Plan Review Details - Permit 17110790
Plan Review Stops For Permit 17110790
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2018-08-03 Cont ID  
Sent By dbattles Date 2018-08-03 Time 15:14 Rev Time 0.00
Received By dbattles Date 2018-08-03 Time 15:14 Sent To  
Notes
2018-08-03 15:18:39STEVEN PUT ADDRESS IN SYSTEM 1990 AUGUSTINE RD.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By aclange Date 2018-04-02 Time 13:06 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 13:06 Sent To  
Notes
2018-04-02 13:07:12SEE BUILDING REVIEW NOTES REGARDING ADDRESSING.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By skennedy Date 2018-01-04 Time 09:42 Rev Time 0.00
Received By skennedy Date 2018-01-04 Time 09:42 Sent To  
Notes
2018-01-04 09:50:221ST REVIEW FBC 2014 EXISTING BUILDING
  
 VERIFY ADDRESS IS CORRECT WITH MICHAEL ORIO.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-12-05 Cont ID  
Sent By dbattles Date 2018-12-05 Time 08:57 Rev Time 0.00
Received By dbattles Date 2018-12-05 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-03 Cont ID  
Sent By dbattles Date 2018-08-03 Time 15:19 Rev Time 0.00
Received By dbattles Date 2018-08-03 Time 15:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By aclange Date 2018-04-02 Time 13:06 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 10:11 Sent To  
Notes
2018-04-02 13:05:54****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 SECOND REVIEW:
  
  
 PARTIALLY COMPLIED, ELEVATION CERTIFICATES PROVIDED HAS
 NOT BEEN SEALED. CONFIRM THAT THESE ARE FOR THE CORRECT
 BUILDING. THERE IS A NOTE THAT THESE ARE FOR THE TRASH
 COMPACTOR.
 1. THE FLOOD ZONE MAPS WERE UPDATED OCTOBER 5, 2017.
 PLEASE UPDATE THE SURVEY AND PLANS TO NAV 88.
 AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FREE BOARD DESIGN FLOOD
 ELEVATION.
  
 NOT ADDRESSED
 2. PROVIDE PRODUCT APPROVAL FOR ROOFING MATERIALS.
 PROVIDE TRUSS FRAMING ENGINEERING.
  
 IF YOU ELECT TO DO THESE AS DEFERRED SUBMITTALS INCLUDE
 THESE ON THE COVER SHEET.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLANS SUBMITTED INCLUDE ADDITIONAL PAGES FOR A TRASH
 COMPACTOR. THIS IS UNDER A SEPERATE PERMIT. REMOVE
 THESE PAGES.
 3. ONLY ONE SET OF PLANS PROVIDED. TWO ARE REQUIRED. IF
 YOU GO WITH PRIVATE PROVIDER 3 COPIES ARE REQUIRED. IF
 YOU ELECT TO DO PRIVATE PROVIDER INSPECTIONS, PLEASE
 PROVIDE THE NOTICE TO BUILDING OFFICIAL FORM
 61G20-2.005-2002-01 BEFORE PERMITTING.
  
 NOT ADDRESSED.
 4. PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE BUS
 SHELTER TO THE ADJACENT SIDEWALK. FL ACCESSIBILITY 402
 AND 403.
  
 5. NEW COMMENT: THE ADDRESSING ON THE RESUBMITTAL HAS
 CHANGED. THE BUS SHELTER IS ON OKEECHOBEE BLVD. SOME OF
 THE PAGES SHOW 1990 AGUSTINE RD.
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
  
 6. THERE IS A NOTE IN OUR SYSTEM REGARDING PRIVATE
 PROVIDER INSPECTIONS. IF YOU ELECT TO DO THIS WE WILL
 NEED 3 SETS OF PLANS FOR REVIEW. ADDITIONALLY WE WILL
 NEED AN APPLICATION FOR PRIVATE PROVIDER INSPECTIONS
 ALONG WITH THE SUPPORTING DOCUMENTS.
 IF YOU NEED THIS APPLICATION CONTACT ME AND I CAN EMAIL
 IT TO YOU. NOTE: IF YOU DECIDE TO GO WITH PRIVATE
 PROVIDER IT COULD TAKE SEVERAL DAYS TO PROCESS SINCE I
 REVIEW IT FIRST
 AND THEN IT NEEDS APPROVAL FROM THE BUILDING OFFICIAL.
  
 7. NEW COMMENT:
 REPEAT REVIEWS FOR THE SAME COMMENTS.
  
 F.S. 553.80 (2) (B)
 (B) WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-20 Cont ID  
Sent By aclange Date 2017-12-20 Time 15:01 Rev Time 0.00
Received By aclange Date 2017-12-20 Time 11:19 Sent To E
Notes
2017-12-20 15:00:41****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. THE FLOOD ZONE MAPS WERE UPDATED OCTOBER 5, 2017.
 PLEASE UPDATE THE SURVEY AND PLANS TO NAV 88.
 AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FREE BOARD DESIGN FLOOD
 ELEVATION.
  
 2. PROVIDE PRODUCT APPROVAL FOR ROOFING MATERIALS.
 PROVIDE TRUSS FRAMING ENGINEERING.
  
 IF YOU ELECT TO DO THESE AS DEFERRED SUBMITTALS INCLUDE
 THESE ON THE COVER SHEET.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. ONLY ONE SET OF PLANS PROVIDED. TWO ARE REQUIRED. IF
 YOU GO WITH PRIVATE PROVIDER 3 COPIES ARE REQUIRED. IF
 YOU ELECT TO DO PRIVATE PROVIDER INSPECTIONS, PLEASE
 PROVIDE THE NOTICE TO BUILDING OFFICIAL FORM
 61G20-2.005-2002-01 BEFORE PERMITTING.
  
 4. PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE BUS
 SHELTER TO THE ADJACENT SIDEWALK. FL ACCESSIBILITY 402
 AND 403.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By jpearson Date 2018-07-24 Time 15:47 Rev Time 0.00
Received By jpearson Date 2018-07-24 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By jpearson Date 2018-04-09 Time 13:53 Rev Time 0.00
Received By jpearson Date 2018-04-09 Time 12:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By jpearson Date 2017-12-21 Time 07:42 Rev Time 0.00
Received By jpearson Date 2017-12-21 Time 07:42 Sent To ENG
Notes
2017-12-21 07:42:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO PANEL.
 SHOW GEC SIZE AND SYSTEM. DOES THIS HAVE ITS OWN
 SERVICE, OR FED FROM SOMEWHERE ELSE? PROVIDE DETAILS.
 FBC 107.2.1; NEC 215.5, 230, 250.50, 250.94, 408.30
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 3. PROVIDE AUTOMATIC LIGHTING CONTROLS REQUIRED PER
 ENERGY CODE. "LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME
 SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10
 HOURS." FBC EC 405.2.4
  
 A COMPLETE REVIEW COULD NOT BE COMPLETED AT THIS TIME
 DUE TO LACK OF INFORMATION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2018-12-03 Cont ID  
Sent By RRossano Date 2018-12-03 Time   Rev Time 0.00
Received By rrossano Date 2018-12-03 Time   Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2018-09-11 Cont ID  
Sent By RRossano Date 2018-09-11 Time   Rev Time 1.00
Received By rrossano Date 2018-09-11 Time   Sent To I
Notes
2018-09-11 08:47:48PLEASE ADDRESS ZONING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2018-08-24 Cont ID  
Sent By shill Date 2018-08-24 Time 15:38 Rev Time 0.00
Received By shill Date 2018-08-24 Time 15:38 Sent To  
Notes
2018-08-24 15:38:39CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 10:16 Rev Time 0.00
Received By shill Date 2018-04-21 Time 10:16 Sent To  
Notes
2018-04-21 10:16:39CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By squinone Date 2017-12-22 Time   Rev Time 0.00
Received By squinone Date 2017-12-22 Time   Sent To I
Notes
2017-12-22 08:18:301) ADDRESS ZONING COMMENTS.
 2) ADVISORY: WILL A CROSS DRAIN BE REQUIRED FOR THE
 5-FT SIDEWALK WITHIN THE EXISTING SWALE? PLEASE,
 ADDRESS COMMENT WITH FDOT.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-12-05 Cont ID  
Sent By dbattles Date 2018-12-05 Time 08:58 Rev Time 0.00
Received By dbattles Date 2018-11-05 Time 10:09 Sent To  
Notes
2018-11-07 10:09:26RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-11 Cont ID  
Sent By cpuell Date 2018-09-11 Time 12:41 Rev Time 0.00
Received By cpuell Date 2018-08-28 Time 14:50 Sent To  
Notes
2018-08-29 14:50:17RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-24 Cont ID  
Sent By shill Date 2018-08-24 Time 15:38 Rev Time 0.00
Received By shill Date 2018-07-02 Time 15:06 Sent To  
Notes
2018-07-03 15:06:42B30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-02 Cont ID  
Sent By cpuell Date 2018-05-02 Time 11:28 Rev Time 0.00
Received By cpuell Date 2018-03-27 Time 15:13 Sent To  
Notes
2018-03-28 15:13:56B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-22 Cont ID  
Sent By lmarchan Date 2017-12-22 Time 15:45 Rev Time 0.00
Received By lmarchan Date 2017-11-20 Time 13:47 Sent To  
Notes
2017-12-13 15:16:0312/13 REMOVED FROM ENGINEERING BOX, ROUTED TO A.LANGE
 DESK
  
  
2017-11-21 13:47:24ROUTED TO ZONING

Review Stop Z ZONING
Rev No 5 Status P Date   Cont ID  
Sent By AH Date 2018-11-30 Time   Rev Time 0.00
Received By ahansen Date 2018-11-30 Time 16:01 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2018-09-07 Cont ID  
Sent By A.Hansen Date 2018-09-07 Time   Rev Time 0.00
Received By ahansen Date 2018-09-07 Time 15:06 Sent To ENG
Notes
2018-09-07 15:09:36THE PERMIT PLAN DID NOT ADDRESS THE COMMENTS PROVIDED
 IN THE PREVIOUS REVIEW. THE PROPOSED BIKE PAD/SHELTER
 CONFIGURATION DOES NOT FUNCTION ADEQUATELY. IN
 ADDITION, THE PERMIT PLAN IS INCONSISTENT WITH THE
 APPROVED SITE PLAN AND LANDSCAPE PLAN.

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By A.Hansen Date 2018-07-13 Time   Rev Time 0.00
Received By ahansen Date 2018-07-13 Time 15:04 Sent To I
Notes
2018-07-13 15:04:1207-13-18 BY AH; THE PERMIT PLANS ARE NOT CONSISTENT
 WITH THE SITE PLAN AND LANDSCAPE PLAN APPROVED ON
 4/12/18. THIS INCLUDES INCONSISTENCIES BETWEEN THE
 PLANS FOR THE BIKE PARKING LOCATED ALONG WITH THE
 PROPOSED BUS SHELTER. PLEASE NOTE THAT THIS IS A REPEAT
 COMMENT FROM THE REVIEW COMPLETED ON 5/1/18.
  
 ALSO AS A REMINDER NOTE, THE MINOR PD AMENDMENT
 APPROVAL LETTER ISSUED ON 4/12/18 STATES UNDER
 CONDITION NUMBER FOUR (4) THAT:
 "PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY FOR THE PROJECT, THE APPLICANT SHALL
 CONSTRUCT THE PEDESTRIAN CONNECTION BETWEEN THE SCHOOL
 BUS SHELTER AND OKEECHOBEE BOULEVARD. A PERMIT FROM
 FDOT SHALL BE REQUIRED FOR CONSTRUCTION OF THIS
 CONNECTION ON OKEECHOBEE BOULEVARD."
  
 SENT TO INCOMING/PROCESSING

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-01 Cont ID  
Sent By Alex H Date 2018-05-01 Time   Rev Time 0.00
Received By ahansen Date 2018-05-01 Time 16:42 Sent To I
Notes
2018-05-01 16:46:1805-01-18 BY AH; THE PERMIT PLANS DO NOT INCLUDE AND ARE
 NOT CONSISTENT WITH THE SITE PLAN AND LANDSCAPE PLAN
 APPROVED ON 4/12/18. THIS INCLUDES INCONSISTENCIES
 BETWEEN THE PLANS FOR THE BIKE PARKING LOCATED ALONG
 WITH THE PROPOSED BUS SHELTER. SENT TO
 INCOMING/PROCESSING

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-07 Cont ID  
Sent By AH Date 2017-12-07 Time 15:41 Rev Time 0.00
Received By ahansen Date 2017-12-07 Time 15:40 Sent To ENG
Notes
2017-12-07 15:39:53THE PLANS NEED TO SHOW HOW THE CONCRETE PAD FOR THE BUS
 SHELTER WILL PROVIDE ADA-COMPLIANT ACCESS TO PUBLICALLY
 ACCESSIBLE SIDEWALKS. IN ADDITION, THE APPROVAL LETTER
 FOR THE BELLA VITA MINOR SITE PLAN AMENDMENT ISSUED ON
 OCTOBER 26, 2017 INCLUDES THE FOLLOWING CONDITION OF
 APPROVAL:
 "5. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT
 FOR THE PROJECT, THE LANDSCAPE PLAN, SITE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS SHALL BE REVISED
 TO RELOCATE THE CURBS TO THE POSITION OF THE WHEEL
 STOPS AND PROVIDE A LANDSCAPED OVERHANG WHERE POSSIBLE
 WITHIN THE PARKING AREAS TO PROVIDE MORE PERVIOUS
 LANDSCAPE AREA. THE DESIGN SHALL FOLLOW THE TYPICAL
 PARKING STALL LAYOUT AS SHOWN ON THE APPROVED PLANS. A
 MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE REQUIRED TO
 REFLECT ANY REVISIONS TO THE PLANS."
 SINCE NO REVISED SITE PLAN, LANDSCAPE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS CONSISTENT WITH
 THE ABOVE CONDITION HAVE BEEN SUBMITTED, THE BUILDING
 PLANS INCLUDED IN THIS PERMIT CANNOT BE APPROVED.
  