| Plan Review Stops For Permit 17110679 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-21 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-21 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2017-11-21 07:57:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SEE NOA SUBMITTED. PAGE 2 STATES: "THIS ACCEPTANCE | | | IS FOR GAF MINERAL GUARD RESIDENTIAL ROLL ROOFING, ... | | | FOR USE WITH APPROVED PREPARED ROOF ASSEMBLIES ...." | | | | | | THIS PRODUCT IS A COMPONENT OF AN ASSEMBLY. SUBMIT A | | | PRODUCT APPROVAL WHICH INCLUDES ASSEMBLIES WITH DESIGN | | | PRESSURE LIMITATIONS FOR THE ASSEMBLIES. INDICATE WHICH | | | APPROVED ASSEMBLY IS PROPOSED. IF ASSEMBLY DOES NOT | | | MEET DESIGN PRESSURES FOR ZONES 2 AND 3, ENGINEERING | | | REQUIRED. | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-21 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-16 |
Time |
14:22 |
Sent To |
|
|
| Notes |
|
|
|