Plan Review Details - Permit 17110550
Plan Review Stops For Permit 17110550
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-22 Cont ID  
Sent By pleduc Date 2017-11-27 Time   Rev Time 0.00
Received By pleduc Date 2017-11-22 Time 15:50 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-16 Cont ID  
Sent By cpuell Date 2017-11-17 Time 09:22 Rev Time 0.00
Received By pleduc Date 2017-11-15 Time 16:55 Sent To I
Notes
2017-11-16 13:20:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN INDICATES 48 NEW FLEXHEAD
 SYSTEMS. THE ORIGINAL DESIGN DID NOT INCLUDE FLEX
 HEADS. DUE TO THE INCREASED FRICTION LOSS WITH FLEXHEAD
 SYSTEMS ARE REVIEW AND REVISED HYDRALIC CALCULATION
 SHEET SHLL BE PROVIDED TO ENSURE ADAQUATE WATER SUPPLY.
  
 PLEASE PROVIDE OR CORRECT INSTALL EQUIPMENT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-27 Cont ID  
Sent By cpuell Date 2017-11-27 Time 09:12 Rev Time 0.00
Received By cpuell Date 2017-11-21 Time 11:07 Sent To  
Notes
2017-11-22 11:08:04RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-17 Cont ID  
Sent By cpuell Date 2017-11-17 Time 09:22 Rev Time 0.00
Received By cpuell Date 2017-11-14 Time 08:50 Sent To FIRE
Notes
***NONE***