Plan Review Details - Permit 17110531
Plan Review Stops For Permit 17110531
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 07:20 Rev Time 0.00
Received By aclange Date 2017-12-20 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By aclange Date 2017-11-17 Time 09:57 Rev Time 0.00
Received By aclange Date 2017-11-17 Time 08:48 Sent To  
Notes
2017-11-17 09:58:48****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. CLEAR WIDTH OF DOORWAYS
  
 404.2.4 MANEUVERING CLEARANCES.
  
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
 SEE DOORS AT ROOM 106 AND DOOR BETWEEN ROOMS 100 AND
 109 ON PAGE A-1. FROM THE FRONT, 18 INCHES SHALL BE
 PROVIDED PARALLEL TO THE DOORWAY.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-29 Cont ID  
Sent By jpearson Date 2017-12-29 Time 09:03 Rev Time 0.00
Received By jpearson Date 2017-12-29 Time 09:03 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By jpearson Date 2017-12-04 Time 15:25 Rev Time 0.00
Received By jpearson Date 2017-12-04 Time 14:44 Sent To I
Notes
2017-12-04 15:25:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 2. SHOW ALL EXISTING AND PROPSED LIGHTING AND
 RECEPTACLE OUTLETS ON FLOOR PLAN. INDICATE CIRCUITRY
 FOR NEW ITEMS. FBC 107.2.1
 3. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5
 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC EC 405.7.1
 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-20 Cont ID  
Sent By wjolin Date 2017-12-20 Time 14:27 Rev Time 0.00
Received By wjolin Date 2017-12-20 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-17 Cont ID  
Sent By wjolin Date 2017-11-17 Time 11:13 Rev Time 0.00
Received By wjolin Date 2017-11-17 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-29 Cont ID  
Sent By jpearson Date 2017-12-29 Time 09:03 Rev Time 0.00
Received By jpearson Date 2017-12-13 Time 12:57 Sent To  
Notes
2017-12-14 12:57:49B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-04 Cont ID  
Sent By jpearson Date 2017-12-04 Time 15:26 Rev Time 0.00
Received By jpearson Date 2017-11-14 Time 15:34 Sent To  
Notes
2017-11-14 15:34:43B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By ccole Date 2017-12-22 Time 15:27 Rev Time 0.00
Received By ccole Date 2017-12-22 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By ccole Date 2017-11-21 Time 17:16 Rev Time 0.00
Received By ccole Date 2017-11-21 Time 17:16 Sent To  
Notes
2017-11-21 17:21:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110531
 11/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1. KEYNOTE #8: CORRIDORS SHALL NOT BE USED
 AS A RETURN DUCT- SEE SECTION 601.2. IF THE GRILL IS
 TRANSFERRING AIR INTO A RETURN AIR PLENUM ABOVE THE
 CORRIDOR CEILING IT IS PERMITTED - SEE SECTION 601.2.1
 (1-5.).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-05-01 Cont ID  
Sent By gjohnson Date 2018-05-01 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2018-05-01 Time 11:47 Sent To  
Notes
***NONE***