| 2017-12-08 15:50:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS |
| | IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| | EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| | SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 |
| | 2. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| | RE3706.2, RE3902 |
| | 4. NOTE 11 STATES THAT BEDROOM CIRCUITS SHALL COMPLY |
| | WITH 210.12. THIS DOES NOT COVER THE SCOPE OF THIS |
| | ARTICLE, WHICH STATES: "ALL 120-VOLT, SINGLE PHASE, 15 |
| | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION." PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE3902.12 |
| | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 7. PLAN SHOWS STANDARD RECESS LIGHTS IN LASTER CLOSET. |
| | PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| | LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| | BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. |
| | NEC 410.16; FBC RE4003.12 |
| | 8. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |