Plan Review Details - Permit 17110787
Plan Review Stops For Permit 17110787
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 10:29 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 10:29 Sent To  
Notes
2018-03-09 10:30:22PROJECT ADDRESSING IS SHOWN ON THE CIVIL PLANS FOR THIS
 PROJECT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-12-01 Cont ID  
Sent By aclange Date 2017-12-01 Time 13:22 Rev Time 0.00
Received By aclange Date 2017-12-01 Time 13:22 Sent To  
Notes
2017-12-01 13:22:45****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
 AZOLA WEST PALM BEACH ? 17110788
  
 CONTACT MICHEAL ORIO REGARDING ADDRESSING FOR THIS
 PROPERTY.
  
 ADDRESSING:
 . CITY MUNI CODE SEC.78-6 (1-7)
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
 E-MAIL: [email protected]

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 06:26 Rev Time 0.00
Received By shill Date 2018-07-05 Time 06:26 Sent To  
Notes
2018-07-05 06:26:37OK PER EMAIL FROM SYBILLE WELTER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-05 Cont ID  
Sent By shill Date 2018-05-05 Time 13:35 Rev Time 0.00
Received By shill Date 2018-05-05 Time 11:56 Sent To  
Notes
2018-05-05 13:35:57***PROVISOS***
 ***ISSUED AT APPLICANT'S RISK***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 1. ELEVATION CERTIFICATE WAS PROVIDED. SURVEYOR STATES
 THIS IS IN AN X ZONE. SITE PLAN AND SURVEY DO NOT SHOW
 THE LOCATION OF THE PROPOSED SALES TRAILER RELATIVE TO
 THE FLOOD BOUNDARY LINE AROUND THE EXISTING POND. IF
 THIS REVISION IS NOT PROVIDED, THIS STRUCTURE WILL BE
 TREATED AS IF IN THE SPECIAL FLOOD HAZARD AREA. TWO
 ADDITIONAL ELEVATION CERTIFICATES ARE REQUIRED:
 A. AFTER FORMING, PRIOR TO CONCRETE POUR, A "BUILDING
 UNDER CONSTRUCTION" ELEVATION CERTIFICATE WITH FORM
 BOARD SURVEY IS REQUIRED
 B. AFTER FINAL GRADING AND INSTALLATION OF ALL
 EQUIPMENT SERVICING THE BUILDING (MECHANICAL, PLUMBING,
 ETC.) BEFORE FINAL INSPECTION A "FINISHED CONSTRUCTION"
 ELEVATION CERTIFICATE AND FINAL TIE IN SURVEY IS
 REQUIRED.
  
 2. EXIT DOORS SHOWN WITH 1/2" CHANGE IN LEVEL;
 COMPLIANCE WITH FBC ACCESSIBILITY 303.3 IS REQUIRED.
 THE NOTE ON SHEET LS0.0 IS NOT CLEAR.
  
 3. ALTHOUGH CIVIL SHEETS HAVE THIS BUILDING LABELED AS
 A "CLUBHOUSE" ALL OTHER SHEETS INDICATE THIS IS A
 LEASING OFFICE. THIS BUILDING HAS BEEN REVIEWED FOR
 BUSINESS OCCUPANCY ONLY. USE AS A CLUBHOUSE REQUIRES A
 CHANGE OF OCCUPANCY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 11:23 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 07:21 Sent To  
Notes
2018-03-09 11:24:16****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 AZOLA WEST PALM BEACH 17110787 LEASING CENTER
  
 SECOND REVIEW:
  
 1. ELEVATION CERTIFICATE NOT PROVIDED.
  
 FLOOD ZONE CERTIFICATES
 FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE.
 AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FREE BOARD, DESIGN FLOOD
 ELEVATION.
 NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS
 HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL
 DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE
 WITH NAV 88.
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS, A/C PADS OR OTHER SLABS FOR GENERATORS.
  
  
 2. OK ADDRESSED
  
 3. OK WILL BE PROCESSED AS A DEFERRED SUBMITTAL.
  
 4. OK ADDRESSED
 5. OK ADDRESSED
 6. OK ADDRESSED
  
 7. OK ADDRESSED
  
 8. OK ADDRESSED
  
 9. OK ADDRESSED
 10. OK ADDRESSED
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-01 Cont ID  
Sent By aclange Date 2017-12-01 Time 13:12 Rev Time 0.00
Received By aclange Date 2017-11-30 Time 16:17 Sent To  
Notes
2017-12-01 13:12:26****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 AZOLA WEST PALM BEACH 17110787 LEASING CENTER
  
 FIRST REVIEW:
  
  
 ART IN PUBLIC PLACES:
  
  
 1. FLOOD ZONE CERTIFICATES
  
 FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE.
 AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FREE BOARD, DESIGN FLOOD
 ELEVATION.
 NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS
 HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL
 DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE
 WITH NAV 88.
  
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
  
 (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
  
 (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS, A/C PADS OR OTHER SLABS FOR GENERATORS.
  
  
 2. PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 3. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS, TRUSS ENGINEERING ETC..
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 NOTE: ON PAGE A2.2 NOTE 4, SHOWS WINDOWS TO BE DONE
 UNDER A SEPERATE PERMIT. SUBMIT PRODUCT APPROVALS AS A
 DEFERRED SUBMITTAL UNDER THIS PERMIT.
  
 4. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR
 BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL
 BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR
 MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT
 THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513,
 FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS
 WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 5. PROVIDE LANDING ON EXTERIOR OF DOORS. THIS IS NOT
 SHOWN ON S.4 CH.1 AND CH.2.
  
 FBC 1008.1.5 FLOOR ELEVATION.
 THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF A
 DOOR. SUCH FLOOR OR LANDING SHALL BE AT THE SAME
 ELEVATION ON EACH SIDE OF THE DOOR. LANDINGS SHALL BE
 LEVEL EXCEPT FOR EXTERIOR LANDINGS, WHICH ARE PERMITTED
 TO HAVE A SLOPE NOT TO EXCEED 0.25 UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE).
  
 6. EXISTING 2 STORY BUILDING TO BE DEMOLISHED REQUIRES
 A SEPERATE DEMO PERMIT. FBC 105.1
  
 7. PARKING DETAILS: PARKING LOT STRIPING DETAILS VARY
 FROM SINGLE TO DOUBLE STRIPING THROUGHOUT THE PLANS.
 WEST PALM BEACH PARKING LOT STRIPING IS DOUBLE
 STRIPING. A DETAIL IS AVAILABLE AT THIS DEPARTMENT.
 NOTE: FC 553.5041(6) HAS CHANGED REGARDING SIGNAGE. THE
 NEW MINIMUM HEIGHT IS 60 INCHES.
  
 8. PROVIDE ELEVATION AT COFFEE BAR. FBC 107.3.5
  
 9. PROVIDE STRUCTURAL DETAILS FOR COVERED PATIO.
 INCLUDE, FOOFINGS, FRAMING AND ANCHORING.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 10. IMPACT FEES:
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-21 Cont ID  
Sent By ppetty Date 2018-05-21 Time 13:42 Rev Time 0.00
Received By ppetty Date 2018-05-21 Time 13:38 Sent To  
Notes
2018-05-21 13:42:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. NEW
 COMMENTS FOLLOW THE ORIGINAL COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
  
 NEW COMMENT:
  
 18. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-03-19 Cont ID  
Sent By jpearson Date 2018-03-19 Time 08:24 Rev Time 0.00
Received By jpearson Date 2018-03-19 Time 08:24 Sent To  
Notes
2018-03-19 07:36:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. NEW
 COMMENTS FOLLOW THE ORIGINAL COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94 (THIS APPLIES TO EVERY SERVICE AND
 MUST BE SHOWN ON PLAN.)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2
 (NOT PROVIDED.)
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
  
 NEW COMMENT:
  
 18. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By jpearson Date 2017-12-19 Time 13:25 Rev Time 0.00
Received By jpearson Date 2017-12-19 Time 13:25 Sent To  
Notes
2017-12-19 12:54:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PANEL H SHOWS A GROUNDING ELECTRODE CONDUCTOR TYING
 INTO THE GROUNDING ELECTRODE SYSTEM. THE GROUNDING
 ELECTRODE CONDUCTORS ARE INSTALLED TO THE MAIN SERVICE
 ONLY. THIS IS NOT LABELED AS A MAIN, AND IS SHOWN BEING
 FED FROM THE 1200 AMP MAIN. CLARIFY AND PROVIDE
 CORRECTION AS NEEDED. NEC 230.2(E), 250.64
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 4. PANEL SCHEDULE FOR PANEL H SHOWS A 1/0 CONDUCTOR ON
 A 175 AMP BREAKER FEEDING THE ELEVATOR. PER CODE, A 1/0
 COPPER CONDUCTOR IS NOT RATED FOR 175 AMPS. PROVIDE
 CORRECTION. PROVIDE CORRECTION. NEC 310.15(B)(16),
 408.30
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. SPECIFY FEEDER SIZES TO THE INDIVIDUAL PANELS ON
 RISER DIAGRAM TO CORRESPOND TO THE VOLTAGE DROP
 REQUIREMENTS STATED ON SHEET E-4.0. FBC 107.2.1
 7. IT APPEARS THAT ALL UNITS IN THIS BUILDING WILL BE
 "A" OR "C" TYPE, BUT THE PLAN SHOWS PANEL SCHEDULES FOR
 "B" TYPE ALSO. REMOVE ANY INFORMATION NOT RELEVANT TO
 THIS PLAN. FBC 107.2.1
 8. SHEET E-4B.1, NOTE 9 IN ELECTRICAL NOTES AND NOTE 6
 IN GENERAL NOTES STATE THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11, WHICH IS NOT THE CORRECT CODE
 SECTION. PROVIDE CORRECTION. ALSO, NOTE 2 STATES
 RECEPTACLES WEATHER PROOF PER NEC 406.8, ALSO WRONG
 CODE SECTION. PROVIDE CORRECTION. NEC 406.9, 406.12;
 FBC 107.2.1
 9. SHEET E-4B.1, NOTE 7 IN GENERAL NOTES STATES THAT
 BREAKERS FEEDING AREAS LISTED IN 250.22 SHALL BE AFCI
 TYPE BREAKERS. CLARIFY WHY 250.22 IS RELATED TO THIS
 CODE REQUIREMENT. PER CODE: "ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION."
 PROVIDE CORRECTION. NEC 210.12
 10. PANEL SCHEDULE FOR PANEL A & C SHOWS THE WATER
 HEATER BREAKER AS A 30 AMP BREAKER. BASED ON THE LOAD
 OF A STANDARD 4500 WATT ELEMENT AT 208 VOLT, THE
 BREAKER SHOULD BE SIZED AT 25 AMP. PROVIDE CORRECTION.
 NEC 422.13
 11. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED, SUCH AS ELECTRIC ROOM,
 ELEVATOR CONTROL ROOM, FIRE ROOM, ETC. FBC EC 405.2.2,
 405.2.2.2
 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. THIS INCLUDES ELECTRIC ROOM AND
 ELEVATOR ROOM CU'S, WHICH ARE NOT CURRENTLY SHOWN ON
 PLAN. SHOW LOCATION OF UNITS AND CORRESPONDING
 RECEPTACLE. NEC 210.63; FBC 107.2.1
 13. FEEDERS FROM FPL TO 1200 AMP MAIN ARE TOO SMALL.
 PLANS SHOWS 4 SETS OF 300 KCMIL AL CONDUCTORS, WHICH
 ARE RATED FOR 920 AMPS. WIRE MUST BE SIZED EQUAL TO OR
 GREATER THAN THE MAIN BREAKER. PROVIDE CORRECTION. NEC
 240.4(C)
 14. UNIT C-1 DOES NOT SHOW THE REQUIRED GFCI RECEPTACLE
 WITHIN 3 FEET OF EACH BASIN IN THE MASTER BATH. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 15. IN UNIT C-1 THERE APPEARS TO BE A KITCHEN ISLAND.
 IF SO, PROVIDE THE REQUIRED GFCI RECEPTACLE. NEC
 210.52(C)(2)
 16. UNIT A-1, THE OUTLET OUTSIDE ON CIRCUIT 16 IS
 REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8, 406.9
 17. UNIT A-2, THE OUTLET OUTSIDE ON CIRCUIT 16 IS
 REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8, 406.9
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2018-05-25 Cont ID  
Sent By shill Date 2018-05-25 Time 13:43 Rev Time 0.00
Received By shill Date 2018-05-25 Time 13:43 Sent To  
Notes
2018-05-25 13:43:11OK PER MG
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-05-14 Cont ID  
Sent By shill Date 2018-05-14 Time 18:47 Rev Time 0.00
Received By shill Date 2018-05-14 Time 18:47 Sent To  
Notes
2018-05-14 18:48:17OK PER MANNY GONZALEZ
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-04-13 Cont ID  
Sent By skennedy Date 2018-04-13 Time 11:39 Rev Time 0.00
Received By skennedy Date 2018-04-13 Time 11:39 Sent To  
Notes
2018-04-13 11:40:05CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-12-18 Time   Rev Time  
Received By   Date 2017-12-18 Time   Sent To  
Notes
2017-12-18 08:29:27CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By sathomas Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-05-07 Cont ID  
Sent By scaldero Date 2018-05-07 Time 13:29 Rev Time 0.00
Received By scaldero Date 2018-05-07 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By pleduc Date 2018-02-22 Time   Rev Time 0.00
Received By pleduc Date 2018-02-22 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-28 Cont ID  
Sent By wjolin Date 2017-11-28 Time 14:57 Rev Time 0.00
Received By wjolin Date 2017-11-28 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-24 Cont ID  
Sent By skennedy Date 2018-05-24 Time 11:26 Rev Time 0.00
Received By skennedy Date 2018-05-01 Time 11:12 Sent To  
Notes
2018-05-02 11:12:47C35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-13 Cont ID  
Sent By cpuell Date 2018-04-13 Time 15:13 Rev Time 0.00
Received By cpuell Date 2018-02-20 Time 13:49 Sent To  
Notes
2018-02-21 13:49:41C34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-02 Cont ID  
Sent By gjohnson Date 2018-01-02 Time 10:58 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 09:22 Sent To  
Notes
2017-11-21 13:49:41C34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-05-09 Cont ID  
Sent By shill Date 2018-05-09 Time 07:08 Rev Time 0.00
Received By shill Date 2018-05-09 Time 07:08 Sent To  
Notes
2018-05-09 07:09:31MU2018-4765
 $4,281.84
 RECEIVED IMPACT FEE RECEIPT VIA EMAIL, ROUTED TO
 RECORDS (VIA EMAIL)
  
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-05-05 Cont ID  
Sent By shill Date 2018-05-05 Time 12:16 Rev Time 0.00
Received By shill Date 2018-05-05 Time 12:12 Sent To  
Notes
2018-05-05 12:13:38MU2018-4765
 $4,281.84
 ***NEED RECEIPT, EMAILED APPLICANT***
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 10:31 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 10:30 Sent To  
Notes
2018-03-09 10:31:17IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-01 Cont ID  
Sent By aclange Date 2017-12-01 Time 13:20 Rev Time 0.00
Received By aclange Date 2017-12-01 Time 13:20 Sent To  
Notes
2017-12-01 13:21:24IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-23 Cont ID  
Sent By skennedy Date 2018-05-23 Time 14:50 Rev Time 0.00
Received By skennedy Date 2018-05-21 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-15 Cont ID  
Sent By ccole Date 2018-03-13 Time 09:27 Rev Time 0.00
Received By ccole Date 2018-03-13 Time 17:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-15 Cont ID  
Sent By ccole Date 2017-12-15 Time 15:34 Rev Time 0.00
Received By ccole Date 2017-12-15 Time 15:34 Sent To  
Notes
2017-12-15 16:29:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110787
 12/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MLC-1: A SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF AC-1 PER SECTION 606.2.1. PLEASE
 NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 2) MLC-1: PROVIDE THE FLEX DUCT SIZES.
  
 3) MLC-1 & MLC-3: IT APPEARS THAT THE EF-1 SHOWN IN THE
 LEASING OFFICE AND IN THE VENTILATION SCHEDULE SHOULD
 HAVE BEEN LOCATED IN THE RESTROOM- SEE TABLE 403.3.
  
 4) MLC-1 & MLC-3: IT APPEARS THAT NO O/A HAS BEEN
 CALCULATED AND PROVIDED FOR THE E- LOUNGE ROOM.
 ADDITIONALLY, THE PLAN SHOWS NO AC DISTRIBUTION TO THE
 ROOM-PLEASE CLARIFY.
  
 5) MLC-1 & A-2.2: ADVISORY: A NON-COMBUSTIBLE DOOR FOR
 THE AC CLOSET WILL BE REQUIRED IF THE RETURN IS NOT
 DUCTED DIRECTLY TO THE AIR HANDLER- SEE SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION CODE, AND SECTION
 602.2.1 FBC-14 MECHANICAL.
  
 6) MLC-1: PROVIDE AN AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 7) MLC-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSERS AND MOUNTING PAD- SEE
 SECTION 1609 FBC-14 BUILDING.
  
 8) REQUIRED SUBMITTALS:
  
 FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE AC
 STANDS, AND THE AIR INTAKE AND EXHAUST OUTLET LOUVERS.
 DUCT SMOKE DETECTOR
 MOTORIZED DAMPER
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status N Date 2020-03-04 Cont ID  
Sent By shill Date 2020-03-04 Time 12:47 Rev Time 0.00
Received By shill Date 2020-03-04 Time 12:47 Sent To  
Notes
2020-03-04 12:48:03NOT IN THE SFHA; CONFIRMED BY SURVEY AND ELEVATION
 CERTIFICATE. ALSO CONFIRMED ON MYGEONAV.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2018-05-05 Cont ID  
Sent By shill Date 2018-05-05 Time 14:23 Rev Time 0.00
Received By shill Date 2018-05-05 Time 14:23 Sent To  
Notes
2018-05-05 14:25:40PROPOSED DFE = 18.75' NGVD29
 **CAUTION** ELEVATION CERTIFICATE IS REQUIRED TO BE
 NAVD88. CONVERSION BY SURVEYOR ON THE ELEVATION
 CERTIFICATE IS REQUIRED.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 11:26 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 11:26 Sent To  
Notes
2018-03-09 11:27:22ELEVATION CERTIFICATE NOT PROVIDED. SEE BUILDING REVIEW
 NOTES.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-12-01 Cont ID  
Sent By aclange Date 2017-12-01 Time 13:19 Rev Time 0.00
Received By aclange Date 2017-12-01 Time 13:19 Sent To  
Notes
2017-12-01 13:20:07****PLAN REVIEW COMMENTS****
  
 ART LANGE ? BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
  
 SEE BUILDING REVIEW FOR COMMENTS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-09 Cont ID  
Sent By gjohnson Date 2018-05-09 Time 08:16 Rev Time 0.00
Received By gjohnson Date 2018-05-09 Time 08:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-20 Cont ID  
Sent By gjohnson Date 2018-03-20 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2018-03-20 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By gjohnson Date 2018-01-02 Time 09:18 Rev Time 0.00
Received By gjohnson Date 2017-12-28 Time 10:55 Sent To  
Notes
2018-01-02 10:57:551ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. LS-0.0 UNDER APPLICABLE CODES THIS BUILDING
 SHALL COMPLY WITH FBC ACCESSIBILITY 5TH EDITION 2014
 NOT 2012. PLEASE CORRECT. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE LIST OCCUPANT LOAD FOR PLUMBING FIXTURE COUNT
 CALCULATION. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. A-2.2 UNDER THE DOOR SCHEDULE , DOOR GENERAL
 NOTES #1 IT REFERENCES THE 2010 CODE EDITION THIS
 PROJECT IS UNDER 2014 5TH EDITION.
 PLEASE CORRECT. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE SHOW THE CLEAR FLOOR SPACE REQUIRED FOR THE
 LAVATORY AND BREAK ROOM SINK IT SHALL COMPLY WITH FBC
 ACC 606.2
  
 5. LABEL THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR
 THE WATER CLOSET , LAVATORY AND BREAK ROOM SINK. . PER
 WPB AMEND TO FBC 107.2.1
  
 6. THE DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE
 EXCEPTIONS: 2. WHERE THE TOILET ROOM OR BATHING ROOM IS
 FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE.
  
 7. PLEASE PROVIDE A DETAIL SHOWING THE REQUIRED KNEE
 AND TOE CLEARANCE FOR THE VANITY IN THE BATHROOM. PER
 FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 8. THE BREAK ROOM SINK SHALL BE 34" MAX OFF THE
 FINISHED FLOOR TO THE RIM OF THE SINK THE DETAIL #5
 SHT. A-2.3 SHOWS 36" PLEASE CLARIFY . PER FBC ACC 606.3
  
 9. PLEASE PROVIDE CALCULATIONS FOR THE ROOF GUTTERS PER
 FBC PL TABLE 1106.6
  
 10. SHT. A-10.1 SHOWS DETAILS FOR A WATER FOUNTAIN,
 SHOWER, AND A TOILET COMPARTMENT THAT DOES NOT MATCH
 THE PLAN PLEASE REMOVE ANY DETAILS NOT PERTAINING TO
 THIS BUILDING. PER WPB AMEND TO FBC 107.2.1
  
