Plan Review Details - Permit 17110789
Plan Review Stops For Permit 17110789
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By skennedy Date 2018-08-01 Time 10:16 Rev Time 0.00
Received By skennedy Date 2018-08-01 Time 10:16 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-04-02 Cont ID  
Sent By aclange Date 2018-04-02 Time 14:44 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 14:44 Sent To  
Notes
2018-04-02 14:45:27CONTACT MICHAEL REGARDING THE ADDRESSING FOR THIS
 PROPERTY.
  
  
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-31 Cont ID  
Sent By dbattles Date 2018-07-31 Time 15:12 Rev Time 0.00
Received By dbattles Date 2018-07-31 Time 13:44 Sent To  
Notes
2018-07-31 15:15:08DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 PROVISO:
 [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL,
 PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471
 OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND
 ISSUED BY THE CITY OF WEST PALM BEACH. SUBJECT TO THE
 INSPECTOR?S DISCRETION, THIS MAY BE ACCEPTED IN THE
 FIELD AT TIME OF INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By aclange Date 2018-04-02 Time 14:43 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 14:11 Sent To  
Notes
2018-04-02 14:43:30****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 AZOLA TRASH COMPACTOR 17110789
  
 SECOND REVIEW:
  
 NEW COMMENTS:
  
 A) THIS APPLICATION IS FOR A TRASH ENCLOSURE AND
 COMPACTOR. A COMPLETE SET OF CIVIL PLANS HAVE BEEN
 SUBMITTED ALONG WITH THE BUS ENCLOSURE PLANS. THE
 TRANSMITTLE LETTER ATTACHED IS FOR THE BUS ENCLOSURE.
  
 B) NEW COMMENT: THE ADDRESSING ON THE RESUBMITTAL HAS
 CHANGED.
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
  
 C) PRIVATE PROVIDER:
 THERE IS A NOTE IN OUR SYSTEM REGARDING PRIVATE
 PROVIDER INSPECTIONS. IF YOU ELECT TO DO THIS WE WILL
 NEED 3 SETS OF PLANS FOR REVIEW. ADDITIONALLY WE WILL
 NEED AN APPLICATION FOR PRIVATE PROVIDER INSPECTIONS
 ALONG WITH THE SUPPORTING DOCUMENTS.
 IF YOU NEED THIS APPLICATION CONTACT ME AND I CAN EMAIL
 IT TO YOU. NOTE: IF YOU DECIDE TO GO WITH PRIVATE
 PROVIDER IT COULD TAKE SEVERAL DAYS TO PROCESS SINCE I
 REVIEW IT FIRST
 AND THEN IT NEEDS APPROVAL FROM THE BUILDING OFFICIAL.
  
 D) NEW COMMENT:
  
 REPEAT REVIEWS FOR THE SAME COMMENTS.
  
 F.S. 553.80 (2) (B)
 (B) WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 FIRST REVIEW
  
  
 1. THIS PROPERTY IS IN FLOOD ZONE A.
  
 FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016, AFTER
 OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE BOARD WILL
 BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 FBC 1612.1 GENERAL.
  
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 AFTER OCTOBER 5TH 2017 THE NGVD HAS BEEN UPDATED TO
 NAVD88. PLEASE UPDATE THE PLANS TO REFLECT THIS AS WELL
 AS THE NEW FREE BOARD.
  
 FBC 1612.4 DESIGN AND CONSTRUCTION.
  
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  
 2. STRUCTURAL CALCULATIONS:
  
 (A) CODE REFERENCES SHOWN ARE FOR IBC 2015. AT TIME OF
 SUBMITTING THE CURRENT CODE IS FBC 2014 5TH EDITION.
  
 (B) BASIC WIND SPEED SHOWN IS 165.00 MPH. SEE FBC
 FIGURE 1609C AND FBC 1609.3 BASIC WIND SPEED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By aclange Date 2017-12-22 Time 09:29 Rev Time 0.00
Received By aclange Date 2017-12-22 Time 07:32 Sent To E
Notes
2017-12-22 09:29:45****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 AZOLA TRASH COMPACTOR 17110789
  
 1. THIS PROPERTY IS IN FLOOD ZONE A.
  
 FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016, AFTER
 OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE BOARD WILL
 BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 FBC 1612.1 GENERAL.
  
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 AFTER OCTOBER 5TH 2017 THE NGVD HAS BEEN UPDATED TO
 NAVD88. PLEASE UPDATE THE PLANS TO REFLECT THIS AS WELL
 AS THE NEW FREE BOARD.
  
 FBC 1612.4 DESIGN AND CONSTRUCTION.
  
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  
 2. STRUCTURAL CALCULATIONS:
  
 (A) CODE REFERENCES SHOWN ARE FOR IBC 2015. AT TIME OF
 SUBMITTING THE CURRENT CODE IS FBC 2014 5TH EDITION.
  
 (B) BASIC WIND SPEED SHOWN IS 165.00 MPH. SEE FBC
 FIGURE 1609C AND FBC 1609.3 BASIC WIND SPEED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By jpearson Date 2018-07-24 Time 16:00 Rev Time 0.00
Received By jpearson Date 2018-07-24 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By jpearson Date 2018-04-09 Time 12:32 Rev Time 0.00
Received By jpearson Date 2018-04-09 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 11:05 Rev Time 0.00
Received By jpearson Date 2017-12-22 Time 11:05 Sent To ENG
Notes
2017-12-22 11:05:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2018-07-31 Cont ID  
Sent By dbattles Date 2018-08-01 Time 13:04 Rev Time 0.00
Received By skennedy Date 2018-07-31 Time 15:25 Sent To  
Notes
2018-08-01 13:06:331) UNDER REVIEW THROUGH ENGINEERING DEVELOPMENT
 APPROVAL PERMIT NO. E17110029.
  
2018-07-31 15:27:28DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 PREVIOUS COMMENT STATED THAT ENGINEERING APPROVAL WAS
 NEEDED PRIOR TO PERMIT ISSUANCE.
 I DIDN'T SEE A COMMENT RESPONSE SHEET, SO I DON'T KNOW
 IF APPROVAL WAS GIVEN.
 PLEASE PROVIDE STATUS OF ENGINEERING.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 10:19 Rev Time 0.00
Received By shill Date 2018-04-21 Time 10:19 Sent To  
Notes
2018-04-21 10:19:56CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By squinone Date 2018-01-02 Time   Rev Time 0.00
Received By squinone Date 2018-01-02 Time   Sent To I
Notes
2018-01-02 11:55:101) UNDER REVIEW THROUGH ENGINEERING DEVELOPMENT
 APPROVAL PERMIT NO. E17110029.
 2) ADDRESS BUILDING AND ZONING COMMENTS.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-01 Cont ID  
Sent By skennedy Date 2018-08-01 Time 13:06 Rev Time 0.00
Received By skennedy Date 2018-07-02 Time 15:03 Sent To  
Notes
2018-07-03 15:04:07B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-03 Cont ID  
Sent By cpuell Date 2018-05-03 Time 11:42 Rev Time 0.00
Received By cpuell Date 2018-03-27 Time 15:18 Sent To  
Notes
2018-03-28 15:18:31B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-03 Cont ID  
Sent By cpuell Date 2018-01-03 Time 09:09 Rev Time 0.00
Received By cpuell Date 2017-11-17 Time 13:46 Sent To  
Notes
2017-12-13 15:23:5512/13 REMOVED FROM ENGINEERING BOX AND ROUTED TO
 A.LANGE DESK
  
  
2017-11-21 13:46:22ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-13 Cont ID  
Sent By AH Date 2018-07-13 Time   Rev Time 0.00
Received By ahansen Date 2018-07-13 Time 11:39 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By Alex H Date 2018-05-03 Time   Rev Time 0.00
Received By ahansen Date 2018-05-03 Time 11:27 Sent To I
Notes
2018-05-03 11:29:01AH- THE PERMIT NEEDS TO INCLUDE COPIES OF AND BE
 CONSISTENT WITH THE RECENTLY APPROVED SITE PLAN FOR
 THIS SITE. 5-3-18. SENT TO INTAKE.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-07 Cont ID  
Sent By AH Date 2017-12-07 Time 14:30 Rev Time 0.00
Received By ahansen Date 2017-11-27 Time 16:28 Sent To ENG
Notes
2017-12-07 14:32:11THE APPROVAL LETTER FOR THE BELLA VITA MINOR SITE PLAN
 AMENDMENT ISSUED ON OCTOBER 26, 2017 INCLUDES THE
 FOLLOWING CONDITION OF APPROVAL:
 "5. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT
 FOR THE PROJECT, THE LANDSCAPE PLAN, SITE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS SHALL BE REVISED
 TO RELOCATE THE CURBS TO THE POSITION OF THE WHEEL
 STOPS AND PROVIDE A LANDSCAPED OVERHANG WHERE POSSIBLE
 WITHIN THE PARKING AREAS TO PROVIDE MORE PERVIOUS
 LANDSCAPE AREA. THE DESIGN SHALL FOLLOW THE TYPICAL
 PARKING STALL LAYOUT AS SHOWN ON THE APPROVED PLANS. A
 MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE REQUIRED TO
 REFLECT ANY REVISIONS TO THE PLANS."
  
 SINCE NO REVISED SITE PLAN, LANDSCAPE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS CONSISTENT WITH
 THE ABOVE CONDITION HAVE BEEN SUBMITTED, THE BUILDING
 PLANS INCLUDED IN THIS PERMIT CANNOT BE APPROVED.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved