLE ENTRANCE FROM THE REAR OF THE
 BUILDING CAN BE COUNTED TOWARD THE 20 %
 DISPROPORTIONATE COST. SEE 2014 ACCESSIBILITY CODE
 SECTION 202.4.1. DISPROPORTIONATE COST.
  
 10) SHEET 003_G-101 SHOWS THE KITCHEN AS ROOM
 IDENTIFICATION TAG 2004 PLEASE SEE TOILET ROOM 2014
 DIRECTLY ACROSS WHERE THE KITCHEN RANGE AND GRILLE ARE
 LOCATED. PLEASE PROVIDE COMPLIANCE WITH:
  
 2014 FBC-B 1210.4 TOILET ROOM LOCATION. TOILET ROOMS
 SHALL NOT OPEN DIRECTLY INTO A ROOM USED FOR THE
 PREPARATION OF FOOD FOR SERVICE TO THE PUBLIC.
  
 11A) SHEET 013_A-102 AND SHEET 028_A-506 SHOW THE
 WOMENS CARD ROOM 2048 WITH A OCCUPANT LOAD OF
 65. SINCE THE OCCUPANT LOAD IS 50 OR MORE 2 MEANS OF
 EGRESS ARE REQUIRED, 2014 FBC-B TABLE 1015.1.
 THERE IS A INTERVENING ROOM (2047) WHICH IS ALLOWED
 (1014.2) WITH THE EXCEPTION OF (4).
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 THE LOCKER ROOMS ARE USED FOR STORAGE. NOTE # 21 STATES
 THE LOCKERS ARE TO BE TWO TIER HIGH, THIS NOTE IS NOT
 FOUND ON THE LOCKERS IN THE CENTER OF EACH LOCKER ROOM.
 WHAT WE ARE TRYING TO DETERMINE IS THE OPENNESS OF THE
 WOMENS LOCKER ROOM, SUCH AS AN ALCOVE WHERE YOU WOULD
 BE ABLE TO SEE ACROSS THE LOCKER ROOM AND THE EXIT
 LIGHT ON THE 2ND MEANS OF EGRESS FROM THIS ROOM. THE
 CODE SECTION 1205.2.1 ADJOINING SPACES IS TO BE USED
 FOR NATURAL LIGHTING, IF THE LOCKER ROOM IS BLOCKED
 WITH LOCKERS 2 TIERED HIGH WITHOUT THE KNOWN VERTICAL
 HEIGHT THE SIGHT LINE MAY NOT ALLOW A PERSON TO KNOW
 THERE IS A 2ND MEANS OF EGRESS THROUGH THIS ROOM.
 ESPECIALLY IF A LADY HAD A LOCKER ON THE OTHER SIDE OF
 THE CARD ROOM.
  
 11B) IF THE EXIT DOOR IN THE LADIES LOCKER ROOM IS
 ALLOWED TO BE THE 2ND MEANS OF EGRESS, THE EXIT
 DISCHARGE IS TO TAKE THE OCCUPANT TO THE PUBLIC WAY.
 1027.5 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE SHALL
 PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC
 WAY. NEITHER SHEET 004_AS-101 NOR 013_A-102 AND SHEET
 028_A-506 SHOW THIS. PLEASE NOTE THIS SHOULD BE AN
 ACCESSIBLE EXIT AS WELL.
  
 12) SHEET 028_A-506 THE MENS LOCKER ROOM HAS THE SAME
 SITUATION, SHEET 031_A-603 SHOWS EXIT LIGHTS IN BOTH
 THE MENS AND LADIES LOCKER ROOMS. THE MENS LOCKER ROOM
 IS NOT REQUIRED TO HAVE A SECOND MEANS OF EGRESS BUT
 THE SAME SITUATION AS WITHIN THE LADIES LOCKER ROOM,
 2014 FBC-B TABLE 1015.1.
 THERE IS A INTERVENING ROOM (2047) WHICH IS ALLOWED
 (1014.2) WITH THE EXCEPTION OF (4).
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 THE LOCKER ROOMS ARE USED FOR STORAGE.
  
 13A) SHEET 028_A-506 IN BOTH THE LADIES AND MENS
 ACCESSIBLE SHOWERS, ROOMS 2060, 2061 & 2075 THERE IS NO
 CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN. PLEASE
 REVIEW THE 2014 ACCESSIBILITY CODE 608.2.1 TRANSFER
 TYPE SHOWER COMPARTMENTS. TRANSFER TYPE SHOWER
 COMPARTMENTS SHALL BE 36 INCHES (915 MM) BY 36 INCHES
 (915 MM) CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 36 INCH (915
 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT. CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED. SHOW THE CONTROLS ON WALL.
  
 13B) THESE SHOWERS APPEAR TO HAVE A CURB, A 36X36 INCH
 TRANSFER SHOWER CURB HEIGHT IS:
 608.7 THRESHOLDS. EXCEPTION: A THRESHOLD 2 INCHES (51
 MM) HIGH MAXIMUM SHALL BE PERMITTED IN TRANSFER TYPE
 SHOWER COMPARTMENTS IN EXISTING FACILITIES WHERE
 PROVISION OF A 1/2 INCH (13 MM) HIGH THRESHOLD WOULD
 DISTURB THE STRUCTURAL REINFORCEMENT OF THE FLOOR SLAB.
 PLEASE PROVIDE A DETAIL.
  
 13C) PLEASE ALSO SHOW BACKING FOR SEAT AND GRAB BARS,
 AND IF THE SEAT IS TO BE A FOLDING SEAT OR NON-FOLDING
 SEAT. 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL
 BE PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. SEATS
 SHALL COMPLY WITH 610.
  