 11. THE COFFEE BAR SHALL COMPLY WITH FBC ACC 227, 308
  
 12 . THE MEP SHEETS SHOW A OUTSIDE DOOR TO MECHANICAL
 ROOM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 13. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 14. A TRAP PRIMER IS REQUIRED FOR ALL FLOOR DRAINS. PER
 FBC PL 1002.4
  
 15. PROVIDE THE MANUFACTURE SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 16. PLEASE PLACE NOTE ON THE PLAN A SEPARATE PERMIT
 WILL BE REQUIRED FOR THE BACK FLOW DEVICES PER WPB
 UTILITIES DEPARTMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-01-05 Cont ID  
Sent By shill Date 2018-01-05 Time 07:03 Rev Time 0.00
Received By shill Date 2018-01-05 Time 07:03 Sent To  
Notes
2018-01-05 07:04:57PROVISO:
  
 A SEPARATE ROOF PERMIT IS REQUIRED; PERMIT TO BE ISSUED
 PRIOR TO COMMENCEMENT OF ANY ROOF WORK
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE) ARE TO BE SUBMITTED WITH
 ROOF PERMIT APPLICATION
  
 PRODUCTS TO COMPLY WITH DESIGN PRESSURES SPECIFIED ON
 SHEET S 5.CH.1.
  
2017-11-21 09:22:55DEFERED

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status N Date 2018-05-14 Cont ID  
Sent By shill Date 2018-05-14 Time 12:38 Rev Time 0.00
Received By shill Date 2018-05-14 Time 12:38 Sent To  
Notes
2018-05-14 12:38:46REMOVED REQUIREMENT FOR RESIDENT INSPECTOR
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2018-05-14 Cont ID  
Sent By shill Date 2018-05-14 Time 11:39 Rev Time 0.00
Received By shill Date 2018-05-14 Time 11:39 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2018-05-05 Cont ID  
Sent By shill Date 2018-05-05 Time 12:14 Rev Time 0.00
Received By shill Date 2018-05-05 Time 12:14 Sent To  
Notes
2018-05-05 12:16:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE THRESHOLD AGREEMENT WAS APPROVED. HOWEVER, THIS
 BUILDING IS NOT "THRESHOLD" BUT REQUIRES A RESIDENT
 INSPECTOR. YOU MAY VOLUNARILY ELECT FOR THIS TO BE
 TREATED AS THRESHOLD, BUT THAT WOULD REQUIRE THE
 STATUTORY STATEMENT ON THE PLANS AND THERE MAY BE OTHER
 UNINTENDED CONSEQUENCES.
  
 PLEASE COMPLETE A RESIDENT INSPECTOR AGREEMENT. SEND TO
 ME VIAL EMAIL FOR PRELIMINARY REVIEW. THIS REVIEW WILL
 THEN PASS PENDING RECEIPT OF THREE ORIGINALS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 15:13 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 14:31 Sent To  
Notes
2018-03-09 15:13:18 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 ****PLAN REVIEW COMMENTS****
  
 1. SEE THE SECTION BELOW REGARDING THE SPECIAL
 INSPECTOR REQUIREMENTS.
  
 A. RESUMES NOT PROVIDE FOR EACH INSPECTOR.
  
 B. CONTRACTOR / OWNER PAGE 16 NOT COMPLETED.
  
 C. PLEASE PROVIDE 3 ORIGINAL SETS.
  
  
 RESIDENT/SPECIAL INSPECTOR PROGRAM
  
 IN ORDER FOR AN INSPECTOR TO WORK IN THE CITY OF WEST
 PALM BEACH, THE FOLLOWING REQUIREMENTS AND STIPULATIONS
 MUST BE MET:
 1. COMPLETE THE RESIDENT INSPECTOR AGREEMENT IN FULL
 AND RETURN THREE ORIGINALS THE DEVELOPMENT SERVICES
 DEPARTMENT OF THE CITY OF WEST PALM BEACH.
 2. A RESIDENT INSPECTOR MUST BE AN ENGINEER, ARCHITECT
 OR HOLD A STANDARD CERTIFICATION AS A BUILDING
 INSPECTOR, ISSUED BY THE FLORIDA DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION THROUGH THE BUILDING CODE
 ADMINISTRATORS AND INSPECTORS BOARD. FOR MORE
 INFORMATION, CONTACT:
  
 FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION
 BLAIR STONE ROAD
 TALLAHASSEE, FL 32399-0783
 (850)487-1395
 3. ALL RESIDENT INSPECTORS ARE REQUIRED TO SUBMIT A
 RESUME OF INSPECTION EXPERIENCE ON PREVIOUS PROJECTS.
 ALL CERTIFICATES AS SPECIFIED MUST ACCOMPANY THE RESUME
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED.
 4. THE RESIDENT INSPECTOR SHALL BE PRESENT AT ALL TIMES
 THAT WORK IS IN PROGRESS FOR STRUCTURAL COMPONENTS. ALL
 OTHER INSPECTIONS MAY BE MADE ON AN AS NEEDED BASIS BY
 SUCH INSPECTOR ONLY AFTER APPROVAL BY THE BUILDING
 OFFICIAL OR DESIGNEE. AT THE COMPLETION OF THE
 CONSTRUCTION WORK OR PROJECT, THE RESIDENT INSPECTOR
 SHALL SUBMIT A CERTIFICATE OF CODE COMPLIANCE TO THE
 BUILDING OFFICIAL OR DESIGNEE, STATING THAT WORK,
 INCLUDING SITE WORK, WAS DONE IN COMPLIANCE WITH THE
 BUILDING CODE AND IN ACCORDANCE WITH THE PERMITTED
 PLANS AND SPECIFICATIONS.
 5. THE RESIDENT INSPECTOR SHALL REMAIN WITH THE PROJECT
 UNTIL ISSUANCE OF THE CERTIFICATE OF CODE COMPLIANCE
 AND AFTER CALLING FOR A FINAL INSPECTION TO BE MADE AND
 APPROVED BY THE BUILDING OFFICIAL OR HIS DESIGNEE.
 NOTE: COMPLIANCE INSPECTIONS WILL BE MADE AT ANY TIME
 TO MONITOR ACTIVITIES.
 THE BUILDING OFFICIAL WILL NOT APPROVE ANY CHANGE OF
 RESIDENT INSPECTORS BECAUSE OF A BETTER JOB
 OPPORTUNITY. ANY REQUEST TO CHANGE A RESIDENT INSPECTOR
 SHALL ONLY OCCUR UPON APPROVAL OF THE BUILDING OFFICIAL
 OR HIS DESIGNEE.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 11:53 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 11:28 Sent To  
Notes
2018-03-09 11:53:44****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 ****PLAN REVIEW COMMENTS****
  
 1. SEE THE SECTION BELOW REGARDING THE SPECIAL
 INSPECTOR REQUIREMENTS.
  
 A. RESUMES NOT PROVIDE FOR EACH INSPECTOR.
  
 B. CONTRACTOR / OWNER PAGE 16 NOT COMPLETED.
  
 C. PLEASE PROVIDE 3 ORIGINAL SETS.
  
  
 RESIDENT/SPECIAL INSPECTOR PROGRAM
  
 IN ORDER FOR AN INSPECTOR TO WORK IN THE CITY OF WEST
 PALM BEACH, THE FOLLOWING REQUIREMENTS AND STIPULATIONS
 MUST BE MET:
 1. COMPLETE THE RESIDENT INSPECTOR AGREEMENT IN FULL
 AND RETURN THREE ORIGINALS THE DEVELOPMENT SERVICES
 DEPARTMENT OF THE CITY OF WEST PALM BEACH.
 2. A RESIDENT INSPECTOR MUST BE AN ENGINEER, ARCHITECT
 OR HOLD A STANDARD CERTIFICATION AS A BUILDING
 INSPECTOR, ISSUED BY THE FLORIDA DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION THROUGH THE BUILDING CODE
 ADMINISTRATORS AND INSPECTORS BOARD. FOR MORE
 INFORMATION, CONTACT:
  
 FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION
 BLAIR STONE ROAD
 TALLAHASSEE, FL 32399-0783
 (850)487-1395
 3. ALL RESIDENT INSPECTORS ARE REQUIRED TO SUBMIT A
 RESUME OF INSPECTION EXPERIENCE ON PREVIOUS PROJECTS.
 ALL CERTIFICATES AS SPECIFIED MUST ACCOMPANY THE RESUME
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED.
 4. THE RESIDENT INSPECTOR SHALL BE PRESENT AT ALL TIMES
 THAT WORK IS IN PROGRESS FOR STRUCTURAL COMPONENTS. ALL
 OTHER INSPECTIONS MAY BE MADE ON AN AS NEEDED BASIS BY
 SUCH INSPECTOR ONLY AFTER APPROVAL BY THE BUILDING
 OFFICIAL OR DESIGNEE. AT THE COMPLETION OF THE
 CONSTRUCTION WORK OR PROJECT, THE RESIDENT INSPECTOR
 SHALL SUBMIT A CERTIFICATE OF CODE COMPLIANCE TO THE
 BUILDING OFFICIAL OR DESIGNEE, STATING THAT WORK,
 INCLUDING SITE WORK, WAS DONE IN COMPLIANCE WITH THE
 BUILDING CODE AND IN ACCORDANCE WITH THE PERMITTED
 PLANS AND SPECIFICATIONS.
 5. THE RESIDENT INSPECTOR SHALL REMAIN WITH THE PROJECT
 UNTIL ISSUANCE OF THE CERTIFICATE OF CODE COMPLIANCE
 AND AFTER CALLING FOR A FINAL INSPECTION TO BE MADE AND
 APPROVED BY THE BUILDING OFFICIAL OR HIS DESIGNEE.
 NOTE: COMPLIANCE INSPECTIONS WILL BE MADE AT ANY TIME
 TO MONITOR ACTIVITIES.
 THE BUILDING OFFICIAL WILL NOT APPROVE ANY CHANGE OF
 RESIDENT INSPECTORS BECAUSE OF A BETTER JOB
 OPPORTUNITY. ANY REQUEST TO CHANGE A RESIDENT INSPECTOR
 SHALL ONLY OCCUR UPON APPROVAL OF THE BUILDING OFFICIAL
 OR HIS DESIGNEE.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-24 Cont ID  
Sent By Hansen Date 2018-05-24 Time   Rev Time 0.00
Received By ahansen Date 2018-05-24 Time 10:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-13 Cont ID  
Sent By AH Date 2018-04-13 Time   Rev Time 0.00
Received By ahansen Date 2018-04-13 Time 13:39 Sent To I
Notes
2018-04-13 13:41:28THE BUILDING PERMIT APPLICATION NEEDS TO INCLUDE AND BE
 CONSISTENT WITH THE SITE PLAN THAT WAS APPROVED ON
 4/13/18 THROUGH THE MINOR PD AMENDMENT PROCESS.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AH Date 2017-12-13 Time   Rev Time 0.00
Received By ahansen Date 2017-12-13 Time 13:26 Sent To  
Notes
2017-12-13 10:53:17SHEET SP-2 IN THE SUBMITTAL INCLUDES SEVERAL PARKING
 STRIPING AND BIKE RACK DETAILS WHICH WERE NOT PART OF
 THE APPROVED SITE PLAN AND WHICH DO NOT COMPLY WITH
 CITY STANDARDS.
 THE APPROVAL LETTER FOR THE BELLA VITA MINOR SITE PLAN
 AMENDMENT ISSUED ON OCTOBER 26, 2017 INCLUDES THE
 FOLLOWING CONDITION OF APPROVAL:
 "5. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT
 FOR THE PROJECT, THE LANDSCAPE PLAN, SITE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS SHALL BE REVISED
 TO RELOCATE THE CURBS TO THE POSITION OF THE WHEEL
 STOPS AND PROVIDE A LANDSCAPED OVERHANG WHERE POSSIBLE
 WITHIN THE PARKING AREAS TO PROVIDE MORE PERVIOUS
 LANDSCAPE AREA. THE DESIGN SHALL FOLLOW THE TYPICAL
 PARKING STALL LAYOUT AS SHOWN ON THE APPROVED PLANS. A
 MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE REQUIRED TO
 REFLECT ANY REVISIONS TO THE PLANS."
 SINCE NO REVISED SITE PLAN, LANDSCAPE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS CONSISTENT WITH
 THE ABOVE CONDITION HAVE BEEN SUBMITTED, THE BUILDING
 PLANS INCLUDED IN THIS PERMIT CANNOT BE APPROVED.
  


Account Summary | Usage Policy | Privacy Policy