Plan Review Details - Permit 17110711
Plan Review Stops For Permit 17110711
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By aclange Date 2017-11-21 Time 09:09 Rev Time 0.00
Received By aclange Date 2017-11-21 Time 07:51 Sent To  
Notes
2017-11-21 09:13:26****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. SHOWER WALLS: SEE MANUFACTURER APPLICATIONS FOR
 GYPSUM BOARD XP.
  
 "USE IT AS A TILE BACKERBOARD IN DRY AREAS OR AREAS
 WITH LIMITED MOISTURE, SUCH AS TOILET OR SINK AREAS,
 AND WALL AND CEILING AREAS ABOVE TILE IN TUBS AND
 SHOWERS."
  
 PLEASE SELECT A DIFFERENT PRODUCT FOR THE SHOWER WALLS.
 INCLUDE WHAT PRODUCT WILL BE COVERING THE BOARD.
  
 FBC 2509.1 WET AREAS.
 SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO
 SECTION FBC 1210.2.
  
 FBC 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-12-06 Cont ID  
Sent By jpearson Date 2017-12-06 Time 09:02 Rev Time 0.00
Received By jpearson Date 2017-12-06 Time 07:47 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By wjolin Date 2017-11-28 Time 14:16 Rev Time 0.00
Received By wjolin Date 2017-11-28 Time 14:08 Sent To  
Notes
2017-11-28 14:16:438146 OKEECHOBEE BOULEVARD - SUITE 6
 PERMIT #17110711
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER FLORIDA FIRE PREVENTION CODE SECTION 38.2.5.2.2
 (NFPA 101) DEAD-END CORRIDORS SHALL NOT EXCEED 20 FEET
 IN LENGTH IN NON FIRE SPRINKLER PROTECTED BUSINESS
 OCCUPANCIES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-06 Cont ID  
Sent By jpearson Date 2017-12-06 Time 09:07 Rev Time 0.00
Received By jpearson Date 2017-11-16 Time 11:18 Sent To  
Notes
2017-11-20 11:18:26B04

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-29 Cont ID  
Sent By ccole Date 2017-11-29 Time 07:44 Rev Time 0.00
Received By ccole Date 2017-11-28 Time 17:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-30 Cont ID  
Sent By gjohnson Date 2017-11-30 Time 08:56 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 18:11 Sent To  
Notes
2017-11-30 09:28:251ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ALTERNATE ROLL IN TYPE SHOWER SHALL BE 36" WIDE
 48" DOES NOT COMPLY. PER FBC ACC 608.2.3 ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS.
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36
 INCHES WIDE AND 60 INCHES DEEP MINIMUM CLEAR INSIDE
 DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING SIDES.
 A 36 INCH WIDE MINIMUM ENTRY SHALL BE PROVIDED AT ONE
 END OF THE LONG SIDE OF THE COMPARTMENT.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.3
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT
 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR
 SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15
 INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE
 SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY.
  
 3. SHT. 1 NOTE #12 SHALL COMPLY WITH FBC 2509.2 BASE
 FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 O.C. FOR 1/2-INCH THICK (12.7 MM) WATER-RESISTANT
 GYPSUM BACKING BOARD AND MORE THAN 16 INCHES O.C. FOR
 5/8-INCH THICK WATER-RESISTANT GYPSUM BACKING BOARD.
  
 4. THE BRANCH DRAIN OF THE WASHING MACHINE SHALL BE A
 MIN OF 3". PER FBC PL 406.2
  
 5. A LINT TRAP IS REQUIRED ON THE WASHING MACHINE
 DRAIN. PER FBC PL 1003.6
  
 6. THE DRAIN PIPE FOR THE TEMPERATURE AND PRESSURE
 RELIEF VALVE ON THE WATER HEATER SHALL DISCHARGE A MAX
 OF 6" ABOVE S1 OR INTO THE WATER HEATER PAN IT SHALL
 NOT DISCHARGE 1/2" BELOW CEILING AS NOTED ON WATER
 HEATER DETAIL SHT 3. PER FBC PL 504.6 (6)(10)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  