 13D) 2014 FBC-B 608.4 SEATS. A FOLDING OR NON-FOLDING
 SEAT SHALL BE PROVIDED IN TRANSFER TYPE SHOWER
 COMPARTMENTS. A FOLDING SEAT SHALL BE PROVIDED IN
 ROLL-IN TYPE SHOWERS REQUIRED IN TRANSIENT LODGING
 GUEST ROOMS WITH MOBILITY FEATURES COMPLYING WITH
 806.2. SEATS SHALL COMPLY WITH 610.
  
 14) THE PLAN DOES NOT ADDRESS RESTROOM/ BATHROOM
 FINISHES IN WET AREAS, PLEASE SHOW COMPLIANCE WITH
 FBC-B 2509.2 BASE FOR TILE & 2509.3 LIMITATIONS.
  
 15) SHEET 021_A-402 STAIR DETAILS DOES NOT PROVIDE
 ENOUGH DETAIL FOR DESIGNING THE GUARDRAIL/ HANDRAIL
 SYSTEM.
 2014 FBC-B 1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
 POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH SECTION
 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES AND GUARDS
 SHALL ALSO COMPLY WITH SECTION 2407.
  
 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS
 SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF
 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
  
 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL
 THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS
 SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50
 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
 2406.4.4 GLAZING IN GUARDS AND RAILINGS. GLAZING IN
 GUARDS AND RAILINGS, INCLUDING STRUCTURAL BALUSTER
 PANELS AND NONSTRUCTURAL IN-FILL PANELS, REGARDLESS OF
 AREA OR HEIGHT ABOVE A WALKING SURFACE SHALL BE
 CONSIDERED A HAZARDOUS LOCATION. 2407.1 MATERIALS. FOR
 ALL GLAZING TYPES, THE MINIMUM NOMINAL THICKNESS SHALL
 BE 1/4 INCH (6.4 MM). FULLY TEMPERED GLASS AND
 LAMINATED GLASS SHALL COMPLY WITH CATEGORY II OF CPSC
 16 CFR PART 1201 OR CLASS A OF ANSI Z97.1.
  
 16) SHEET 027_A-505 THE ROOM 2022 SHOWS THE USE OF
 FOLDING PARTITIONS TO CREATE 2 A2 ASSEMBLY ROOMS.
 PLEASE PROVIDE THE OVERALL DIAGONAL DISTANCE FOR BOTH
 ROOMS, WHAT 1/3RD THE DISTANCE WOULD ALSO BE,
 IT WOULD APPEAR ON THE ROOM TO THE LEFT THE 2 EXITS
 DOORS ARE CLOSER THAN 1/3RD THE OVERALL DISTANCE FOR
 THAT PORTION OF THE ROOM. FBC-B 1015.2.1. EXCEPTION 2.
  
 17) PLEASE SUBMIT THE FOLDING DOOR MANUFACTURED SPECS
 OF HOW IT IS TO BE HUNG, AND IF IT WOULD TAKE EXTRA
 SUPPORT NOT SHOWN ON THE STRUCTURAL SHEETS. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 18) EXITING CONFLICT IN SWING OF DOORS BETWEEN ROOMS
 2022 AND 2023, WHEN THE FOLDING DOORS ARE CLOSED
 BETWEEN THESE ROOMS DEPENDING ON THE EXITING PLAN YET
 NOT SEEN, THESE DOORS WILL BE SWINGING THE WRONG WAY
 FOR THE 2ND MEANS OF EGRESS FOR ROOM 2022 AND THE BAR
 AREA 2064.
 FBC-B 1008.1.2. DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING A ROOM OR AREA CONTAINING
 AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 19) SHEET 026_A-504 SHOWS WHAT APPEARS TO BE AN
 EXTERIOR STAIR # 2012 AND IT APPEARS THERE IS A LANDING
 ON THE UPPER FLOOR LEVEL AND GOES DOWN TO THE LOWER
 LEVEL BUT THE PLAN DOES NOT INDICATE HOW YOU GET TO THE
 STAIR? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 20A) PLEASE NOTE SHEET 003_G-101 THE LIFE SAFETY PLAN
 FOR THE LOWER LEVEL DOES NOT INDICATE THE OCCUPANCY
 TYPE FOR THE LOWER FLOOR. THERE SEEMS THERE MAY BE MORE
 THAN ONE OCCUPANCY, POSSIBLY A MIXED OCCUPANCY IN THE
 STORAGE, THERE IS A S1 OCCUPANCY WITH THE STORAGE OF
 GOLF CARTS, PLEASE IDENTIFY IF THEY ARE GAS OR IF THEY
 ARE ELECTRIC. ARE THE GOLF CARTS CHARGED UP AT NIGHT,
 THE ELECTRICAL SHEETS DO NOT INDICATE AS SUCH? THE
 PLANS ALSO INDICATE AN EXISTING GOLF CART MAINTENANCE
 SHOP PLEASE LIST IF THERE IS AND QUANTITIES OF
 HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1).
  
 20B) THE LIFE SAFETY PLAN UNDER THE HEADING OF
 OCCUPANCY SEPARATION LIST N/A. THE PLANS LIST CODE
 SECTIONS 508.3 (NON-SEPARATED AND 508.4 SEPARATED). THE
 CONCERN IS THE FIRE BARRIER REQUIRED BETWEEN THE LOWER
 FLOOR(S-1 OCCUPANCY) AND THE A-2 (UPPER FLOOR). FBC-B
 TABLE 707.3.10 WOULD REQUIRE 2 HOUR SEPARATION. SHEET
 003_G-101 SHOWS A NEW MASONRY INFILL WALL ON THE LOWER
 FLOOR BUT NO FIRE RATING. THE DOOR 1007 INDICATES A 90
 MINUTE FIRE RATING.
  
