Plan Review Details - Permit 17110776
Plan Review Stops For Permit 17110776
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-28 Cont ID  
Sent By jpearson Date 2017-12-28 Time 13:46 Rev Time 0.00
Received By jpearson Date 2017-12-28 Time 13:46 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 12:51 Rev Time 0.00
Received By jpearson Date 2017-12-22 Time 12:51 Sent To I
Notes
2017-12-22 12:51:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS CORRECTED ARE NOTED AS CORRECTED
 REMAINING ITEMS HAVE ADDITIONAL NOTES IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED
 6. THERE ARE 2 SETS OF PLANS PROVIDED, BUT ONLY ONE OF
 THEM SHOWS THE LOCATION OF THE LIGHTS TO BE INSTALLED.
 PROVIDE CORRECTION. FBC 107.2.1 (ONLY ONE PAGE OF THE
 CORRECTED PLAN WAS PROVIDED, WE MUST HAVE 2 SETS,
 ORGANIZED AND STAPLED TOGETHER.)
 7. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1 (ALL SHEETS OF THE
 PLAN MUST BE SIGNED. ONLY ONE SHEET WAS SIGNED.)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 13:24 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 13:24 Sent To I
Notes
2017-11-21 13:24:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AIC RATING OF MAIN PANEL. NEC 110.3, 110.9
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL, INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE DETAIL OF AUTOMATIC LIGHTING CONTROL.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE
 405.2.4; FBC 107.2.1
 5. RISER DIAGRAM SHOWS AN EQUIPMENT GROUNDING CONDUCTOR
 INCLUDED IN THE FEED FROM THE POWER COMPANY, WHICH IS A
 CODE VIOLATION. PROVIDE CORRECTION. NEC 250.6, 250.66,
 250.122
 6. THERE ARE 2 SETS OF PLANS PROVIDED, BUT ONLY ONE OF
 THEM SHOWS THE LOCATION OF THE LIGHTS TO BE INSTALLED.
 PROVIDE CORRECTION. FBC 107.2.1
 7. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-12-28 Time   Rev Time 0.00
Received By cpuell Date 2017-12-27 Time 11:51 Sent To  
Notes
2017-12-28 11:51:43JPEARSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 12:52 Rev Time 0.00
Received By jpearson Date 2017-12-20 Time 13:36 Sent To  
Notes
2017-12-21 13:36:49RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 13:24 Rev Time 0.00
Received By jpearson Date 2017-11-17 Time 11:50 Sent To  
Notes
2017-11-20 11:51:11ROUTED TO ELECTRICAL INBOX