| Plan Review Stops For Permit 17110787 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-09 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-09 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2018-03-09 10:30:22 | PROJECT ADDRESSING IS SHOWN ON THE CIVIL PLANS FOR THIS | | | PROJECT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-01 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-01 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2017-12-01 13:22:45 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | 561-805-6718 [email protected] | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | | 2015 5TH EDITION | | | AZOLA WEST PALM BEACH ? 17110788 | | | | | | CONTACT MICHEAL ORIO REGARDING ADDRESSING FOR THIS | | | PROPERTY. | | | | | | ADDRESSING: | | | . CITY MUNI CODE SEC.78-6 (1-7) | | | (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE | | | ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION | | | OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR | | | PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE | | | READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR | | | TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE | | | ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE | | | BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE | | | HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE | | | NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF | | | NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE, | | | SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE | | | CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS | | | WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL, | | | INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A | | | SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS | | | SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL | | | ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL | | | ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE | | | POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH | | | A COMMON EXTERIOR ENTRANCE. | | | (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE | | | RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL | | | DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE | | | DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE | | | REQUIREMENTS OF THIS SECTION. | | | | | | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ | | | INFORMATION TECHNOLOGY | | | TEL: 561-494-1040 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-05 |
Time |
06:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-05 |
Time |
06:26 |
Sent To |
|
|
| Notes |
| 2018-07-05 06:26:37 | OK PER EMAIL FROM SYBILLE WELTER | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-05 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-05 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2018-05-05 13:35:57 | ***PROVISOS*** | | | ***ISSUED AT APPLICANT'S RISK*** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | | | | 1. ELEVATION CERTIFICATE WAS PROVIDED. SURVEYOR STATES | | | THIS IS IN AN X ZONE. SITE PLAN AND SURVEY DO NOT SHOW | | | THE LOCATION OF THE PROPOSED SALES TRAILER RELATIVE TO | | | THE FLOOD BOUNDARY LINE AROUND THE EXISTING POND. IF | | | THIS REVISION IS NOT PROVIDED, THIS STRUCTURE WILL BE | | | TREATED AS IF IN THE SPECIAL FLOOD HAZARD AREA. TWO | | | ADDITIONAL ELEVATION CERTIFICATES ARE REQUIRED: | | | A. AFTER FORMING, PRIOR TO CONCRETE POUR, A "BUILDING | | | UNDER CONSTRUCTION" ELEVATION CERTIFICATE WITH FORM | | | BOARD SURVEY IS REQUIRED | | | B. AFTER FINAL GRADING AND INSTALLATION OF ALL | | | EQUIPMENT SERVICING THE BUILDING (MECHANICAL, PLUMBING, | | | ETC.) BEFORE FINAL INSPECTION A "FINISHED CONSTRUCTION" | | | ELEVATION CERTIFICATE AND FINAL TIE IN SURVEY IS | | | REQUIRED. | | | | | | 2. EXIT DOORS SHOWN WITH 1/2" CHANGE IN LEVEL; | | | COMPLIANCE WITH FBC ACCESSIBILITY 303.3 IS REQUIRED. | | | THE NOTE ON SHEET LS0.0 IS NOT CLEAR. | | | | | | 3. ALTHOUGH CIVIL SHEETS HAVE THIS BUILDING LABELED AS | | | A "CLUBHOUSE" ALL OTHER SHEETS INDICATE THIS IS A | | | LEASING OFFICE. THIS BUILDING HAS BEEN REVIEWED FOR | | | BUSINESS OCCUPANCY ONLY. USE AS A CLUBHOUSE REQUIRES A | | | CHANGE OF OCCUPANCY. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-09 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-09 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2018-03-09 11:24:16 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | AZOLA WEST PALM BEACH 17110787 LEASING CENTER | | | | | | SECOND REVIEW: | | | | | | 1. ELEVATION CERTIFICATE NOT PROVIDED. | | | | | | FLOOD ZONE CERTIFICATES | | | FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. | | | AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FREE BOARD, DESIGN FLOOD | | | ELEVATION. | | | NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS | | | HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL | | | DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE | | | WITH NAV 88. | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED | | | (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS, A/C PADS OR OTHER SLABS FOR GENERATORS. | | | | | | | | | 2. OK ADDRESSED | | | | | | 3. OK WILL BE PROCESSED AS A DEFERRED SUBMITTAL. | | | | | | 4. OK ADDRESSED | | | 5. OK ADDRESSED | | | 6. OK ADDRESSED | | | | | | 7. OK ADDRESSED | | | | | | 8. OK ADDRESSED | | | | | | 9. OK ADDRESSED | | | 10. OK ADDRESSED | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-01 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-11-30 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2017-12-01 13:12:26 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | AZOLA WEST PALM BEACH 17110787 LEASING CENTER | | | | | | FIRST REVIEW: | | | | | | | | | ART IN PUBLIC PLACES: | | | | | | | | | 1. FLOOD ZONE CERTIFICATES | | | | | | FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. | | | AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FREE BOARD, DESIGN FLOOD | | | ELEVATION. | | | NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS | | | HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL | | | DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE | | | WITH NAV 88. | | | | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | | | | (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | | | | (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED | | | | | | (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS, A/C PADS OR OTHER SLABS FOR GENERATORS. | | | | | | | | | 2. PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC... | | | | | | 3. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS, TRUSS ENGINEERING ETC.. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | NOTE: ON PAGE A2.2 NOTE 4, SHOWS WINDOWS TO BE DONE | | | UNDER A SEPERATE PERMIT. SUBMIT PRODUCT APPROVALS AS A | | | DEFERRED SUBMITTAL UNDER THIS PERMIT. | | | | | | 4. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR | | | BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL | | | BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR | | | MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT | | | THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513, | | | FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS | | | WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR | | | STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND | | | ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR | | | STRUCTURES. | | | | | | 5. PROVIDE LANDING ON EXTERIOR OF DOORS. THIS IS NOT | | | SHOWN ON S.4 CH.1 AND CH.2. | | | | | | FBC 1008.1.5 FLOOR ELEVATION. | | | THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF A | | | DOOR. SUCH FLOOR OR LANDING SHALL BE AT THE SAME | | | ELEVATION ON EACH SIDE OF THE DOOR. LANDINGS SHALL BE | | | LEVEL EXCEPT FOR EXTERIOR LANDINGS, WHICH ARE PERMITTED | | | TO HAVE A SLOPE NOT TO EXCEED 0.25 UNIT VERTICAL IN 12 | | | UNITS HORIZONTAL (2-PERCENT SLOPE). | | | | | | 6. EXISTING 2 STORY BUILDING TO BE DEMOLISHED REQUIRES | | | A SEPERATE DEMO PERMIT. FBC 105.1 | | | | | | 7. PARKING DETAILS: PARKING LOT STRIPING DETAILS VARY | | | FROM SINGLE TO DOUBLE STRIPING THROUGHOUT THE PLANS. | | | WEST PALM BEACH PARKING LOT STRIPING IS DOUBLE | | | STRIPING. A DETAIL IS AVAILABLE AT THIS DEPARTMENT. | | | NOTE: FC 553.5041(6) HAS CHANGED REGARDING SIGNAGE. THE | | | NEW MINIMUM HEIGHT IS 60 INCHES. | | | | | | 8. PROVIDE ELEVATION AT COFFEE BAR. FBC 107.3.5 | | | | | | 9. PROVIDE STRUCTURAL DETAILS FOR COVERED PATIO. | | | INCLUDE, FOOFINGS, FRAMING AND ANCHORING. | | | | | | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING | | | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA | | | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION | | | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL | | | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING | | | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: | | | | | | 10. IMPACT FEES: | | | | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-05-21 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-05-21 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2018-05-21 13:42:23 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS | | | REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. NEW | | | COMMENTS FOLLOW THE ORIGINAL COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. CORRECTED | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. CORRECTED. | | | 17. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 18. CORRECTED | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-03-19 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-03-19 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2018-03-19 07:36:36 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS | | | REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. NEW | | | COMMENTS FOLLOW THE ORIGINAL COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. NEC 250.94 (THIS APPLIES TO EVERY SERVICE AND | | | MUST BE SHOWN ON PLAN.) | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED | | | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE | | | AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2 | | | (NOT PROVIDED.) | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. CORRECTED. | | | 17. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 18. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-12-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-19 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-12-19 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2017-12-19 12:54:13 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, | | | 107.2.1 | | | 2. PANEL H SHOWS A GROUNDING ELECTRODE CONDUCTOR TYING | | | INTO THE GROUNDING ELECTRODE SYSTEM. THE GROUNDING | | | ELECTRODE CONDUCTORS ARE INSTALLED TO THE MAIN SERVICE | | | ONLY. THIS IS NOT LABELED AS A MAIN, AND IS SHOWN BEING | | | FED FROM THE 1200 AMP MAIN. CLARIFY AND PROVIDE | | | CORRECTION AS NEEDED. NEC 230.2(E), 250.64 | | | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. NEC 250.94 | | | 4. PANEL SCHEDULE FOR PANEL H SHOWS A 1/0 CONDUCTOR ON | | | A 175 AMP BREAKER FEEDING THE ELEVATOR. PER CODE, A 1/0 | | | COPPER CONDUCTOR IS NOT RATED FOR 175 AMPS. PROVIDE | | | CORRECTION. PROVIDE CORRECTION. NEC 310.15(B)(16), | | | 408.30 | | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 6. SPECIFY FEEDER SIZES TO THE INDIVIDUAL PANELS ON | | | RISER DIAGRAM TO CORRESPOND TO THE VOLTAGE DROP | | | REQUIREMENTS STATED ON SHEET E-4.0. FBC 107.2.1 | | | 7. IT APPEARS THAT ALL UNITS IN THIS BUILDING WILL BE | | | "A" OR "C" TYPE, BUT THE PLAN SHOWS PANEL SCHEDULES FOR | | | "B" TYPE ALSO. REMOVE ANY INFORMATION NOT RELEVANT TO | | | THIS PLAN. FBC 107.2.1 | | | 8. SHEET E-4B.1, NOTE 9 IN ELECTRICAL NOTES AND NOTE 6 | | | IN GENERAL NOTES STATE THAT RECEPTACLES SHALL BE TAMPER | | | RESISTANT PER NEC 406.11, WHICH IS NOT THE CORRECT CODE | | | SECTION. PROVIDE CORRECTION. ALSO, NOTE 2 STATES | | | RECEPTACLES WEATHER PROOF PER NEC 406.8, ALSO WRONG | | | CODE SECTION. PROVIDE CORRECTION. NEC 406.9, 406.12; | | | FBC 107.2.1 | | | 9. SHEET E-4B.1, NOTE 7 IN GENERAL NOTES STATES THAT | | | BREAKERS FEEDING AREAS LISTED IN 250.22 SHALL BE AFCI | | | TYPE BREAKERS. CLARIFY WHY 250.22 IS RELATED TO THIS | | | CODE REQUIREMENT. PER CODE: "ALL 120-VOLT, SINGLE | | | PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING | | | OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS, | | | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, | | | SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR | | | SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION." | | | PROVIDE CORRECTION. NEC 210.12 | | | 10. PANEL SCHEDULE FOR PANEL A & C SHOWS THE WATER | | | HEATER BREAKER AS A 30 AMP BREAKER. BASED ON THE LOAD | | | OF A STANDARD 4500 WATT ELEMENT AT 208 VOLT, THE | | | BREAKER SHOULD BE SIZED AT 25 AMP. PROVIDE CORRECTION. | | | NEC 422.13 | | | 11. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED | | | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE | | | AUTOMATIC CONTROL REQUIRED, SUCH AS ELECTRIC ROOM, | | | ELEVATOR CONTROL ROOM, FIRE ROOM, ETC. FBC EC 405.2.2, | | | 405.2.2.2 | | | 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | | EQUIPMENT PER CODE. THIS INCLUDES ELECTRIC ROOM AND | | | ELEVATOR ROOM CU'S, WHICH ARE NOT CURRENTLY SHOWN ON | | | PLAN. SHOW LOCATION OF UNITS AND CORRESPONDING | | | RECEPTACLE. NEC 210.63; FBC 107.2.1 | | | 13. FEEDERS FROM FPL TO 1200 AMP MAIN ARE TOO SMALL. | | | PLANS SHOWS 4 SETS OF 300 KCMIL AL CONDUCTORS, WHICH | | | ARE RATED FOR 920 AMPS. WIRE MUST BE SIZED EQUAL TO OR | | | GREATER THAN THE MAIN BREAKER. PROVIDE CORRECTION. NEC | | | 240.4(C) | | | 14. UNIT C-1 DOES NOT SHOW THE REQUIRED GFCI RECEPTACLE | | | WITHIN 3 FEET OF EACH BASIN IN THE MASTER BATH. PROVIDE | | | CORRECTION. NEC 210.11(C)(3), 210.52(D) | | | 15. IN UNIT C-1 THERE APPEARS TO BE A KITCHEN ISLAND. | | | IF SO, PROVIDE THE REQUIRED GFCI RECEPTACLE. NEC | | | 210.52(C)(2) | | | 16. UNIT A-1, THE OUTLET OUTSIDE ON CIRCUIT 16 IS | | | REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED. | | | PROVIDE CORRECTION. NEC 210.8, 406.9 | | | 17. UNIT A-2, THE OUTLET OUTSIDE ON CIRCUIT 16 IS | | | REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED. | | | PROVIDE CORRECTION. NEC 210.8, 406.9 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-25 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-25 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2018-05-25 13:43:11 | OK PER MG | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2018-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-14 |
Time |
18:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-14 |
Time |
18:47 |
Sent To |
|
|
| Notes |
| 2018-05-14 18:48:17 | OK PER MANNY GONZALEZ | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2018-04-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-04-13 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-04-13 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2018-04-13 11:40:05 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-18 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2017-12-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-12-18 08:29:27 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
sathomas |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-05-07 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-05-07 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-05-07 |
Time |
13:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-02-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-02-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-02-22 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-11-28 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-11-28 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-11-28 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-05-24 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-05-01 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-04-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-04-13 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-02-20 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-02 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-17 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2018-05-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-09 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-09 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2018-05-09 07:09:31 | MU2018-4765 | | | $4,281.84 | | | RECEIVED IMPACT FEE RECEIPT VIA EMAIL, ROUTED TO | | | RECORDS (VIA EMAIL) | | | | | | | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2018-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-05 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-05 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2018-05-05 12:13:38 | MU2018-4765 | | | $4,281.84 | | | ***NEED RECEIPT, EMAILED APPLICANT*** | | | | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-09 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-09 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2018-03-09 10:31:17 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | 561-805-6718 [email protected] |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-01 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-01 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2017-12-01 13:21:24 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | 561-805-6718 [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-05-23 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-05-21 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-03-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-03-13 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-03-13 |
Time |
17:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-15 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-15 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2017-12-15 16:29:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110787 | | | 12/15/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET MLC-1: A SMOKE DETECTOR IS REQUIRED IN THE | | | RETURN AIR SYSTEM OF AC-1 PER SECTION 606.2.1. PLEASE | | | NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | 2) MLC-1: PROVIDE THE FLEX DUCT SIZES. | | | | | | 3) MLC-1 & MLC-3: IT APPEARS THAT THE EF-1 SHOWN IN THE | | | LEASING OFFICE AND IN THE VENTILATION SCHEDULE SHOULD | | | HAVE BEEN LOCATED IN THE RESTROOM- SEE TABLE 403.3. | | | | | | 4) MLC-1 & MLC-3: IT APPEARS THAT NO O/A HAS BEEN | | | CALCULATED AND PROVIDED FOR THE E- LOUNGE ROOM. | | | ADDITIONALLY, THE PLAN SHOWS NO AC DISTRIBUTION TO THE | | | ROOM-PLEASE CLARIFY. | | | | | | 5) MLC-1 & A-2.2: ADVISORY: A NON-COMBUSTIBLE DOOR FOR | | | THE AC CLOSET WILL BE REQUIRED IF THE RETURN IS NOT | | | DUCTED DIRECTLY TO THE AIR HANDLER- SEE SECTION | | | C403.2.7.2 FBC-14 ENERGY CONSERVATION CODE, AND SECTION | | | 602.2.1 FBC-14 MECHANICAL. | | | | | | 6) MLC-1: PROVIDE AN AUTOMATICALLY CONTROLLED SHUTOFF | | | DAMPERS FOR THE O/A INTAKE- SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION. | | | | | | 7) MLC-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR | | | INSTALLATION OF THE CONDENSERS AND MOUNTING PAD- SEE | | | SECTION 1609 FBC-14 BUILDING. | | | | | | 8) REQUIRED SUBMITTALS: | | | | | | FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE AC | | | STANDS, AND THE AIR INTAKE AND EXHAUST OUTLET LOUVERS. | | | DUCT SMOKE DETECTOR | | | MOTORIZED DAMPER | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
N |
Date |
2020-03-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-04 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-04 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2020-03-04 12:48:03 | NOT IN THE SFHA; CONFIRMED BY SURVEY AND ELEVATION | | | CERTIFICATE. ALSO CONFIRMED ON MYGEONAV. | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
P |
Date |
2018-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-05 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-05 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2018-05-05 14:25:40 | PROPOSED DFE = 18.75' NGVD29 | | | **CAUTION** ELEVATION CERTIFICATE IS REQUIRED TO BE | | | NAVD88. CONVERSION BY SURVEYOR ON THE ELEVATION | | | CERTIFICATE IS REQUIRED. | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-09 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-09 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2018-03-09 11:27:22 | ELEVATION CERTIFICATE NOT PROVIDED. SEE BUILDING REVIEW | | | NOTES. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-01 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-01 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2017-12-01 13:20:07 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE ? BUILDING PLANS EXAMINER | | | 561-805-6718 [email protected] | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | | 2015 5TH EDITION | | | | | | | | | SEE BUILDING REVIEW FOR COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-05-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-09 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-09 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-03-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-20 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-20 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-02 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-12-28 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2018-01-02 10:57:55 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. LS-0.0 UNDER APPLICABLE CODES THIS BUILDING | | | SHALL COMPLY WITH FBC ACCESSIBILITY 5TH EDITION 2014 | | | NOT 2012. PLEASE CORRECT. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE LIST OCCUPANT LOAD FOR PLUMBING FIXTURE COUNT | | | CALCULATION. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. SHT. A-2.2 UNDER THE DOOR SCHEDULE , DOOR GENERAL | | | NOTES #1 IT REFERENCES THE 2010 CODE EDITION THIS | | | PROJECT IS UNDER 2014 5TH EDITION. | | | PLEASE CORRECT. PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. PLEASE SHOW THE CLEAR FLOOR SPACE REQUIRED FOR THE | | | LAVATORY AND BREAK ROOM SINK IT SHALL COMPLY WITH FBC | | | ACC 606.2 | | | | | | 5. LABEL THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR | | | THE WATER CLOSET , LAVATORY AND BREAK ROOM SINK. . PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 6. THE DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC | | | 603.2.3 DOOR SWING. | | | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR | | | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE | | | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE | | | EXCEPTIONS: 2. WHERE THE TOILET ROOM OR BATHING ROOM IS | | | FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING | | | WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC | | | OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING | | | INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR | | | ANY FIXTURE. | | | | | | 7. PLEASE PROVIDE A DETAIL SHOWING THE REQUIRED KNEE | | | AND TOE CLEARANCE FOR THE VANITY IN THE BATHROOM. PER | | | FBC ACC 606.2 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 8. THE BREAK ROOM SINK SHALL BE 34" MAX OFF THE | | | FINISHED FLOOR TO THE RIM OF THE SINK THE DETAIL #5 | | | SHT. A-2.3 SHOWS 36" PLEASE CLARIFY . PER FBC ACC 606.3 | | | | | | 9. PLEASE PROVIDE CALCULATIONS FOR THE ROOF GUTTERS PER | | | FBC PL TABLE 1106.6 | | | | | | 10. SHT. A-10.1 SHOWS DETAILS FOR A WATER FOUNTAIN, | | | SHOWER, AND A TOILET COMPARTMENT THAT DOES NOT MATCH | | | THE PLAN PLEASE REMOVE ANY DETAILS NOT PERTAINING TO | | | THIS BUILDING. PER WPB AMEND TO FBC 107.2.1 | | | | | | 11. THE COFFEE BAR SHALL COMPLY WITH FBC ACC 227, 308 | | | | | | 12 . THE MEP SHEETS SHOW A OUTSIDE DOOR TO MECHANICAL | | | ROOM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 13. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | 14. A TRAP PRIMER IS REQUIRED FOR ALL FLOOR DRAINS. PER | | | FBC PL 1002.4 | | | | | | 15. PROVIDE THE MANUFACTURE SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1 | | | | | | 16. PLEASE PLACE NOTE ON THE PLAN A SEPARATE PERMIT | | | WILL BE REQUIRED FOR THE BACK FLOW DEVICES PER WPB | | | UTILITIES DEPARTMENT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-01-05 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-01-05 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2018-01-05 07:04:57 | PROVISO: | | | | | | A SEPARATE ROOF PERMIT IS REQUIRED; PERMIT TO BE ISSUED | | | PRIOR TO COMMENCEMENT OF ANY ROOF WORK | | | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND | | | ENGINEERING (IF APPLICABLE) ARE TO BE SUBMITTED WITH | | | ROOF PERMIT APPLICATION | | | | | | PRODUCTS TO COMPLY WITH DESIGN PRESSURES SPECIFIED ON | | | SHEET S 5.CH.1. | | | | | 2017-11-21 09:22:55 | DEFERED |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
5 |
Status |
N |
Date |
2018-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-14 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-14 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2018-05-14 12:38:46 | REMOVED REQUIREMENT FOR RESIDENT INSPECTOR | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
P |
Date |
2018-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-14 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-14 |
Time |
11:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2018-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-05 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-05 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2018-05-05 12:16:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THE THRESHOLD AGREEMENT WAS APPROVED. HOWEVER, THIS | | | BUILDING IS NOT "THRESHOLD" BUT REQUIRES A RESIDENT | | | INSPECTOR. YOU MAY VOLUNARILY ELECT FOR THIS TO BE | | | TREATED AS THRESHOLD, BUT THAT WOULD REQUIRE THE | | | STATUTORY STATEMENT ON THE PLANS AND THERE MAY BE OTHER | | | UNINTENDED CONSEQUENCES. | | | | | | PLEASE COMPLETE A RESIDENT INSPECTOR AGREEMENT. SEND TO | | | ME VIAL EMAIL FOR PRELIMINARY REVIEW. THIS REVIEW WILL | | | THEN PASS PENDING RECEIPT OF THREE ORIGINALS. | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-09 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-09 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2018-03-09 15:13:18 | | | | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | 561-805-6718 [email protected] | | | | | | ****PLAN REVIEW COMMENTS**** | | | | | | 1. SEE THE SECTION BELOW REGARDING THE SPECIAL | | | INSPECTOR REQUIREMENTS. | | | | | | A. RESUMES NOT PROVIDE FOR EACH INSPECTOR. | | | | | | B. CONTRACTOR / OWNER PAGE 16 NOT COMPLETED. | | | | | | C. PLEASE PROVIDE 3 ORIGINAL SETS. | | | | | | | | | RESIDENT/SPECIAL INSPECTOR PROGRAM | | | | | | IN ORDER FOR AN INSPECTOR TO WORK IN THE CITY OF WEST | | | PALM BEACH, THE FOLLOWING REQUIREMENTS AND STIPULATIONS | | | MUST BE MET: | | | 1. COMPLETE THE RESIDENT INSPECTOR AGREEMENT IN FULL | | | AND RETURN THREE ORIGINALS THE DEVELOPMENT SERVICES | | | DEPARTMENT OF THE CITY OF WEST PALM BEACH. | | | 2. A RESIDENT INSPECTOR MUST BE AN ENGINEER, ARCHITECT | | | OR HOLD A STANDARD CERTIFICATION AS A BUILDING | | | INSPECTOR, ISSUED BY THE FLORIDA DEPARTMENT OF BUSINESS | | | AND PROFESSIONAL REGULATION THROUGH THE BUILDING CODE | | | ADMINISTRATORS AND INSPECTORS BOARD. FOR MORE | | | INFORMATION, CONTACT: | | | | | | FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL | | | REGULATION | | | BLAIR STONE ROAD | | | TALLAHASSEE, FL 32399-0783 | | | (850)487-1395 | | | 3. ALL RESIDENT INSPECTORS ARE REQUIRED TO SUBMIT A | | | RESUME OF INSPECTION EXPERIENCE ON PREVIOUS PROJECTS. | | | ALL CERTIFICATES AS SPECIFIED MUST ACCOMPANY THE RESUME | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. | | | 4. THE RESIDENT INSPECTOR SHALL BE PRESENT AT ALL TIMES | | | THAT WORK IS IN PROGRESS FOR STRUCTURAL COMPONENTS. ALL | | | OTHER INSPECTIONS MAY BE MADE ON AN AS NEEDED BASIS BY | | | SUCH INSPECTOR ONLY AFTER APPROVAL BY THE BUILDING | | | OFFICIAL OR DESIGNEE. AT THE COMPLETION OF THE | | | CONSTRUCTION WORK OR PROJECT, THE RESIDENT INSPECTOR | | | SHALL SUBMIT A CERTIFICATE OF CODE COMPLIANCE TO THE | | | BUILDING OFFICIAL OR DESIGNEE, STATING THAT WORK, | | | INCLUDING SITE WORK, WAS DONE IN COMPLIANCE WITH THE | | | BUILDING CODE AND IN ACCORDANCE WITH THE PERMITTED | | | PLANS AND SPECIFICATIONS. | | | 5. THE RESIDENT INSPECTOR SHALL REMAIN WITH THE PROJECT | | | UNTIL ISSUANCE OF THE CERTIFICATE OF CODE COMPLIANCE | | | AND AFTER CALLING FOR A FINAL INSPECTION TO BE MADE AND | | | APPROVED BY THE BUILDING OFFICIAL OR HIS DESIGNEE. | | | NOTE: COMPLIANCE INSPECTIONS WILL BE MADE AT ANY TIME | | | TO MONITOR ACTIVITIES. | | | THE BUILDING OFFICIAL WILL NOT APPROVE ANY CHANGE OF | | | RESIDENT INSPECTORS BECAUSE OF A BETTER JOB | | | OPPORTUNITY. ANY REQUEST TO CHANGE A RESIDENT INSPECTOR | | | SHALL ONLY OCCUR UPON APPROVAL OF THE BUILDING OFFICIAL | | | OR HIS DESIGNEE. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-09 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-09 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2018-03-09 11:53:44 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | 561-805-6718 [email protected] | | | | | | ****PLAN REVIEW COMMENTS**** | | | | | | 1. SEE THE SECTION BELOW REGARDING THE SPECIAL | | | INSPECTOR REQUIREMENTS. | | | | | | A. RESUMES NOT PROVIDE FOR EACH INSPECTOR. | | | | | | B. CONTRACTOR / OWNER PAGE 16 NOT COMPLETED. | | | | | | C. PLEASE PROVIDE 3 ORIGINAL SETS. | | | | | | | | | RESIDENT/SPECIAL INSPECTOR PROGRAM | | | | | | IN ORDER FOR AN INSPECTOR TO WORK IN THE CITY OF WEST | | | PALM BEACH, THE FOLLOWING REQUIREMENTS AND STIPULATIONS | | | MUST BE MET: | | | 1. COMPLETE THE RESIDENT INSPECTOR AGREEMENT IN FULL | | | AND RETURN THREE ORIGINALS THE DEVELOPMENT SERVICES | | | DEPARTMENT OF THE CITY OF WEST PALM BEACH. | | | 2. A RESIDENT INSPECTOR MUST BE AN ENGINEER, ARCHITECT | | | OR HOLD A STANDARD CERTIFICATION AS A BUILDING | | | INSPECTOR, ISSUED BY THE FLORIDA DEPARTMENT OF BUSINESS | | | AND PROFESSIONAL REGULATION THROUGH THE BUILDING CODE | | | ADMINISTRATORS AND INSPECTORS BOARD. FOR MORE | | | INFORMATION, CONTACT: | | | | | | FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL | | | REGULATION | | | BLAIR STONE ROAD | | | TALLAHASSEE, FL 32399-0783 | | | (850)487-1395 | | | 3. ALL RESIDENT INSPECTORS ARE REQUIRED TO SUBMIT A | | | RESUME OF INSPECTION EXPERIENCE ON PREVIOUS PROJECTS. | | | ALL CERTIFICATES AS SPECIFIED MUST ACCOMPANY THE RESUME | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. | | | 4. THE RESIDENT INSPECTOR SHALL BE PRESENT AT ALL TIMES | | | THAT WORK IS IN PROGRESS FOR STRUCTURAL COMPONENTS. ALL | | | OTHER INSPECTIONS MAY BE MADE ON AN AS NEEDED BASIS BY | | | SUCH INSPECTOR ONLY AFTER APPROVAL BY THE BUILDING | | | OFFICIAL OR DESIGNEE. AT THE COMPLETION OF THE | | | CONSTRUCTION WORK OR PROJECT, THE RESIDENT INSPECTOR | | | SHALL SUBMIT A CERTIFICATE OF CODE COMPLIANCE TO THE | | | BUILDING OFFICIAL OR DESIGNEE, STATING THAT WORK, | | | INCLUDING SITE WORK, WAS DONE IN COMPLIANCE WITH THE | | | BUILDING CODE AND IN ACCORDANCE WITH THE PERMITTED | | | PLANS AND SPECIFICATIONS. | | | 5. THE RESIDENT INSPECTOR SHALL REMAIN WITH THE PROJECT | | | UNTIL ISSUANCE OF THE CERTIFICATE OF CODE COMPLIANCE | | | AND AFTER CALLING FOR A FINAL INSPECTION TO BE MADE AND | | | APPROVED BY THE BUILDING OFFICIAL OR HIS DESIGNEE. | | | NOTE: COMPLIANCE INSPECTIONS WILL BE MADE AT ANY TIME | | | TO MONITOR ACTIVITIES. | | | THE BUILDING OFFICIAL WILL NOT APPROVE ANY CHANGE OF | | | RESIDENT INSPECTORS BECAUSE OF A BETTER JOB | | | OPPORTUNITY. ANY REQUEST TO CHANGE A RESIDENT INSPECTOR | | | SHALL ONLY OCCUR UPON APPROVAL OF THE BUILDING OFFICIAL | | | OR HIS DESIGNEE. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-05-24 |
|
|
Cont ID |
|
| Sent By |
Hansen |
Date |
2018-05-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
ahansen |
Date |
2018-05-24 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-04-13 |
|
|
Cont ID |
|
| Sent By |
AH |
Date |
2018-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
ahansen |
Date |
2018-04-13 |
Time |
13:39 |
Sent To |
I |
|
| Notes |
| 2018-04-13 13:41:28 | THE BUILDING PERMIT APPLICATION NEEDS TO INCLUDE AND BE | | | CONSISTENT WITH THE SITE PLAN THAT WAS APPROVED ON | | | 4/13/18 THROUGH THE MINOR PD AMENDMENT PROCESS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
AH |
Date |
2017-12-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
ahansen |
Date |
2017-12-13 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2017-12-13 10:53:17 | SHEET SP-2 IN THE SUBMITTAL INCLUDES SEVERAL PARKING | | | STRIPING AND BIKE RACK DETAILS WHICH WERE NOT PART OF | | | THE APPROVED SITE PLAN AND WHICH DO NOT COMPLY WITH | | | CITY STANDARDS. | | | THE APPROVAL LETTER FOR THE BELLA VITA MINOR SITE PLAN | | | AMENDMENT ISSUED ON OCTOBER 26, 2017 INCLUDES THE | | | FOLLOWING CONDITION OF APPROVAL: | | | "5. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT | | | FOR THE PROJECT, THE LANDSCAPE PLAN, SITE PLAN, AND | | | ENGINEERING PAVING AND DRAINAGE PLANS SHALL BE REVISED | | | TO RELOCATE THE CURBS TO THE POSITION OF THE WHEEL | | | STOPS AND PROVIDE A LANDSCAPED OVERHANG WHERE POSSIBLE | | | WITHIN THE PARKING AREAS TO PROVIDE MORE PERVIOUS | | | LANDSCAPE AREA. THE DESIGN SHALL FOLLOW THE TYPICAL | | | PARKING STALL LAYOUT AS SHOWN ON THE APPROVED PLANS. A | | | MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE REQUIRED TO | | | REFLECT ANY REVISIONS TO THE PLANS." | | | SINCE NO REVISED SITE PLAN, LANDSCAPE PLAN, AND | | | ENGINEERING PAVING AND DRAINAGE PLANS CONSISTENT WITH | | | THE ABOVE CONDITION HAVE BEEN SUBMITTED, THE BUILDING | | | PLANS INCLUDED IN THIS PERMIT CANNOT BE APPROVED. | | | |
|
|