 20C) PLEASE PROVIDE A LIFE SAFETY PLAN WITH COMMON PATH
 OF TRAVEL FBC-B TABLE 1014.3 AND TRAVEL DISTANCES
 INCOMPLIANCE WITH FBC-B TABLE 1016.2.
  
 21) SHEET 095_S0.2 PROVIDES THE COMPONENTS AND CLADDING
 PRESSURES IN VULT PRESSURES. PLEASE PROVIDE THE
 PRESSURES ALSO IN VASD SINCE THE PRODUCT APPROVALS ARE
 ALL IN VASD. FBC-B 1609.3.1 WIND SPEED CONVERSION VULT
 TO VASD.
  
 22) PLEASE SUBMIT (3) COPIES OF EACH. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 23) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 24) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 25) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 26) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 27) EITHER THE CONTRACTOR OR THE DESIGN PROFESSIONAL
 PLEASE PROVIDE ON THEIR LETTERHEAD AN ITEMIZED LETTER
 PROVIDING WHERE UP TO $1,100,000.00 DOLLARS HAS BEEN
 SPENT FOR ACCESSIBLE UPGRADES.
 2014 FBC-ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE
 COST. ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 28) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 29) CLOSING. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By jleahy Date 2018-03-06 Time 17:21 Rev Time 0.00
Received By jleahy Date 2018-03-06 Time 17:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-01-03 Cont ID  
Sent By jleahy Date 2018-01-03 Time 08:32 Rev Time 0.00
Received By jleahy Date 2018-01-02 Time 10:58 Sent To  
Notes
2018-01-02 15:32:34FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVISO
  
 ROOF TOP OUTLET REQUIRED FOR SERVICING EQUIPMENT 210.63

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-14 Cont ID  
Sent By scaldero Date 2018-02-14 Time 12:08 Rev Time 0.00
Received By scaldero Date 2018-02-14 Time 09:07 Sent To  
Notes
2018-02-14 12:08:19PERMIT # 17110860
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW - APPROVED PROVISO:
  
 FAILURE TO COMPLY WITH ALL PROVISO COMMENTS WILL RESULT
 IN A FAILED FIRE INSPECTION.
  
 REPEAT COMMENTS:
  
 SHEET G101: TABLES AND CHAIRS APPEAR TO IMPEDE THE
 DIRECT ACCESS PATH TO THE EXIT DOORS. THIS NEEDS TO BE
 REVIEWED AND VERIFIED IN THE FIELD. CHANGES MAY BE
 REQUIRED TO THE FURNITURE LAYOUT, AS DEEMED NECESSARY
 BY THE FIRE INSPECTOR.
  
 SHEETS E2.1 AND E2.2: EMERGENCY LIGHTING FIXTURES
 AND/OR EXIT SIGNAGE IS NOT CLEARLY IDENTIFIED.
 EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL BE INSTALLED
 AND MAINTAINED PER NFPA 101, CHAPTER 7. THIS IS TO BE
 VERIFIED AND INSPECTED TO ENSURE CODE COMPLIANCE, BY
 THE FIRE INSPECTOR. FAILURE TO COMPLY WITH THE FIRE
 CODE REQUIREMENTS, WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By wjolin Date 2017-11-29 Time 09:22 Rev Time 0.00
Received By wjolin Date 2017-11-29 Time 07:19 Sent To  
Notes
2017-11-29 08:10:211901 VILLAGE BOULEVARD - CLUBHOUSE
 PERMIT #17110860
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: TEMPORARY CONSTRUCTION TRAILERS OR MODULAR
 BUILDINGS WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET G-101:
 INSUFFICIENT QUANTITY OF ILLUMITED EXIT SIGNS PROVIDED
 THROUGHOUT MAIN LEVEL. FOR EXAMPLE ONLY A SINGLE EXIT
 SIGN IS PROVIDED IN ASSEMBLY ROOMS #2004, #2048, AND
 #2087 TO NAME A FEW. COORDINATE ADDITIONAL EXIT SIGNAGE
 WITH ELECTRICAL PLANS.
  
 THE SOUTH EXIT SIGN IN ASSEMBLY ROOM #2023 DIRECTS
 OCCUPANTS TO A DOUBLE EGRESS DOOR THAT IS SWINGING
 AGAINST THE PATH OF TRAVEL. PER SECTION 7.2.1.4.2, DOOR
 IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
 FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
  
 SEVERAL CHAIRS AND TABLES ARE IMPEDING A DIRECT EXIT
 ACCESS PATH TO THE EXIT DOORS.
  
 EXIT DOORS LEADING TO EXTERIOR STAIR #2065 INDICATE A
 OCCUPANT LOAD CAPACITY OF 165 AND 330 PERSONS (495
 TOTAL PERSONS); HOWEVER, THE EXIT STAIR ONLY HAS A
 WIDTH OF APPROXIMATELY 5 FEET THAT WOULD LIMIT THE
 EGRESS CAPACITY TO ROUGHLY 200 PERSONS. THE SAME
 SITUATION OCCURS AT EXTERIOR STAIR #2021.
  
 NO OCCUPANT LOAD PROVIDED FOR ASSEMBLY #2003 AND #2063.
  
 OCCUPANT LOAD FACTOR FOR KITCHEN AND SUPPORT STAFF IS
 100 SQUARE FEET PER PERSON PER NFPA 101. PLANS INDICATE
 AN OCCUPANT LOAD FACTOR OF 200 SQUARE FEET PERSON.
  
 SHEET A-801: THE DOOR SCHEDULE INFORMATION IS
 INCOMPLETE (NO DOOR NOTES, HARDWARE, ETC.)
  
 SHEET M2.1: GOLF CART STORAGE DOES NOT APPEAR TO BE
 VENTILATED. HOW WILL THE POSSIBLE HYDROGEN OFF-GASSING
 FROM THE GOLF CART BATTERIES BE MITIGATED?
  
 SHEET E2.1: NO NEW OR EXISTING EMERGENCY LIGHTING OR
 EXIT SIGNAGE SHOWN.
  
 SHEET E2.2: PLEASE CLEARLY INDICATE WHICH LIGHTING
 FIXTURES ARE EMERGENCY LIGHTS. ENSURE EMERGENCY
 LIGHTING PROVIDED FOR EXTERIOR EGRESS STAIRS.
  
 SHEET FA1.2:
 FIRE ALARM SYSTEM UTILIZING HORN-STROBE NOTIFICATION
 APPLIANCES. PER SECTION 12.3.4.3.3, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 PROVIDE FIRE ALARM NOTIFICATION APPLIANCES IN THE
 KITCHEN COLD STORAGE AREAS (FREEZERS).
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 09:28 Rev Time 0.00
Received By gjohnson Date 2018-04-06 Time 09:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-16 Cont ID  
Sent By gjohnson Date 2018-03-16 Time 14:20 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 14:20 Sent To  
Notes
2018-03-16 15:01:39 
 2ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 COMMENT 1: PROVIDE ELEVATION PLAN SHOWING LOCATION OF
 CONCENTRIC VENT TERMINAL WITH DIMENSIONS TO OPENINGS.
 PER WBP AMEND TO FBC 107.2.1.
 RESPONSE: DIMENSIONS HAVE BEEN ADDED TO FUEL GAS
 ISOMETRIC PLAN ON SHEET FG3.1. DIMENSION NOT SHOWN
  
 NEW COMMENTS:
  
 1. SHOW THE LENGTH OF THE PIPE ON THE RISER FROM THE MP
 REGULATOR TO THE KITCHEN EQUIPMENT. PER FBC FG 402.4.1
 AND PER WBP AMEND TO FBC 107.2.1.
  
 2. PLEASE SIZE THE PIPE DOWN STREAM OF THE EMERGENCY
 VALVE FOR KIT EQUIPMENT. PER FBC FG 402.4.1 AND PER WBP
 AMEND TO FBC 107.2.1.
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDES FOR ALL GAS EQUIPMENT AND REGULATORS. PER WBP
 AMEND TO FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By gjohnson Date 2018-01-17 Time 11:52 Rev Time 0.00
Received By gjohnson Date 2018-01-17 Time 11:52 Sent To  
Notes
2018-01-17 12:17:461ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. PROVIDE ELEVATION PLAN SHOWING LOCATION OF COCENTRIC
 VENT TERMINAL WITH DIMENSIONS TO OPENINGS. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. FG2.0 HAS GAS LOGS SHOWN ON PLAN WITH DIFFERENT
 BTU LOADS THESE ARE NOT SHOWN ON ANY FLOOR PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. SHT. FG0.1 THE PROPANE GAS PIPING SIZING LIST
 TABLES FOR NATURAL GAS PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 4. SHT. FG0.1 THE PROPANE GAS PIPE SIZING CHART IS
 CONFUSING THEY LIST FIRE PITS AND FIRE PLACES THAT ARE
 NOT SHOWN ON PLAN. UNDER AREAS SERVED IT LIST METER TO
 BUILDING INTERIOR, EXISTING METER AND GWH REG. THE PLAN
 SHOWS PROPANE WHAT ARE THESE CHARTS FOR PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. FG 3.1 TH E GAS ISOMETRIC APPEARS THAT IT DID
 NOT LOAD PROPERLY I CAN NOR READ IT A COMPREHENSIVE GAS
 REVIEW NOT NOT BE DONE AT THIS TIME. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-04-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-26 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-19 Cont ID  
Sent By cpuell Date 2018-03-19 Time 14:11 Rev Time 0.00
Received By cpuell Date 2018-02-13 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-17 Cont ID  
Sent By gjohnson Date 2018-01-17 Time 12:17 Rev Time 0.00
Received By gjohnson Date 2017-11-27 Time 09:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-04-04 Cont ID  
Sent By jwitmer Date 2018-04-04 Time 09:48 Rev Time 0.00
Received By jwitmer Date 2018-04-04 Time 09:42 Sent To  
Notes
2018-04-04 09:48:02IMPACT FEES PAID
 PALM BEACH COUNTY IMPACT FEE OFFICE
 DATE RECEIVED: 03/28/28/2018
 RECEIPT NUMBER:2018-0328-198
 TRACKING NUMBER: MU-2018-010095-0000
 TOTAL AMOUNT: $7,977.08
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By jwitmer Date 2018-03-08 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2018-03-08 Time 11:00 Sent To  
Notes
2018-03-08 11:01:03IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jwitmer Date 2017-12-22 Time 13:47 Rev Time 0.00
Received By jwitmer Date 2017-12-21 Time 07:45 Sent To  
Notes
2017-12-22 13:47:05IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-10 Cont ID  
Sent By ccole Date 2018-04-10 Time 11:20 Rev Time 0.00
Received By ccole Date 2018-04-10 Time 09:12 Sent To  
Notes
2018-04-10 11:23:10MECHANICAL PROVISO.
 REQUIRED SUBMITTALS:
  
 * MIAMI-DADE NOA'S FOR ROOF STAND,
 AND LOUVERS
 * STEALTH ACCESS PANELS
 * DUCT SMOKE DETECTORS
 * SHOP DRAWINGS FOR ROOF LADDER
  
 ALL SUBMITTALS SHALL BE APPROVED AND STAMPERD BY THE
 EOR AND PROVIDED TO THE BUILDING DEPARTMENT PRIOR TO
 1ST INSPECTION.
  
 PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, AND
 WALK-IN COOLERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By ccole Date 2018-03-09 Time 14:55 Rev Time 0.00
Received By ccole Date 2018-03-09 Time 14:54 Sent To  
Notes
2018-03-09 15:20:012ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110860
 3/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.3: THE REVISED PLAN INDICATES COMPLIANCE IN
 TERMS OF EXHAUST VENTILATION CAPACITY FOR THE GOLF CART
 PARKING GARAGE, HOWEVER THE SEQUENCE OF OPERATION FOR
 THE EXHAUST FANS HAS NOT BEEN CLARIFIED. PLEASE NOTE
 THAT SECTION 502.4.2 REQUIRES CONTINUOUS VENTILATION TO
 LIMIT HYDROGEN CONCENTRATION, AND SECTION 502.4.3
 REQUIRES THE VENTILATION SYSTEM TO BE SUPERVISED BY
  
 AN APPROVED CENTRAL, PROPRIETARY OR REMOTE STATION
 SERVICE OR SHALL INITIATE AN AUDIBLE AND VISUAL SIGNAL
 AT A CONSTANTLY ATTENDED ON-SITE LOCATION. PLEASE
 PROVIDE ADDITIONAL NOTES AND DETAILS.
  
 2) M2.1: EXHAUST FANS EF-0-1 AND EF-7 ARE REQUIRED TO
 DISCHARGE TO THE OUTDOORS- SECTION 501.3. THE PLAN
 SHOWS THE FANS DISCHARGING ONTO THE GARAGE.
  
 3) M2.5 & A.105: PLEASE PROVIDE ENLARGED ARCHITECTURAL
 AND STRUCTURAL DETAILS FOR THE PROPOSED NEW ROOF LADDER
 NEEDED FOR ACCESS TO AHU-1-8A AND AHU-1-8B.
  
 4) M5.1: THE WIND LOAD ENGINEERING FOR THE RTUIS IS
 INCOMPLETE. PLEASE SHOW HOW THE UNIOTS WILL BE ATTACHED
 TO THE CURBS, AND SUBMIT THE NOA FOR THE THYBAR CURB
 WITH SHOP DRAWING APPROVAL BY THE EOR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By ccole Date 2018-01-05 Time 08:38 Rev Time 0.00
Received By ccole Date 2017-12-28 Time 16:34 Sent To  
Notes
2018-01-05 08:38:391ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110860
 1/4/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT
 AS REQUIRED BY SECTION C101.4.3 FBC-14 ENERGY
 CONSERVATION.
  
 2) M1.3: PROVIDE A SCOPE OF WORK FOR THE CHILLER,
 PUMPS, AND ALL OTHER ASSOCIATED EQUIPMENT- EXISTING TO
 REMAIN? PROVIDE A SYMBOL ON THE PLAN THAT INDICATES THE
 POINT OF DEMO FOR THE EXISTING CHILLER PIPING. M4.1:
 PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLER, PUMPS ETC.
  
 3) SHEETS A-101, M1.3 & M2.1: THE GOLF CART STORAGE
 AREA IS CLASSIFIED AS A PARKING GARAGE AND REQUIRES AN
 EXHAUST VENTILATION SYSTEM IN COMPLIANCE WITH SECTION
 404.1 FBC-14 MECHANICAL. PLEASE CLARIFY IF THERE IS AN
 EXISTING SYSTEM THAT IS IN COMPLIANCE, OR REVISE THE
 PLANS TO SHOW ALL PROPOSED ALTERATIONS AND NEW
 INSTALLATIONS.
  
 4) SHEETS A-101, M1.3, & M2.1: PLEASE IDENTIFY ALL
 ROOMS AND SPACES ON THE MECHANICAL PLANS AS THEY ARE
 SHOWN ON THE ARCHITECTURAL PLANS. CLARIFY IF ANY OF THE
 ROOMS ARE USED FOR GOLF CART BATTERY STORAGE AND/OR
 BATTERY RECHARGING. PROVIDE EXHAUST VENTILATION SYSTEMS
 AND CALCULATIONS WHERE REQUIRED BY SECTION 502.
  
 5) M4.1: PLEASE INCLUDE EXHAUST VENTILATION
 CALCULATIONS IN THE VENTILATION SCHEDULE. INDICATE THE
 REQUIRED AND PROVIDED CFMS OF EXHAUST FOR EACH LOCKER
 ROOM, BATHROOM, JANITORS CLOSETS, STORAGE ROOMS ETC.
  
 6) M4.1: SECTION 403.3.2.3.3 NOTED UNDER THE
 VENTILATION SCHEDULE DOES NOT EXIST IN THE FBC-14 FIFTH
 EDITION MECHANICAL CODE- PLEASE CORRECT AND CLARIFY
 WHAT THE 0.5 DIVERSITY FACTOR IS AND HOW IT IS
 APPLICABLE TO THE PROPOSED PROJECT.
  
 7) M2.5: INDICATE HOW ACCESS TO AHU'S 1-8A & 1-8B WILL
 BE PROVIDED- SECTION 306.5.
  
 8) M2.5: THE CONDENSATE PIPING SUPPORTS SHALL BE SPACED
 MINIMUM 4' APART PER TABLE 305.4.
  
 9) M2.5 & M5.1: PROVIDE THE SITE SPECIFIC WIND LOAD
 DESIGN CRITERIA FOR INSTALLATION OF THE ROOF TOP
 SUPPORTS AND EQUIPMENT- SECTION 1609 FBC-14 BUILDING.
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE THYBAR
 CURB WITH SHOP DRAWING APPROVAL STAMP BY THE EOR.
 CLARIFY IF THE RTU ATTACHMENT DETAILS ON M2.1 ARE
 APPLICABLE TO ALL THE ROOFTOP UNITS INCLUDING THE AHU'S
 AND OAU'S, AND
  
 PROVIDE ATTACHMENT AND ANCHORING DETAILS FOR THE
 ROOFTOP DUCTWORK- SECTION 301.15.
  
 10) M2.5: THE FLORIDA PRODUCT APPROVAL #3203.1 FOR THE
 RM ENTERPRISES STAND IS NOT A VALID NUMBER. PLEASE
 PROVIDE THE CORRECT NUMBER AND SUBMIT THE PRODUCT
 APPROVAL WITH ALL APPLICABLE INSTALLATION DETAILS,
 NOTES, DESIGN PRESSURES, FASTENERS ETC. MARKED UP BY
 THE EOR.
  
 11) M7.1: SHOW IN THE CONTROL DIAGRAMS THE LOCATIONS OF
 THE DUCT SMOKE DETECTORS REQUIRED IN THE RETURN AIR
 SYSTEMS- SECTION 606.2.1.
  
 12) M2.1- 2.2, 2.3, & 2.4: SHOW THE LOCATIONS OF CO2
 SENSORS WHERE REQUIRED BY SECTION C403.2.5.1 AND IN
 ACCORDANCE WITH THE CONTROL DIAGRAMS ON M7.1.
  
 13) PROVIDE CHILLER PIPING AND PIPING INSULATION
 SPECIFICATIONS AND INSTALLATION, SUPPORT, AND HANGING
 DETAILS.
  
 14) CLEAR ACCESS TO THE ABOVE CEILING VAV BOXES AND
 EXHAUST FANS IS REQUIRED. SHOW THE LOCATIONS OF ANY
 REQUIRED ACCESS PANELS AND PROVIDE CONSTRUCTION
 DETAILS- SECTION 306.1.
  
 15) SHEET FG0.1: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 16) FG1.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED WATER HEATERS, AND PROVIDE COMBUSTION AIR
 CALCULATIONS AND VENTING PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 09:29 Rev Time 0.00
Received By gjohnson Date 2018-04-06 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-16 Cont ID  
Sent By gjohnson Date 2018-03-16 Time 14:19 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 09:28 Sent To  
Notes
2018-03-16 14:20:17 
 2ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 COMMENT 4: THE LOCKER ROOMS SHALL BE PROVIDED WITH A
 WATER FOUNTAIN PER FBC PL TABLE 403.1 AND 410.
  
 RESPONSE: PER FBC PL 403.1, TWO DRINKING FOUNTAINS ARE
 REQUIRED, PER PBC PL 410; A HI-LOW DRINKING FOUNTAIN IS
 COUNTED AS TWO DRINKING FOUNTAINS. THERE IS A HI-LOW
 DRINKING FOUNTAIN LOCATED IN KITCHEN 2004 OUTSIDE OF
 STAFF DINING 2015. THE MEN?S AND WOMEN?S LOCKER ROOMS
 HAVE FULL-TIME ATTENDANTS (ROOMS 2081 & 2049) WHICH
 CATER TO THOSE IN THE LOCKER ROOMS. A) WILL
 THE OCCUPANTS FROM THE LOCKER ROOMS HAVE ACCESS TO THE
 WATER FOUNTAIN IN THE KITCHEN MOST COMMERCIAL KITCHENS
 DON?T ALLOW GUEST TO ENTER, IF NOT THAN A WATER
 FOUNTAIN SHALL BE PROVIDED FOR THE OCCUPANTS THE FACT
 THAT THERE IS AN ATTENDANT DOES NOT COMPLY WITH THE
 CODE. PER FBC PL TABLE 403.1 AND 410
  
  COMMENT 7: SHT. A-505, 506 ALL TRANSFER TYPE SHOWERS
 SHALL SHOW INSIDE DIMENSIONS OF 36"X36". SOME OF THE
 DIMENSIONS ON THE PLAN DO NOT COMPLY. PLEASE CLARIFY
 PER FBC ACC 608.2.1.
  
 RESPONSE: ONLY SHOWERS 2060, 2061, AND 2075 ARE
 ACCESSIBLE SHOWERS. SEE REV.1 DRAWING SHEET A-506.
 A) THE DIMENSIONS ARE STILL SHOWN AT 39-1/4? WIDE AND
 37? DEEP PLEASE CLARIFY.
  
  
 COMMENT 8: PLEASE SHOW THE DIMENSIONS OF THE HEIGHT OF
 THE RIM AND THE CLEARANCE FOR KNEE AND TOE CLEARANCE
 FOR THE LAVATORY IN BATHROOMS 2054, 2081, 2027, 2041,
 AND 2049 PER FBC ACC 213.3.4, 606.
  
 RESPONSE: SEE DETAIL 10 ON REV.1 DRAWING SHEET A-905.
 A) THE DETAIL DOES NOT SHOW THE REQUIRED KNEE AND TOE
 CLEARANCE, PLEASE SHOW CLEAR FLOOR SPACE. PER FBC ACC
 306
  
 COMMENT 10: THE PLUMBING SHEETS SHOW THE ROOM NUMBERS
 IN THE 1000'S AND THE ARCHITECTURAL SHEETS SHOW THEM IN
 THE 2000'S. PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1.
  
 RESPONSE: ROOM NUMBERS ON ALL PLUMBING SHEETS HAVE BEEN
 UPDATED TO MATCH THE ARCHITECTURAL NUMERICAL ORDER AS
 PER FBC 107.2.1.
 A) THE ROOM NUMBER ON THE PLUMBING SHEETS ARE STILL
 SHOWN AS 2000?S
  
 NEW COMMENTS:
  
 1. SHT. P7.1 DETAIL #12 AND 13 THE COLD WATER SUPPLY IS
 SHOWN CONNECTING TO INLET OF THE STORAGE TANK AND
 OUTLET OF THE BOILER THE COLD SHOULD BE CONNECTED TO
 THE INLET OF THE BOILER PROVIDE THE MANUFACTURES
 INSTILLATION GUIDE TO VERIFY. PER WBP AMEND TO FBC
 107.2.1.
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR PLEASE PLEASE NOTE ON PLAN. PER WBP AMEND
 TO FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By gjohnson Date 2018-01-17 Time 08:36 Rev Time 0.00
Received By gjohnson Date 2018-01-10 Time 17:53 Sent To  
Notes
2018-01-12 16:09:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS PROJECT IS REQUIRED TO COMPLY WITH FBC PL
 403.1.3 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
  
 2. THE BATHROOM 2014 IN THE KITCHEN SHALL NOT OPEN
 DIRECTLY INTO THE KITCHEN PER FBC PL 403.3.2
  
 3. AT LEAST ONE TOILET COMMITMENT IN THE LOCKER-ROOM
 BATHROOMS SHALL COMPLY WITH THE REQUIREMENTS OF AN
 AMBULATORY STALL PER FBC ACC 213.3.1 AND 604.8.2
  
 4. THE LOCKER ROOMS SHALL BE PROVIDED WITH A WATER
 FOUNTAIN PER FBC PL TABLE 403.1 AND 410
  
 5. SHT. A-903 THE SHOWER STALL DETAIL (36"X36") NOTES
 THE LOWEST POINT OF MOUNTING AT 48" THE CODE STATES 38"
 MIN 48" MAX PLEASE CLARIFY. PER FBC ACC 608.5.1
  
 6. SHT. A-504, 505, 506 PLEASE SHOW THE REQUIRED CLEAR
 FLOOR SPACE FOR THE ACCESSIBLE FIXTURES PLEASE INCLUDE
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. A-505, 506 ALL TRANSFER TYPE SHOWERS SHALL SHOW
 INSIDE DIMENSIONS OF 36"X36" SOME OF THE DIMENSIONS ON
 THE PLAN DO NOT COMPLY PLEASE CLARIFY. PER FBC ACC
 608.2.1
  
 8. PLEASE SHOW THE DIMENSIONS OF THE HEIGHT OF THE RIM
 AND THE CLEARANCE FOR KNEE AND TOE CLEARANCE FOR THE
 LAVATORY,S IN BATHROOMS 2054, 2081, 2027, 2041, 2049
 PER FBC ACC 213.3.4, 606
  
 9. SHT P-2.4, 3.4, 3.6 IN ROOMS 1049 AND 1081 THE
 SANITARY AND WATER PIPING IS SHOWN IN A DIFFERENT
 LOCATION AS THE FIXTURES ARE SHOWN IN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 10. THE PLUMBING SHEETS SHOW THE ROOM NUMBERS IN THE
 1000'S AND THE ARCHITECTURAL SHEETS SHOW THEM IN THE
 2000'S PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 11. SHT. G-001 UNDER THE SHEET INDEX THE FIRE SPRINKLER
 PLANS ARE LISTED UNDER THE FUEL GAS AND THE FUEL GAS
 SHEETS ARE NOT LISTED IN THE INDEX PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 12. THE FFD-1 OUTSIDE THE KEG COOLER APPEARS TO BE ON
 THE EXTERIOR OF THE BUILDING, HOW WILL IT BE COVERED TO
 PREVENT RAIN WATER FROM DISCHARGING INTO THE SANITARY
 SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 13. PLEASE PROVIDE A KITCHEN EQUIPMENT PLAN WITH
 SCHEDULE. PER WPB AMEND TO FBC 107.2.1
  
 14. THE FLOOR SINK FOR THE ICE MACHINE SHALL DISCHARGE
 TO THE SANITARY NOT THE GREASE. PER FBC PL 1003.2
  
 15. THE HCWC AND THE HCSH ARE NOT VENTED PROPERLY THEY
 SHOULD BE VENTED AS A WET VENT OR INDIVIDUAL VENT. PER
 FBC PL 901.2.1, 910.1, 912.1
  
 16. SHT. P-5.1, 5.2 PLEASE IDENTIFY AND LABEL EACH
 RISER AND STACK WITH A NUMBER OR LETTER SYSTEM .PER WPB
 AMEND TO FBC 107.2.1
  
 17. SHT. P5.2 PROVIDE VALVES FOR ALL DROPS AND HOSE
 BIBS. PER FBC PL 606.1, 606.2
  
 18. SHT. P-5.2 PLEASE SIZE THE BRANCHES OR STUB OUTS ON
 FIXTURES. PER WPB AMEND TO FBC 107.2.1
  
 19. LAVS ARE REQUIRED TO HAVE TEMPERED WATER ONLY BUT
 THE JANITORS SINK IS REQUIRED TO HAVE HOT WATER. EACH
 LAV SHOULD BE EQUIPPED WITH A WATER TEMPERATURE
 LIMITING DEVISE PER FBC PL ,416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 607.1 IN NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE
 SUPPLIED FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR
 BUILDING MAINTENANCE PURPOSES.
  
