Plan Review Details - Permit 17110686
Plan Review Stops For Permit 17110686
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By jgomez Date 2017-12-21 Time 16:22 Rev Time 0.00
Received By jgomez Date 2017-12-21 Time 08:33 Sent To  
Notes
2017-12-21 10:31:11RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 3- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION
 DESCRIBES CONVERSION OF GARAGE TO "MOTHER-IN-LAW SUITE"
 AND IS REFERENCING EXPIRED PERMIT APPLICATION
 #08090338. THE EXPIRED PERMIT APPLICATION IS FOR THE
 CONVERSION OF THE GARAGE TO "GAME ROOM" NOT
 "MOTHER-IN-LAW SUITE". NOTE: THERE IS ANOTHER EXPIRED
 PERMIT APPLICATION #07110328 THAT WAS SUBMITTED FOR THE
 CONVERSION OF GARAGE TO GAME ROOM. MOTHER IN LAW SUITE
 AND GAME ROOM ARE TWO DIFFERENT USES. PROPOSED USE
 NEEDS TO BE CLEAR FOR PROPER PLAN REVIEW. ALSO,
 PROPOSED USE NEEDS TO BE APPROVED BY ZONING. REVISE
 DESCRIPTION ON THE PERMIT APPLICATION AND PLANS
 SUBMITTED TO CLEARLY REFLECT THE PROPOSED USE. SEC.
 107.2.1 AND SEC. 102.2 CITY AMENDMENTS.
  
 4- PROVIDE COMPLETE PLANS DRAWN TO SCALE AND CLEARLY
 SHOWING ALL THE SCOPE OF WORK IN DETAIL. CLEARLY
 IDENTIFY EACH ROOM AND SPECIFY ALL ROOMS DIMENSIONS.
 SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: DRAWINGS SUBMITTED FOR EXPIRED PERMIT
 APPLICATIONS WERE DONE BY A PROFESSIONAL ENGINEER.
 PROFESSIONAL DESIGNERS ARE MORE FAMILIAR WITH THE
 PRODUCTION AND COORDINATION OF COMPLETE CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DRAWINGS ARE NOT REQUIRED TO BE
 DONE BY LICENSED DESIGN PROFESSIONALS FOR ONE AND TWO
 FAMILY RESIDENCES, BUT ALL THE CONSTRUCTION DOCUMENTS
 NEED TO BE DRAWN TO SCALE AND WITH ALL THE DESIGN
 CRITERIA TO SHOW COMPLIANCE WITH ALL THE CODE
 REQUIREMENTS. ALL DRAWINGS NEED THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS.
  
 5- THE PLANS NEED TO SPECIFY THE CURRENT CODE AS
 REQUIRED BY CHAPTER 553 FLORIDA STATUTE. ALSO, SPECIFY
 ALL THE WIND LOADS AND BUILDING EXPOSURE (SEC. R301.1
 FBC-RESIDENTIAL), CONSTRUCTION TYPE (SEC. 602.1
 FBC-BUILDING) AND USE AND OCCUPANCY CLASSIFICATION
 (SEC. 302.1 FBC-BUILDING).
  
 6- THE EXISTING GARAGE STRUCTURE IS RISK CATEGORY I.
 CHANGING THE USE OF THE STRUCTURE FROM STORAGE TO
 LIVABLE AREA TRIGGERS A CHANGE OF RISK CATEGORY TO RISK
 CATEGORY II. THEREFORE, THERE IS MORE HAZARD TO HUMAN
 LIFE WHEN THE STRUCTURE FAILS:
 A) PROVIDE COMPLETE PLANS DRAWN TO SCALE AND
 SPECIFICATIONS SHOWING HOW THE STRUCTURE IS REINFORCED
 TO MEET ALL THE LOADS OF CURRENT BUILDING CODE AS
 REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 B) PROVIDE COMPLETE WALL SECTION SHOWING THE LOAD PATH
 FROM THE ROOF TO THE FOUNDATION SHOWING COMPLIANCE WITH
 ALL THE LOADS REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
  
 C) SPECIFY ALL DOORS DESIGN PRESSURES. SEC. R301.1
 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE DETAILS DRAWN TO SCALE AND
 SPECIFICATIONS FOR THE FRAMING OF THE OPENING FOR ALL
 THE NEW FRENCH DOORS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ENERGY CODE. COORDINATE WITH ITEM
 #2 ABOVE. COORDINATE ALL THE CEILING AND WALLS R-VALUE
 INSULATION TO AVOID CONFLICTS/DELAYS. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 9- PLANS TO SHOW COMPLIANCE WITH THE HEATING
 REQUIREMENTS OF SEC. R303.9 FBC-RESIDENTIAL.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ALL EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) HURRICANE SHUTTERS IF DOORS HAVE GLAZING AND IT IS
 NOT IMPACT. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON THE REQUIRED
 FRAMING FRAMING DETAILS AND SECTIONS. PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR.
  
 11- PERSON RESPONSIBLE FOR THE DESIGN TO REVIEW AND
 APPROVE ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 EXTREMELY LOW FOR THE CONVERSION OF A GARAGE TO LIVABLE
 SPACE WITH COMPLETE BATHROOM, KITCHEN, NEW FRENCH
 DOORS, ETC. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR
 OWNER/BUILDERS) AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-08 Cont ID  
Sent By jleahy Date 2017-12-08 Time 16:23 Rev Time 0.00
Received By jleahy Date 2017-12-08 Time 16:23 Sent To  
Notes
2017-12-08 16:28:26FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 FBC RE3706.2, RE3902
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC R314.3, 315.1; FBC 107.2.1
  
  
 PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE
 WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-03 Cont ID  
Sent By cpuell Date 2018-01-03 Time 14:55 Rev Time 0.00
Received By cpuell Date 2017-11-16 Time 12:41 Sent To  
Notes
2017-11-16 12:49:39R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By jgomez Date 2017-12-21 Time 11:16 Rev Time 0.00
Received By jgomez Date 2017-12-21 Time 11:16 Sent To  
Notes
2017-12-21 11:17:051- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By hmoser Date 2017-12-13 Time 09:39 Rev Time 0.00
Received By hmoser Date 2017-12-13 Time 09:30 Sent To  
Notes
2017-12-13 09:39:48PLAN DENIED
 1) REFER TO SECTION 403.6 HEATING AND COOLING
 EQUIPMENT MANDATORY. 2014 FLORIDA ENERGY CODE
 2) NO AIR CONDITIONING PLAN SUBMITTED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By thunt Date 2017-12-04 Time 06:28 Rev Time 0.00
Received By thunt Date 2017-12-04 Time 06:28 Sent To  
Notes
2017-12-04 06:29:1312-04-2017 1ST PLUMBING REVIEW**DENIED**
  
 1) KITCHEN SINK SHALL NOT DISCHARGE INTO THE HORIZONTAL
 WET VENT OF THE BATHROOM GROUP. FPC 912.1
  
 2) SUPPLY MANUFACTURE SPECS AND INSTALLATION MANUAL FOR
 TANKLESS WATER HEATER. PLEASE BE ADVISED WATER HEATER
 MUST BE SIZED SO THAT ALL FIXTURES AT FULL DEMAND HAVE
 HOT WATER OF (110) FPC604.1 AND FPC 607.1
  
 3) PLEASE SEE ZONING COMMENT FROM PLAN REVIEW PERMIT#
 08090338 DATED 02/12/2008, KITCHEN SINK SHALL NOT BE
 PERMITTED
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-12-22 Time   Rev Time  
Received By   Date 2017-12-22 Time   Sent To  
Notes
2017-12-22 16:55:03ZONING: SF14
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]