Plan Review Details - Permit 17110779
Plan Review Stops For Permit 17110779
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By aclange Date 2018-04-09 Time 08:32 Rev Time 0.00
Received By aclange Date 2018-04-09 Time 08:23 Sent To  
Notes
2018-04-09 08:32:22****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 THE 3 "A" MODEL BUILDINGS WILL BE PERMITTED WITH THE
 FOLLOWING ADDRESSES.
  
 BUILDING 1 1891 AUGUSTINE RD. 17110779
  
 BUILDING 2 1861 AUGUSTINE RD. 17110781
  
 BUILDING 3 1831 AUGUSTINE RD. 17110783
  
 NOTE: ONE COMPLETE PERMIT SET WILL BE USED FOR THESE 3
 BUILDINGS. THIS INCLUDES 3 SETS OF PLANS ONE FOR OUR
 RECORDS, ONE FOR CONTRACTOR AND ONE FOR THE THRESHOLD
 INSPECTOR.
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By aclange Date 2017-11-29 Time 12:57 Rev Time 0.00
Received By aclange Date 2017-11-29 Time 12:57 Sent To  
Notes
2017-11-29 12:58:18****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
 AZOLA WEST PALM BEACH ? 17110788
  
 CONTACT MICHEAL ORIO REGARDING ADDRESSING FOR THIS
 PROPERTY.
  
 ADDRESSING:
 . CITY MUNI CODE SEC.78-6 (1-7)
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
 E-MAIL: [email protected]
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 06:25 Rev Time 0.00
Received By shill Date 2018-07-05 Time 06:25 Sent To  
Notes
2018-07-05 06:25:44OK PER EMAIL FROM SYBILLE WELTER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-08 Cont ID  
Sent By skennedy Date 2018-06-08 Time 13:54 Rev Time 0.00
Received By skennedy Date 2018-06-08 Time 10:40 Sent To  
Notes
2018-06-08 13:56:51DEFERRED SUBMITTALS: WINDOWS, DOORS, ROOFING, TRUSSES,
 FLOORING INSULATION, SHORING & RESHORING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By aclange Date 2018-04-09 Time 11:40 Rev Time 0.00
Received By aclange Date 2018-03-28 Time 10:31 Sent To  
Notes
2018-04-09 11:40:35****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 AZOLA WEST PALM BEACH 17110779 TYPE "A"
  
 SECOND REVIEW:
  
 1. OK. ADDRESSED.
  
 2. ELEVATION CERTIFICATE PROVIDED IS NOT COMPLETE.
 SECTION D HAS NOT BEEN SEALED BY A SURVEYOR, ENGINEER
 OR AN ARCHITECT.
  
 3. RECEIVED SOILS EXPLORATION REPORT.
 SEE SECTION 4.2 REGARDING FOUNDATION RECOMMENDATIONS.
 SEE FOOTINGS ON S 3.1.1 THESE SHOULD AT LEAST MEET THE
 MINIMUM RECOMMENDED BY THE GEOTECHNICAL ENGINEERING
 RECOMMENDATIONS.
 REPORT NOT SIGNED AS REVIEWED BY THE ENGINEER OF
 RECORED.
  
 PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 4. PARTIALLY ADDRESSED.
  
 I HAVE PROVIDED THE THRESHOLD INSPECTOR AGREEMENT TO A
 AND J PERMITTING AND HAVE NOT RECEIVED THE COMPLETED
 AGREEMENT WITH THE SUPPORTING DOCUMENTS.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
 NOTE: E-MAILED JOSE SAUMELL ARCHITECT OF RECORD
 [email protected] ON 11/28/17 AN ATTACHMENT
 WITH THE GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD INSPECTORS.
  
 17. PARTIALLY ADDRESSED. STILL LISTED ON KEY NOTES ON
 PAGE A 3.2 F-1 AND F-6
  
 COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF EXTERIOR
 WALLS. SEE OUTLOOKERS USED AT GABLE ENDS AND DECORATIVE
 FOAM MEDALLIONS.
  
 FBC 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH
 THE FOLLOWING LIMITATIONS: 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 18. PARTIALLY ADDRESSED. LOCATIONS OF THE DUCT FOUND.
 PROVIDE RATING ON THE HORIZONTAL DUCT AND THE ASSEMBLY
 USED. IF FLAME BAR IS USED THIS WOULD BE REVIEWED AS
 ALTERNATIVE MATERIALS AND METHODS. THE DUCT RATING
 SHALL BE THE SAME AS THE SHAFT IS SERVICES.
  
 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE SECTION.
  
 FBC 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED AT THE TOP OF THE HOISTWAY AND
 SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR THROUGH
 NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH THE ELEVATOR
 MACHINE ROOM, PROVIDED THAT PORTIONS OF THE DUCTS
 LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES
 IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM)
 OF CLEARANCE ON ALL SIDES.
  
 23. CONFIRM MEASUREMENTS AROUND KITCHEN ISLAND
 CABINETS. IT APPEAR THEY ARE UNDER THE MINIMUM OF 40
 INCHES. SEE FAIR HOUSING DESIGN MANUAL PAGE 7.8.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
 *******************************************************
 ***************************
  
 PROVISOS:
  
 A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS, TRUSS ENGINEERING ETC..
  
 LISTED ON PAGE LS 0.0
 UNDER GROUND UTILITIES
 ROOF PRODUCT APPROVALS
 DOOR AND WINDOW SHOP DRAWINGS AND PRODUCT APPROVALS
 DRAINAGE SHOP DRAWINGS
 ELEVATOR SHOP DRAWINGS
 SHORING SUBMITTAL
 FIRE SPRINKLER AND ALARM SHOP DRAWINGS
 EXTERIOR FRAMING SHOP DRAWINGS
 RAILING SHOP DRAWINGS
 TRUSS ENGINEERING
  
 SWIMMING POOL UNDER A SEPARATE PERMIT.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 B) LISTED ON DEFFERED SUBMITTALS
 SUBMIT 3 SETS OF TRUSS ENGINEERING APPROVED BY THE
 DESIGNER OF RECORD.
  
 C) WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 D) THE OWNER AS NEEDED WILL PROVIDE ADAPTABLE PORTABLE
 RAMPS AT SLIDING PATIO DOORS. RAMPS WILL BE AVAILABLE
 IN THE MANAGEMENT OFFICE AT ALL TIMES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By aclange Date 2017-11-29 Time 15:25 Rev Time 0.00
Received By aclange Date 2017-11-27 Time 08:01 Sent To  
Notes
2017-11-29 14:11:26****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 AZOLA WEST PALM BEACH 17110779 TYPE "A"
  
 FIRST REVIEW:
  
  
 ART IN PUBLIC PLACES:
  
 1. INFORMATION NOTICE: THE CITY OF WEST PALM BEACH ART
 IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO
 ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
  
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2. FLOOD ZONE CERTIFICATES
 FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE.
 AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FREE BOARD, DESIGN FLOOD
 ELEVATION.
 NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS
 HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL
 DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE
 WITH NAV 88.
  
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
  
 (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
  
 (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS, A/C PADS OR OTHER SLABS FOR GENERATORS.
  
  
 3. PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 4. THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BUILDING, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
  
 G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
  
 I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 NOTE: E-MAILED JOSE SAUMELL ARCHITECT OF RECORD
 [email protected] ON 11/28/17 AN ATTACHMENT
 WITH THE GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD INSPECTORS.
  
 5. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS, TRUSS ENGINEERING ETC..
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR
 BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL
 BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR
 MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT
 THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513,
 FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS
 WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 7. PROVIDE AN EVALUATION REPORT FOR SPRAY INSULATION
 SHOWN ON PAGE A 6.1 KEY NOTE 73 AND FOR RIGID POLY ISO
 INSULATED BOARD SHOWN ON PAGE A 3.3 KEYNOTE 42. FBC
 2603.5.4
  
 8. SUBMIT 3 SETS OF TRUSS ENGINEERING APPROVED BY THE
 DESIGNER OF RECORD.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
 9. WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 10. SLIDING GLASS DOOR THRESHOLD. SEE A 8.3 DETAIL 1.
 THE SILL RISER WILL INTERFERE WITH THE MAXIMUM
 THRESHOLD AND ALLOWABLE 4" STEP. SEE FAIR HOUSING ACT
 DESIGN MANUAL'S DETAIL ON PAGE 4.15.
  
 11. PAGE A 9.1 DETAIL 1. FRAMING IS SHOWN AS 24 INCHES
 ON CENTER. CHECK MANUFACTURER'S SPECIFICATION ON
 CEMENTITIOUS BOARD. MANY REQUIRE FRAMING AT 16 INCHES
 ON CENTER.
  
 12. THE SCALE OF 3 INCHES EQUALS 1 FOOT IS NOT ACCURATE
 PLEASE SEE PAGES A 8.1, A 8.2, A 8.3 AND A 8.4.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 13. DETAIL F ON PAGE S 3.3.3 SPECIAL GIRDER TRUSS
 CONNECTION DETAIL 1, 2, 3 AND 4 ARE MISSING
 MEASUREMENTS.
  
 14. ON PAGE A 7.3 ELEVATOR NOTE. ELEVATOR SHALL COMPLY
 WITH FBC 708.14 WAS NOT FOUND. PLEASE UPDATE THIS CODE
 SECTION.
  
 15. PAGE 8.2 DETAIL 17. PLEASE UPDATE CODE SECTION TO
 2014 FBC 5TH EDITION.
  
 16. PLEASE PROVIDE MANUFACTURE'S SPECIFICATIONS FOR
 BARBECUES USED.
  
 17. COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF
 EXTERIOR WALLS. SEE OUTLOOKERS USED AT GABLE ENDS AND
 DECORATIVE FOAM MEDALLIONS.
  
 FBC 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH
 THE FOLLOWING LIMITATIONS: 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 18. VENT ON TOP OF ELEVATOR SHAFT RATING NOT SHOWN. SEE
 PAGE A 7.2. ALSO DETAIL 21 ON A 8.2 WAS NOT PROVIDED.
 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE SECTION.
  
 FBC 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED AT THE TOP OF THE HOISTWAY AND
 SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR THROUGH
 NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH THE ELEVATOR
 MACHINE ROOM, PROVIDED THAT PORTIONS OF THE DUCTS
 LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES
 IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM)
 OF CLEARANCE ON ALL SIDES.
  
 19. CLARIFY VAPOR BARRIER THAT IS TO BE USED. IT VARIES
 FROM 6 MIL TO 10 MIL. SEE S 2.1.1.1, S 4.1.1.1, S 4.1.2
 AND S 4.1.3
  
 20. EXISTING 2 STORY BUILDING TO BE DEMOLISHED REQUIRES
 A SEPERATE DEMO PERMIT. FBC 105.1
  
 21. PARKING DETAILS: PARKING LOT STRIPING DETAILS VARY
 FROM SINGLE TO DOUBLE STRIPING THROUGHOUT THE PLANS.
 WEST PALM BEACH PARKING LOT STRIPING IS DOUBLE
 STRIPING. A DETAIL IS AVAILABLE AT THIS DEPARTMENT.
 NOTE: FC 553.5041(6) HAS CHANGED REGARDING SIGNAGE. THE
 NEW MINIMUM HEIGHT IS 60 INCHES.
  
  
 22. IMPACT FEES:
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-13 Cont ID  
Sent By jpearson Date 2018-04-13 Time 09:49 Rev Time 0.00
Received By jpearson Date 2018-04-13 Time 07:06 Sent To  
Notes
2018-04-04 11:31:56SEE E17110029

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By jpearson Date 2017-12-19 Time 10:26 Rev Time 0.00
Received By jpearson Date 2017-12-18 Time 16:08 Sent To  
Notes
2017-12-19 09:58:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PANEL H SHOWS A GROUNDING ELECTRODE CONDUCTOR TYING
 INTO THE GROUNDING ELECTRODE SYSTEM. THE GROUNDING
 ELECTRODE CONDUCTORS ARE INSTALLED TO THE MAIN SERVICE
 ONLY. THIS IS LABELED AS A MAIN, BUT IS SHOWN BEING FED
 FROM THE 1200 AMP MAIN. CLARIFY AND PROVIDE CORRECTION
 AS NEEDED. NEC 230.2(E), 250.64
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 4. PANEL SCHEDULE FOR PANEL H SHOWS A 1/0 CONDUCTOR ON
 A 175 AMP BREAKER FEEDING THE ELEVATOR. PER CODE, A 1/0
 COPPER CONDUCTOR IS NOT RATED FOR 175 AMPS. PROVIDE
 CORRECTION. PROVIDE CORRECTION. NEC 310.15(B)(16),
 408.30
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. SPECIFY FEEDER SIZES TO THE INDIVIDUAL PANELS ON
 RISER DIAGRAM TO CORRESPOND TO THE VOLTAGE DROP
 REQUIREMENTS STATED ON SHEET E-4.0. FBC 107.2.1
 7. IT APPEARS THAT ALL UNITS IN THIS BUILDING WILL BE
 "A" OR "B" TYPE, BUT THE PLAN SHOWS PANEL SCHEDULES FOR
 "C" TYPE ALSO. REMOVE ANY INFORMATION NOT RELEVANT TO
 THIS PLAN. FBC 107.2.1
 8. SHEET E-4A.1, NOTE 9 IN ELECTRICAL NOTES AND NOTE 6
 IN GENERAL NOTES STATE THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11, WHICH IS NOT THE CORRECT CODE
 SECTION. PROVIDE CORRECTION. ALSO, NOTE 2 STATES
 RECEPTACLES WEATHER PROOF PER NEC 406.8, ALSO WRONG
 CODE SECTION. PROVIDE CORRECTION. NEC 406.9, 406.12;
 FBC 107.2.1
 9. SHEET E-4A.1, NOTE 7 IN GENERAL NOTES STATES THAT
 BREAKERS FEEDING AREAS LISTED IN 250.22 SHALL BE AFCI
 TYPE BREAKERS. CLARIFY WHY 250.22 IS RELATED TO THIS
 CODE REQUIREMENT. PER CODE: "ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION."
 PROVIDE CORRECTION. NEC 210.12
 10. PANEL SCHEDULE FOR PANEL A & B SHOWS THE WATER
 HEATER BREAKER AS A 30 AMP BREAKER. BASED ON THE LOAD
 OF A STANDARD 4500 WATT ELEMENT AT 208 VOLT, THE
 BREAKER SHOULD BE SIZED AT 25 AMP. PROVIDE CORRECTION.
 NEC 422.13
 11. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED, SUCH AS ELECTRIC ROOM,
 ELEVATOR CONTROL ROOM, FIRE ROOM, ETC. FBC EC 405.2.2,
 405.2.2.2
 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. THIS INCLUDES ELECTRIC ROOM AND
 ELEVATOR ROOM CU'S, WHICH ARE NOT CURRENTLY SHOWN ON
 PLAN. SHOW LOCATION OF UNITS AND CORRESPONDING
 RECEPTACLE. NEC 210.63; FBC 107.2.1
 13. FEEDERS FROM FPL TO 1200 AMP MAIN ARE TOO SMALL.
 PLANS SHOWS 4 SETS OF 300 KCMIL AL CONDUCTORS, WHICH
 ARE RATED FOR 920 AMPS. WIRE MUST BE SIZED EQUAL TO OR
 GREATER THAN THE MAIN BREAKER. PROVIDE CORRECTION. NEC
 240.4(C)
 14. UNIT B-3 DOES NOT SHOW THE REQUIRED GFCI RECEPTACLE
 WITHIN 3 FEET OF EACH BASIN IN THE MASTER BATH. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 15. IN UNIT B-3 THERE APPEARS TO BE A KITCHEN ISLAND.
 IF SO, PROVIDE THE REQUIRED GFCI RECEPTACLE. NEC
 210.52(C)(2)
 16. UNIT B-3 DOES NOT SHOW THE REQUIRED 2ND SMALL
 APPLIANCE BRANCH CIRCUIT IN THE KITCHEN, IDENTIFIED IN
 PANEL SCHEDULE AS CIRCUIT NUMBER 4. PROVIDE CORRECTION.
 NEC 210.11(C)(3), 210.52
 17. UNIT B-3, THE OUTLET OUTSIDE ON CIRCUIT 16 IS
 REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8, 406.9
 18. UNIT A-2, THE OUTLET OUTSIDE ON CIRCUIT 16 IS
 REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8, 406.9
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2018-04-04 Cont ID  
Sent By skennedy Date 2018-04-04 Time 11:33 Rev Time 0.00
Received By skennedy Date 2018-04-04 Time 11:33 Sent To  
Notes
2018-04-13 11:41:36CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
2018-04-04 11:33:23SEE E17110029

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-12-18 Time   Rev Time  
Received By   Date 2017-12-18 Time   Sent To  
Notes
2017-12-18 08:28:12CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By scaldero Date 2018-03-26 Time 12:26 Rev Time 0.00
Received By scaldero Date 2018-03-26 Time 12:20 Sent To  
Notes
2018-03-26 12:26:34PERMIT # 17110779
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 COMPLIANCE OF ALL ITEMS WILL BE VERIFIED IN THE FIELD.
 FAILURE TO COMPLY WITH FIRE CODE REQUIREMENTS WILL
 RESULT IN A FAILED INSPECTION.
  
 1) SHEET C5 - PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH
 TO ALLOW SIMULTANEOUS (ENTRY AND EXIT) GATE ACCESS TO
 EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
 NOTE WAS NOT FOUND ON SHEET AS INDICATED IN RESPONSE.
  
 2) COMPLIANCE OF REQUIRED MECHANICAL VENTILATION FOR
 GARAGE UNITS, OF 1CFM PER 1SF OF FLOOR AREA, TO BE
 VERIFIED IN THE FIELD.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By scaldero Date 2017-12-04 Time 14:05 Rev Time 0.00
Received By scaldero Date 2017-12-04 Time 12:48 Sent To  
Notes
2017-12-04 13:16:27PERMIT # 17110779
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMENTS:
  
 1) SHEET C5: PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH
 TO OPEN BOTH THE ENTRY AND EXIT GATES, SIMULTANEOUSLY.
  
 2) SHEET M-5.3: GARAGE EXHAUST FANS (150CFM) APPEAR TO
 SMALL TO VENTILATE THE GARAGES IN ACCORDANCE WITH NFPA
 88A.
 PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1 CFM PER 1 SF OF
 FLOOR AREA DURING HOURS OF NORMAL OPERATION.
  
 3) SHEET M-5.3: GARAGE EXHAUST FANS INDICATE A LIGHT
 SWITCH STARTER. THESE FANS WOULD NEED TO OPERATE
 CONTINUOUSLY OR BY A CO DETECTOR; NOT A MANUAL SWITCH.
  
 4) FS SHEETS: SHEET FS 3.A.1. IS NOT INCLUDED. PLEASE
 ADVISE IF THE SHEET IS MSSING OR IF THE NUMBER IS
 INCORRECT. (THERE IS A FS 2.A.1 AND FS 4.A.1.)
  
 5) PLEASE SEE REVIEW AND RESPOND TO ALL OTHER PLAN
 REVIEW COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-08 Cont ID  
Sent By skennedy Date 2018-06-08 Time 13:54 Rev Time 0.00
Received By skennedy Date 2018-05-15 Time 16:01 Sent To  
Notes
2018-05-16 16:01:31C37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-03 Cont ID  
Sent By shill Date 2018-04-17 Time 13:56 Rev Time 0.00
Received By shill Date 2018-03-21 Time 14:58 Sent To  
Notes
2018-03-22 14:58:39C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-22 Cont ID  
Sent By gjohnson Date 2017-12-22 Time 14:33 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 09:15 Sent To  
Notes
2017-11-21 14:28:16C37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-06-08 Cont ID  
Sent By skennedy Date 2018-06-08 Time 13:54 Rev Time 0.00
Received By skennedy Date 2018-06-08 Time 10:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By aclange Date 2018-04-09 Time 08:50 Rev Time 0.00
Received By aclange Date 2018-04-09 Time 08:50 Sent To  
Notes
2018-04-09 08:51:10IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By aclange Date 2017-11-29 Time 12:58 Rev Time 0.00
Received By aclange Date 2017-11-29 Time 12:58 Sent To  
Notes
2017-11-29 12:59:30IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-16 Cont ID  
Sent By ccole Date 2018-04-16 Time 11:09 Rev Time 0.00
Received By ccole Date 2018-04-16 Time 11:09 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-15 Cont ID  
Sent By ccole Date 2017-12-15 Time 08:23 Rev Time 0.00
Received By ccole Date 2017-12-14 Time 16:53 Sent To  
Notes
2017-12-15 09:10:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110779
 12/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CALCULATIONS ARE INCORRECTLY IDENTIFYING THE
 PROJECT NAME AS BELLA VITA CLUBHOUSE, AND CONTAIN
 CALCULATIONS FOR SYSTEMS A1 AND C1 WHICH ARE NOT SHOWN
 ON THE PLANS.
  
 2) THE SUBMITTED AC CALCULATIONS DO NOT MEET THE
 REQUIRED PROCEDURE FOR SYSTEM SIZING AS OUTLINED IN
 SECTION C407.5.2.3 ENERGY CONSERVATION- MULTIFAMILY
 RESIDENTIAL BUILDINGS:
  
 RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL
 BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME
 ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE
 THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR
 FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING
 THESE FEATURES.
  
 PLEASE SUBMIT REVISED CALCULATIONS.
  
 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE
 THAT A COPY OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED FOR REVIEW AT FINAL INSPECTION.
  
 4) PROVIDE VENTILATION CALCULATIONS FOR THE APARTMENTS-
 TABLE 403.3.
  
 5) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 STORAGE ROOMS, AND THE FIRE SERVICE ROOM- TABLE 403.3
  
 6) SHEETS M2A.1 & M5.3, PARKING GARAGES:THE EF-2
 SCHEDULE INDICATES THE EXHAUST FANS WILL BE ACTIVATED
 BY THE LIGHT SWITCH. PLEASE SEE SECTIONS 404.1 AND
 404.2 AND REVISE THE PLAN TO SHOW THE CORRECT SEQUENCE
 OF FAN OPERATION AND REQUIRED EXHAUST VENTILATION
 RATES.
  
 7) M2A1: A FIRE DAMPER IS REQUIRED FOR THE ELEVATOR
 SHAFT RELIEF AIR OPENING- SECTION 607.5.2.
  
 8) PLEASE PROVIDE AN ENLARGED DETAIL OF THE ELEVATOR
 EXHAUST VENTILATION SYSTEM THAT PROVIDES EXHAUST DUCT
 AND DUCT SUPPORT DETAILS, AND THE EXHAUST DUCT RUN AND
 TERMIANTION LOCATION INCLUDING REQUIRED CLEARANCES PER
 SECTIO 501.3.1.
  
 9) M4A.1, UNITS B1A: & B2: THE 16"X6" RETURN TRANSFER
 GRILLS AT BEDROOM 2 AND THE MASTER BEDROOM ARE
 UNDERSIZED PER SECTION 601.5 (2)
  
 10) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSERS AND STANDS- SEE SECTION
 1609 FBC-14 BUILDING.
  
 11) A5.1: THE DOOR SCHEDULE INDICATES THE AC CLOSET
 DOORS WILL BE PROVIDED WITH INTUMESCENT PAINT ON THE
 INTERIOR SIDE IN ORDER TO MEET COMPLIANCE WITH SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND SECTION
 602.2.1 FBC-14 MECHANICAL. PLEASE NOTE THAT THE WPB
 BUILDING DEPARTMENT WILL NOT PERFORM INSPECTIONS ON THE
 DOOR, BUT WILL REQUIRE A LETTER FROM THE ENGINEER OF
 RECORD TO CERTIFY THE APPLICATION OF THE PAINT AND
 COMPLIANCE WITH THE AFOREMENTIONED CODE SECTIONS.
  
 12) PROVIDE REFRIGERANT PIPING RISER DRAWINGS.
  
 13) REQUIRED SUBMITTALS:
 FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE AC
 STANDS, AND THE AIR INTAKE AND EXHAUST OUTLET LOUVERS.
 RANGE HOODS
 DRYERS
 MOTORIZED DAMPERS
 FIRE DAMPERS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status N Date 2018-06-08 Cont ID  
Sent By skennedy Date 2018-06-08 Time 10:39 Rev Time 0.00
Received By skennedy Date 2018-06-08 Time 10:39 Sent To  
Notes
2018-06-08 10:41:08ALL TYPE A BUILDINGS ARE NOT IN A HIGH HAZARD FLOOD
 ZONE.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By aclange Date 2018-04-09 Time 12:44 Rev Time 0.00
Received By aclange Date 2018-04-09 Time 12:44 Sent To  
Notes
2018-04-09 12:45:45 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
  
 NOTES IN BUILDING REVIEW: THE ELEVATION CERTIFICATES
 PROVIDED HAVE NOT BEEN SIGNED AND SEALED. SEE SECTION
 D.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-12-01 Cont ID  
Sent By aclange Date 2017-12-01 Time 13:23 Rev Time 0.00
Received By aclange Date 2017-12-01 Time 13:23 Sent To  
Notes
2017-12-01 13:24:06****PLAN REVIEW COMMENTS****
  
 ART LANGE ? BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
  
 SEE BUILDING REVIEW FOR THESE COMMENTS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-10 Cont ID  
Sent By gjohnson Date 2018-04-10 Time 15:11 Rev Time 0.00
Received By gjohnson Date 2018-04-10 Time 09:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By gjohnson Date 2017-12-22 Time 14:14 Rev Time 0.00
Received By gjohnson Date 2017-12-22 Time 12:04 Sent To  
Notes
2017-12-22 14:33:211ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. LS-0.0 APPLICABLE CODES-AND GUIDE LINES-CHANGE
 FLORIDA ACCESSIBILITY 2012 TO FBC ACC 2014 5TH EDITION
 AND ADD FHA. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE SIZING CALCULATIONS FOR THE ROOR GUTTERS AND
 DOWN SPOUTS. PER FBC PL TABLE 1106.2(2) AND 1106.6
  
 3. SHT.A-7.2 LEGEND #27 THE ELEVATOR SUMP PIT SHALL BE
 A MIN OF 24" DEEP. PER FBC 712.3.2
  
 4. SHT. A-10.1 UNIT A2 AND B3 SHOW FHA DESIGN SPEC FOR
 BATHEOOMS. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A-10.1 UNIT B2 WHAT FHA DESIGN SPEC IS MASTER
 BATH IT IS CALLED OUT AS USABLE PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. SHT. A-10.2 THIS BUILDING IS NOT REQUIRED TO COMPLY
 WITH FBC ACC 2014 I'M CONFUSED ON WHY YOU HAVE DETAILS
 FOR THIS CODE ON THE PLAN COULD YOU PLEASE CLARIFY THIS
 FOR ME. PER WPB AMEND TO FBC 107.2.1
  
 7.SHT. A-10.1 PLEASE PLACE DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE FIXTURES. PER WPB AMEND TO FBC
 107.2.1
  
 8. SHT. A-10.3 PLEASE PROVIDE THE DIMENSION FOR THE TOP
 OF THE BACKING TO FINISH FLOOR ON THE SHOWER DETAIL
 SHALL BE 38" MIN. PER FHA DESIGN MANUAL REQ. 6 PG. 6.12
  
 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B
 BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN
 HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52
  
 10. SHT. A10.1 PROVIDE DIMENSION BETWEEN APPLIANCES AND
 OPPOSING ELEMENTS IN THE KITCHENS. PER FHA DES MAN REQ
 7 PG.7.7
  
 11. SHT. A-10.1 UNIT A2 PLEASE PROVIDE THE DIMENSION OF
 THE WING WALL NEXT TO THE WC IT SHALL BE 24" MAX.. PER
 FHA DESIGN MANUAL. REQ. 7 PG. 7.43
  
 12. THE DRAIN FOR THE ELEVATOR SUMP IS NOT SHOWN ON THE
 SANITARY ISOMETRICS OR THE FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED
 FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB
 AMEND TO FBC 107.2.1
  
 14 PLEASE PLACE NOT ON THE PLAN A SEPARATE PERMIT IS
 REQUIRED FOR THE BACKFLOW ASSEMBLY. PER WPB UTILITIES
 DEPARTMENT
  
 15. ARE THERE ANY FLOOR DRAIN IN THIS BUILDING IT SHOWS
 A DRAIN SCHEDULE ON SHT. P6.1 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-11-29 Cont ID  
Sent By aclange Date 2017-11-29 Time 13:00 Rev Time 0.00
Received By aclange Date 2017-11-29 Time 13:00 Sent To  
Notes
2017-11-29 13:01:04ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
  
 ROOFING PERMIT REQUIRED.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
2017-11-21 09:16:55DEFERRED
2017-11-21 09:16:28ROOFING

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2018-04-23 Cont ID  
Sent By aclange Date 2018-04-23 Time 12:52 Rev Time 0.00
Received By aclange Date 2018-04-23 Time 12:52 Sent To  
Notes
2018-04-23 12:52:57RECEIVED 3 COMPLETE SETS OF THE THRESHOLD / SPECIAL
 INSPECTOR AGREEMENT. THESE ARE TO BE USED BUILDING 1
 THROUGH 7. THE LEASING CENTER IS NOT A THRESHOLD
 PROJECT.
 COPIES SENT TO KEN CONRAD AND RICHARD GATHRIGHT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By aclange Date 2018-04-09 Time 12:43 Rev Time 0.00
Received By aclange Date 2018-04-09 Time 11:41 Sent To  
Notes
2018-04-09 12:43:40 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
  
  
 THRESHOLD BUILDINGS
  
 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
  
 2. PROVIDE RESUME OF JOB INSPECTORS (P.E., ARCH. OR 468
 INSPECTOR).
  
 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
  
 THESE HAVE BEEN EMAILED PREVIOUSLY TO THE ARCHITECT AND
 A AND J PERMITTING.
  
 NOTE; ONCE ONE COMPLETE SET IS REVIEWED AND APPROVE
 THIS CAN BE USED FOR THE ENTIRE PROJECT THAT MEETS THE
 THRESHOLD BUILDING REQUIREMENTS. FOR EXAMPLE: THE
 LEASING CENTER WOULD NOT BE INCLUDED AS WELL AS ANY
 OTHER ASSOCIATE PERMITS FOR THIS PROJECT.
  
 PLEASE ATTACH ALL OF THE PERMIT NUMBERS FOR THE
 PROJECTS THAT WILL BE INCLUDED.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-11-30 Cont ID  
Sent By aclange Date 2017-11-30 Time 15:34 Rev Time 0.00
Received By aclange Date 2017-11-30 Time 15:34 Sent To  
Notes
2017-11-30 15:35:15SEE BUILDING PLAN REVIEW FOR THRESHOLD COMMENTS.

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-05 Cont ID  
Sent By AH Date 2018-06-05 Time   Rev Time 0.00
Received By   Date 2018-06-05 Time   Sent To I
Notes
2018-06-05 16:25:31THIS APPROVAL CORRESPONDS ONLY TO THE BUILDING PLANS
 FOR BUILDING TYPE A AND NOT ANY OTHER DOCUMENTS/PLANS
 INCLUDED IN THE BUILDING PERMIT APPLICATION. PLEASE
 NOTE THAT SEVERAL PLANS INCLUDED IN THE BUILDING PERMIT
 APPLICATION PACKET (WATER AND SANITARY PLAN, PAVING AND
 DRAINAGE PLAN, DIMENSION AND STRIPING PLAN, EROSION
 CONTROL PLAN) SHOW A BIKE RACK AND BIKE PAD IN THE
 NORTHEAST AREA OF BUILDING #6. THIS BIKE RACK AND BIKE
 PAD WAS NOT INCLUDED IN THE APPROVED SITE PLAN AND
 LANDSCAPE PLAN. INCLUSION OF THIS BIKE PAD AND RACK
 WOULD IMPACT REQUIRED LANDSCAPING FOR BUILDING #6. ALL
 OF THE PLANS LISTED ABOVE WHICH DEPICT THIS BIKE
 RACK/PAD WILL NEED TO BE REVISED TO REMOVE THIS
 ELEMENT, OR CONVERSELY, THE APPLICANT WILL NEED TO
 SUBMIT A MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 APPROVED SITE PLAN TO SEEK APPROVAL OF THIS BIKE
 RACK/PAD.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-13 Cont ID  
Sent By   Date 2018-04-13 Time   Rev Time 0.00
Received By ahansen Date 2018-04-13 Time 13:44 Sent To M
Notes
2018-04-13 13:45:13THE BUILDING PERMIT APPLICATION NEEDS TO INCLUDE AND BE
 CONSISTENT WITH THE SITE PLAN THAT WAS APPROVED ON
 4/13/18 THROUGH THE MINOR PD AMENDMENT PROCESS.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AH Date 2017-12-21 Time   Rev Time 0.00
Received By ahansen Date 2017-12-21 Time 11:32 Sent To  
Notes
2017-12-21 11:29:591) THE STANDARD PARKING STALL DETAILS ON THE PLANS DO
 NOT COMPLY WITH THE CITY'S PARKING STALL STANDARDS'
 DIMENSIONS OR STRIPING REQUIREMENTS IN THE ZONING CODE
 OR WITH THE PARKING STALL DETAILS IN THE APPROVED SITE
 PLAN.
  
 2) SHEET SP-2 IN THE SUBMITTAL INCLUDES SEVERAL PARKING
 STRIPING AND BIKE RACK DETAILS WHICH WERE NOT PART OF
 THE APPROVED SITE PLAN AND WHICH DO NOT COMPLY WITH
 CITY STANDARDS.
  
 3) THE BIKE RACK PLAN VIEW SHOWN ON SHEET C12 HAS
 MINIMUM DIMENSIONS OF 12" BETWEEN THE RACKS AND THE
 EDGE OF THE PAD. THESE DIMENSIONS DO NOT COMPLY WITH
 MINIMUM BIKE RACK PAD DIMENSIONS INCLUDED IN APPROVED
 SITE PLAN.
  
 4) THE DIMENSIONS FOR THE PARALLEL PARKING SPACES
 IDENTIFIED ON THE BUILDING PLANS ARE DIFFERENT FROM
 THOSE IN THE APPROVED SITE PLAN. THE WIDTHS OF THE
 PARALLEL SPACES ON THE BUILDING PLANS ARE OF 8.5 FEET
 AND 10 FEET COMPARED TO 8 FEET ON THE SITE PLAN. THE
 APPLICANT NEEDS TO PROVIDE AN EXPLANATION OF HOW THIS
 ADDITIONAL SPACE ON THE PARKING SPACES IMPACTS OTHER
 COMPONENTS OF THE PLAN. THIS EXPLANATION SHOULD INCLUDE
 AN EAST-WEST CROSS SECTION OF THE SITE IN THE AREA
 AROUND BUILDINGS 2 AND 5 THAT COMPARES DIMENSIONS
 BETWEEN THE PROPOSED BUILDING PLAN AND THE APPROVED
 SITE PLAN.
  
 5) THE BIKE RACK DEPICTED ON THE SITE PLAN ON THE NE
 SIDE OF THE PUPPY PARK IS NOT SHOWN ON THE PAVING AND
 STRIPING PLAN INCLUDED IN THIS SUBMITTAL.
  
 6) PLEASE VERIFY THAT THE NUMBER OF PARKING SPACES ON
 THE PLANS ARE CONSISTENT WITH THE PARKING SPACES ON THE
 SITE PLAN. STAFF NOTED SOME INCONSISTENCIES BETWEEN THE
 NUMBER OF SPACES ON SECTIONS OF BOTH PLANS. FOR
 EXAMPLE, THE PAVING AND STRIPING PLAN DEPICTS FIVE (5)
 PARALLEL PARKING SPACES ON THE SE AREA OF THE SITE TO
 THE EAST OF BUILDING 3 WHILE THE SITE PLAN SHOWS SIX
 (6) PARALLEL SPACES ON THIS AREA. IN ADDITION, THE
 PAVING AND STRIPING PLAN SHOWS SIX (6) SPACES ON THE
 ROW LOCATED ON THE SW CORNER OF THE SITE WHILE THE SITE
 PLAN SHOWS FIVE (5) SPACES FOR THIS SAME PARKING ROW.
 SIMILAR TO THE COMMENT ABOVE, THE APPLICANT NEEDS TO
 EXPLAIN HOW THESE DISCREPANCIES IN THE PARKING AREAS
 IMPACT OTHER COMPONENTS OF THE PLAN.
  
 7) THE APPROVAL LETTER FOR THE BELLA VITA MINOR SITE
 PLAN AMENDMENT ISSUED ON OCTOBER 26, 2017 INCLUDES THE
 FOLLOWING CONDITION OF APPROVAL:
 "5. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT
 FOR THE PROJECT, THE LANDSCAPE PLAN, SITE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS SHALL BE REVISED
 TO RELOCATE THE CURBS TO THE POSITION OF THE WHEEL
 STOPS AND PROVIDE A LANDSCAPED OVERHANG WHERE POSSIBLE
 WITHIN THE PARKING AREAS TO PROVIDE MORE PERVIOUS
 LANDSCAPE AREA. THE DESIGN SHALL FOLLOW THE TYPICAL
 PARKING STALL LAYOUT AS SHOWN ON THE APPROVED PLANS. A
 MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE REQUIRED TO
 REFLECT ANY REVISIONS TO THE PLANS." SINCE NO REVISED
 SITE PLAN, LANDSCAPE PLAN, AND ENGINEERING PAVING AND
 DRAINAGE PLANS CONSISTENT WITH THE ABOVE CONDITION HAVE
 BEEN SUBMITTED, THE BUILDING PLANS INCLUDED IN THIS
 PERMIT CANNOT BE APPROVED.
  