 20. SHT. P-6.1 THE LOCATION OF THE ROOF DRAINS AND
 PIPING IS SHOWN IN A DIFFERENT LOCATION AS THE
 ARCHITECTURAL PLAN SHOWS PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 21. SHT. P6.1 IS ANY OF THE SLOPED TILE ROOF DRAINING
 ONTO THE FLAT ROOF IF SO IS THE SQFT INCLUDED IN THE
 SIZING CALCULATIONS. PER WPB AMEND TO FBC 107.2.1
  
 22. SHT. P6.2 NOTE #1 STATES THE NEW 4" STORM IS TO
 CONNECT TO EXISTING 4" STORM PLEASE PROVIDE EXISTING
 LOAD THAT THE NEW LOAD IS BEING ADDED TO. PER WPB AMEND
 TO FBC 107.2.1
  
 23. SHT.P7.1 DETAIL #9 THE SAMPLING PORT SHALL NO BE A
 DOUBLE SANITARY TEE WITH A CAP ON THE BOTTOM IT SHALL
 BE A MIN OF A 4" TWO WAT CLEAN OUT OR A PREMANUFACTURED
 SAMPLING PORT. PER WPB UTILITIES DEPT.
  
 24. SHT. P7.1 WILL BOTH WATER HEATERS HAVE THE
 THERMOSTATIC MIXING VALVE WITH 110 DEG. AND 140 DEG.
 LINES THE GWH2 APPEARS ONLY TO HAVE A SINGLE HOT LINE
 PLEASE CLARIFY AND PROVIDE SEPARATE DETAIL IF NEEDED.
 PER WPB AMEND TO FBC 107.2.1
  
 25. EXISTING GREASE INTERCEPTOR SHALL BE CERTIFIED THAT
 IT IS IN GOOD WORKING ORDER PROVIDE NOTE ON PLAN AND
 CONTACT WPB UTILITIES DEPT FOR INSPECTION DETAILS . PER
 PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2018-10-15 Cont ID  
Sent By gjohnson Date 2018-10-15 Time 09:36 Rev Time 0.00
Received By gjohnson Date 2018-10-15 Time 09:36 Sent To  
Notes
2018-10-15 09:39:26APPROVED FOR UNDER COUNTER GREASE INTERCEPTER ZURN
 GT2701-20 IN MEMBERS BAR AREA.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2018-03-16 Cont ID  
Sent By gjohnson Date 2018-03-16 Time 15:02 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 15:01 Sent To  
Notes
2018-10-15 09:40:26APPROVED FOR MAIN GREASE INTERCETORS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-04-11 Cont ID  
Sent By lmarchan Date 2018-04-11 Time 07:59 Rev Time 0.00
Received By lmarchan Date 2018-04-11 Time 07:59 Sent To  
Notes
2018-04-10 11:23:33MECH SIGS GOOD
2018-04-06 09:33:124/6/18 THE DIG SIG ON PLUMB SHEETS OK/GPJ
2018-04-04 11:27:03ARCHITECTURAL AND STRUCTURAL SHEETS CHECKED FOR
 ELECTRONIC SIGNATURES, OK/ 04/04/2018. J. W.
2017-12-28 16:49:57MECH GOOD- CCOLE-12/28/17

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-02-13 Cont ID  
Sent By jwitmer Date 2018-02-13 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2018-02-13 Time 08:35 Sent To  
Notes
2018-02-13 08:37:06DATE: 02/13/2018
 RECEIVED ALL OF THE THRESHOLD DOCUMENTS GOOD TO GO!
 DOCUMENTS FILED UNDER BUILDING PERMIT 17110860 / PAPER/
 DIGITAL PLAN!
 SPECIAL INSPECTION PLAN SEE SHEET S0.3.
 KEN CONRAD RECEIVED COPY 02/13/2018.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jwitmer Date 2017-12-22 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2017-12-22 Time 13:47 Sent To  
Notes
2017-12-22 13:48:362014 FBC-THRESHOLD BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110860
 ADD: 1901 VILLAGE BLVD. / BEAR LAKES COUNTRY CLUB
 CONT: MOUW ASSOCIATES, INC.
 TEL: 561-276-9640
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 22/2018
 ACTION: DENIED
  
 1) PLEASE NOTE THIS BUILDING IS CONSIDERED A THRESHOLD
 BUILDING. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 THE THRESHOLD INSPECTIONS FORMS WERE E-MAILED TO:
 [email protected] 12/21/17 01:20 PM.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-04-02 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-02 Time 10:26 Sent To  
Notes
2018-04-02 10:27:25ALL REQUIRED SITE AND LANDSCAPE IMPROVEMENTS REQUIRED
 PRIOR TO C.O.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-03-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-19 Time 10:37 Sent To  
Notes
2018-03-19 10:37:35REFERENCE APPROVED SITE PLAN (MINOR PD AMENDMENT). ALL
 REQUIRED SITE IMPROVEMENTS MUST BE COMPLETE PRIOR TO
 C.O. FOR COUNTRY CLUB.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-12-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-12-22 Time 16:31 Sent To  
Notes