Plan Review Details - Permit 17110550
| Plan Review Stops For Permit 17110550 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-11-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-22 |
Time |
15:50 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-11-17 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-15 |
Time |
16:55 |
Sent To |
I |
|
| Notes |
| 2017-11-16 13:20:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PLAN INDICATES 48 NEW FLEXHEAD | | | SYSTEMS. THE ORIGINAL DESIGN DID NOT INCLUDE FLEX | | | HEADS. DUE TO THE INCREASED FRICTION LOSS WITH FLEXHEAD | | | SYSTEMS ARE REVIEW AND REVISED HYDRALIC CALCULATION | | | SHEET SHLL BE PROVIDED TO ENSURE ADAQUATE WATER SUPPLY. | | | | | | PLEASE PROVIDE OR CORRECT INSTALL EQUIPMENT. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-11-27 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-11-21 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2017-11-22 11:08:04 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-11-17 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-11-14 |
Time |
08:50 |
Sent To |
FIRE |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |