Plan Review Details - Permit 17110530
Plan Review Stops For Permit 17110530
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 11:44 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 11:04 Sent To I
Notes
2018-03-21 11:44:23NEW SHEET A.02 APPROVED BY ZONING ON 03/13/18.
  
  
2018-03-21 11:36:42BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE MANUFACTURER'S DETAILS & SPECS FOR FACTORY
 BUILT FIREPLACE & CLAY FLUE SPECIFIED ON FLOOR PLANS
 AND SHEET A.13. SHOW COMPLIANCE WITH UL 127.
 2- REVISE ORIENTATION OF EXTERIOR ELEVATIONS ON
 DRAWINGS A.06, A.07, A.08 AND A.09 TO MATCH ACTUAL
 ORIENTATION. NORTHEAST, SOUTHEAST, SOUTHWEST AND
 NORTHWEST.
 3-PROVIDE PRODUCT APPROVAL FOR: A) HARDIE BOARD SOFFIT
 AS SHOWN ON DETAIL 7/A.05. B) PRECAST LINTELS AS
 SPECIFIED ON PLANS.
 4-DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.
 5-SOIL TEST REPORT TO HAVE ORIGINAL SEAL AND SIGNATURE.
 THIS IS NOT A DIGITAL SUBMITTAL.
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-08 Cont ID  
Sent By jgomez Date 2018-03-07 Time 19:01 Rev Time 0.00
Received By jgomez Date 2018-03-07 Time 09:59 Sent To Z
Notes
2018-03-07 10:05:36BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE MANUFACTURER'S DETAILS & SPECS FOR FACTORY
 BUILT FIREPLACE & CLAY FLUE SPECIFIED ON FLOOR PLANS
 AND SHEET A.13. SHOW COMPLIANCE WITH UL 127.
 2- REVISE ORIENTATION OF EXTERIOR ELEVATIONS ON
 DRAWINGS A.06, A.07, A.08 AND A.09 TO MATCH ACTUAL
 ORIENTATION. NORTHEAST, SOUTHEAST, SOUTHWEST AND
 NORTHWEST.
 3-PROVIDE PRODUCT APPROVAL FOR: A) HARDIE BOARD SOFFIT
 AS SHOWN ON DETAIL 7/A.05. B) PRECAST LINTELS AS
 SPECIFIED ON PLANS.
 4-DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.
 5-SOIL TEST REPORT TO HAVE ORIGINAL SEAL AND SIGNATURE.
 THIS IS NOT A DIGITAL SUBMITTAL.
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By jgomez Date 2018-01-18 Time 18:28 Rev Time 0.00
Received By jgomez Date 2018-01-18 Time 18:28 Sent To  
Notes
2018-01-18 18:28:4901/18/18 RESPONDE E-MAIL TO ROY STEPHEN (ARCHITECT):
  
 GOOD EVENING MR. ROY,
 IF YOU HAVE NOTICED, I HAVE MADE MY COMMENT BASED ON
 THE INFORMATION THAT WAS SUBMITTED AT TIME OF PERMIT
 APPLICATION. I DIDN'T SEE ANY PROPERTY APPRAISAL IN THE
 SUBMITTAL. THEREFORE, BASED ON THE INFORMATION OBTAINED
 FROM PALM BEACH COUNTY PROPERTY APPRAISER, THE VALUE OF
 THE STRUCTURE IS $142,509. THAT'S WHY I MADE THE CALL
 FOR THE SUBSTANTIAL IMPROVEMENT. BASED ON THE 50% RULE.
 NOW, BASED ON THE INFORMATION YOU PROVIDED NOW IT LOOKS
 LIKE THE "SUBSTANTIAL IMPROVEMENT" MAY NOT APPLY IN
 THIS CASE.
 THERE ARE TWO THINGS THAT NEED TO BE ADDRESSED:
 FIRST, ACCORDING TO THE CITY REVISED ORDINANCE THE
 "APPRAISAL ANALYSES USED TO ESTABLISH MARKET VALUE
 SHALL HAVE BEEN PERFORMED NO MORE THAN SIX MONTHS PRIOR
 TO THE DATE A PERMIT APPLICATION IS SUBMITTED FOR THE
 PROPOSED IMPROVEMENT". SEE DEFINITION OF MARKET VALUE
 ON SEC. 18-289 OF ORDINANCE NO. 4729-17. THEREFORE,
 NEED TO PROVIDE CURRENT MARKET VALUE ANALYSIS.
 SECOND, THE VALUE SHOWN ON THE PERMIT APPLICATION
 SUBMITTED DOESN'T MATCH THE VALUE OF THE CONSTRUCTION
 BUDGET SUBMITTED NOW. THE VALUE NEED TO BE REVISED ON
 THE PERMIT APPLICATION AND NEED TO ADD YOUR DESIGN
 PROFESSIONAL FEES AS WELL. THE VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS.
 WE NEED ALL THIS INFORMATION UPDATED SO OUR RECORDS
 REFLECT WHY THE PROPOSED IMPROVEMENTS DON'T TRIGGER THE
 SUBSTANTIAL IMPROVEMENT COMPLIANCE AT HIS TIME.
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT
 ME.
 REGARDS,
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
  
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROPOSED SCOPE OF WORK IS CONSIDERED "SUBSTANTIAL
 IMPROVEMENT". BASED ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THE PROPOSED WORK
 EXCEEDS THE 50 PERCENT THE VALUE OF THIS STRUCTURE.
 EXISTING HOUSE AND PROPOSED ADDITION NEED TO COMPLY
 WITH ALL THE REQUIREMENTS OF FLOOD RESISTANT
 CONSTRUCTION, INCLUDING A FREEBOARD OF 2 FEET AS
 REQUIRED BY THE CITY ORDINANCE NO 4729-17 SEC. 18-290.
 PROVIDE COMPLETE PLANS AND CONSTRUCTION DOCUMENTS
 SHOWING COMPLIANCE WITH ALL THE FLOOD RESISTANT
 CONSTRUCTION. SPECIFY ON PLANS ALL FINISHED FLOOR
 ELEVATIONS BASED ON THE FLOOD MAPS THAT WENT INTO
 EFFECT ON OCTOBER 05, 2017. NOTE: REFERENCE THE
 ELEVATION DATUM USED ON THE NEW ADOPTED MAPS TO AVOID
 CONFLICTS/DELAYS.
  
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- ROOF TRUSS DESIGN CRITERIA SPECIFIED ON SHEET S.04
 DOESN'T MATCH ROOF LOADS SPECIFIED THE BOTTOM LEFT OF
 SHEET S.01. REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 COLUMNS SUPPORTING THE SECOND FLOOR STUDY. FOUNDATION
 PLAN ON SHEET S.02 ONLY PROVIDE INFORMATION FOR THE
 FOOTING BUT NO INFORMATION FOR THE COLUMNS. ON THE
 OTHER HAND, THE WALL TYPE LEGEND AND PROPOSED FIRST
 FLOOR PLAN ON SHEET A.04 SHOWS WALL TYPE 3 TO BE A
 METAL FRAMED WALL. PROVIDE SPECIFICATIONS ABOUT
 REINFORCING WALL TO RECEIVE BEAM ABOVE. ALSO, SPECIFY
 CONNECTION OF BEAM TO BEARING WALL. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE MANUFACTURER'S DETAILS AND
 SPECIFICATIONS FOR THE PROPOSED FACTORY BUILT FIREPLACE
 AND CLAY FLUE SHOWING COMPLIANCE WITH SEC. R1004
 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THEM IN
 WRITING PRIOR TO SUBMITTAL.
  
 7- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE TOP CONNECTIONS AT ALL STEEL COLUMNS SHOWN ON PLANS
 (INCLUDING THE ONES FOR THE MASTER BEDROOM BAY WINDOW).
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 THE STEEL COLUMNS SHOWN ON THE COLUMN & BASE PLATE
 SCHEDULE ON SHEET S.02. CLEARLY SHOW LOCATION OF ALL
 SPECIFIED ANCHOR BOLTS AND PROVIDE COMPLETE
 SPECIFICATIONS FOR THE WELDING OF THE STEEL COLUMN TO
 THE PLATE. SEC. R301.1 FBC-RESIDENTIAL.
  
 8- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL
 IS REQUIRED.
  
 9- PROVIDE ICYNENE INSULATION ICC EVALUATION REPORT.
 MAKE SURE REPORT IS CURRENT. SEC. R316 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THEM IN
 WRITING PRIOR TO SUBMITTAL.
  
 10- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR
 THE CARBON MONOXIDE ALARMS REQUIRED FOR ALL EXISTING
 BEDROOM AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 11- NOTE #1 BELOW WALL TYPE LEGEND ON SHEET A.04
 SPECIFIES ROOF INSULATION TO BE ICYNENE. CLARIFY WHAT'S
 R3.6/INCH=R30 STANDS FOR? IS THIS 3.6 INCHES EQUIVALENT
 TO R-30 INSULATION?. NOTE: R-30 ICYNENE INSULATION
 REQUIRES MORE THAN 3.6 THICKNESS. SEE ICYNENE
 EVALUATION REPORT AND REVISE AS REQUIRED. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 12- ROOF PLAN ON SHEET A.05: SPECIFY THE ROOF SLOPE OF
 THE FLAT ROOF AS REQUIRED BY SEC. R905.11.1
 FBC-RESIDENTIAL.
  
 13- WINDOW SCHEDULE ON SHEET A.11 IS INCOMPLETE. IT
 DOESN'T SPECIFY TYPE OF WINDOWS AND NOT ALL THE WINDOWS
 SHOWN ON THE FLOOR PLAN ARE SPECIFIED ON THE WINDOW
 SCHEDULE. PROVIDE COMPLETE INFORMATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
 14- STAIR PLAN ON SHEET A.12: SPECIFY ALL DIMENSIONS.
 SEC. R311.7 FBC-RESIDENTIAL.
  
 15- ORIENTATION OF EXTERIOR ELEVATIONS SPECIFIED ON
 DRAWINGS A.06, A.07, A.08 AND A.09 SEEMS TO BE
 INCORRECT. ACCORDING TO SURVEY AND AERIAL VIEW FROM THE
 PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE THE
 EXTERIOR ELEVATIONS ARE FACING MORE LIKE NORTHEAST,
 SOUTHEAST, SOUTHWEST AND NORTHWEST. REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE: THIS IS AFFECTING HOW THE ENERGY CALCULATIONS
 WERE CALCULATED. ENERGY CALCULATIONS NEED TO BE REVISED
 AS WELL.
  
 16- ENERGY CALCULATIONS SUBMITTED;
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF THE FORM SUBMITTED AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) WALL INSULATION R VALUE SPECIFIED ON ITEM #9 DOESN'T
 MATCH R VALUE SPECIFIED BY THE ARCHITECT UNDER THE WALL
 TYPE LEGEND ON SHEET A.04. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) CEILING INFORMATION R VALUE SPECIFIED ON ITEM #10
 DOESN'T MATCH R VALUE SPECIFIED BY THE ARCHITECT UNDER
 THE WALL TYPE LEGEND ON SHEET A.04. REVISE AS REQUIRED
 TO MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) CLARIFY WHY THE CEILING R-VALUE IN PAGE 2 OF 4 IS
 0.1?. IT DOESN'T MATCH INFORMATION SHOWN ON ITEM #10 ON
 PAGE 1 OF 4. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) ORIENTATION OF BUILDING DOESN'T MATCH THE ACTUAL
 ORIENTATION OF THE BUILDING. SEE SURVEY AND AERIAL VIEW
 FROM THE PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION. COORDINATE WITH ITEM #15 ABOVE.
 (EQUIPMENT SIZING CALCULATIONS SHOW THE CORRECT
 BUILDING ORIENTATION: FRONT DOOR FACES SOUTHEAST).
  
 F) WINDOWS INFORMATION SPECIFIED ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED. COORDINATE WITH ITEM
 #16(E) ABOVE. ALSO, REVISE THE WINDOWS AREA, AND
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) INSWING ENTRY DOOR WITH SIDELITES AS SHOWN ON PLANS.
 NOTE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO DRAWINGS NO 1779 SUBMITTED. IF THERE IS
 NOT FLORIDA PRODUCT APPROVAL, THEN MANUFACTURER MAY
 SUBMIT COMPLETE ORIGINAL ENGINEERING PACKAGE FOR
 BUILDING OFFICIAL APPROVAL. PLEASE CONTACT ME FOR MORE
 INFORMATION REGARDING SUBMITTAL PACKAGE FOR BUILDING
 OFFICIAL APPROVAL.
  
 B) FRENCH DOORS: ONLY ONE COPY OF NOA 14-1015.04 FOR
 SERIES "160 SENTINEL" ALUMINUM DOORS WAS SUBMITTED.
 PROVIDE 2 COPIES.
  
 C) SINGLE HUNG WINDOWS. ONLY ONE COPY OF NOA 15-0512.10
 FOR SERIES "SENTINEL 110" ALUMINUM SINGLE HUNG WINDOW
 WAS SUBMITTED. PROVIDE 2 COPIES.
  
 D) FIXED WINDOWS. ONLY ONE COPY OF NOA 15-0413.03 FOR
 SERIES "SENTINEL 130" ALUMINUM FIXED WINDOW WAS
 SUBMITTED. PROVIDE 2 COPIES.
  
 E) WINDOW MULLIONS. ONLY ONE COPY OF NOA 14-1103.09 WAS
 SUBMITTED. PROVIDE 2 COPIES.
  
 F) ROOF TILE AS SPECIFIED ON PLANS.
  
 G) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 H) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY MARK
 SPECIFIC ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES. NOTE: IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS MAY
 BE NEED IT.
  
 I) HARDIE BOARD SOFFIT AS SHOWN ON DETAIL 7/A.05.
  
 J) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PROVIDE REVIEW STAMP ON THE
 FRONT OF THE COVER (OR ANY OTHER FRONT PAGE) OF THE
 PRODUCT APPROVAL NOT ON THE BACK OF THE PAGE. THIS IS
 REQUIRED FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS
 RETENTION.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-15 Cont ID  
Sent By jgomez Date 2017-12-15 Time 15:21 Rev Time 0.00
Received By jgomez Date 2017-12-13 Time 12:02 Sent To  
Notes
2017-12-12 18:18:21RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROPOSED SCOPE OF WORK IS CONSIDERED "SUBSTANTIAL
 IMPROVEMENT". BASED ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THE PROPOSED WORK
 EXCEEDS THE 50 PERCENT THE VALUE OF THIS STRUCTURE.
 EXISTING HOUSE AND PROPOSED ADDITION NEED TO COMPLY
 WITH ALL THE REQUIREMENTS OF FLOOD RESISTANT
 CONSTRUCTION, INCLUDING A FREEBOARD OF 2 FEET AS
 REQUIRED BY THE CITY ORDINANCE NO 4729-17 SEC. 18-290.
 PROVIDE COMPLETE PLANS AND CONSTRUCTION DOCUMENTS
 SHOWING COMPLIANCE WITH ALL THE FLOOD RESISTANT
 CONSTRUCTION. SPECIFY ON PLANS ALL FINISHED FLOOR
 ELEVATIONS BASED ON THE FLOOD MAPS THAT WENT INTO
 EFFECT ON OCTOBER 05, 2017. NOTE: REFERENCE THE
 ELEVATION DATUM USED ON THE NEW ADOPTED MAPS TO AVOID
 CONFLICTS/DELAYS.
  
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- ROOF TRUSS DESIGN CRITERIA SPECIFIED ON SHEET S.04
 DOESN'T MATCH ROOF LOADS SPECIFIED THE BOTTOM LEFT OF
 SHEET S.01. REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 COLUMNS SUPPORTING THE SECOND FLOOR STUDY. FOUNDATION
 PLAN ON SHEET S.02 ONLY PROVIDE INFORMATION FOR THE
 FOOTING BUT NO INFORMATION FOR THE COLUMNS. ON THE
 OTHER HAND, THE WALL TYPE LEGEND AND PROPOSED FIRST
 FLOOR PLAN ON SHEET A.04 SHOWS WALL TYPE 3 TO BE A
 METAL FRAMED WALL. PROVIDE SPECIFICATIONS ABOUT
 REINFORCING WALL TO RECEIVE BEAM ABOVE. ALSO, SPECIFY
 CONNECTION OF BEAM TO BEARING WALL. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE MANUFACTURER'S DETAILS AND
 SPECIFICATIONS FOR THE PROPOSED FACTORY BUILT FIREPLACE
 AND CLAY FLUE SHOWING COMPLIANCE WITH SEC. R1004
 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THEM IN
 WRITING PRIOR TO SUBMITTAL.
  
 7- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE TOP CONNECTIONS AT ALL STEEL COLUMNS SHOWN ON PLANS
 (INCLUDING THE ONES FOR THE MASTER BEDROOM BAY WINDOW).
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 THE STEEL COLUMNS SHOWN ON THE COLUMN & BASE PLATE
 SCHEDULE ON SHEET S.02. CLEARLY SHOW LOCATION OF ALL
 SPECIFIED ANCHOR BOLTS AND PROVIDE COMPLETE
 SPECIFICATIONS FOR THE WELDING OF THE STEEL COLUMN TO
 THE PLATE. SEC. R301.1 FBC-RESIDENTIAL.
  
 8- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL
 IS REQUIRED.
  
 9- PROVIDE ICYNENE INSULATION ICC EVALUATION REPORT.
 MAKE SURE REPORT IS CURRENT. SEC. R316 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THEM IN
 WRITING PRIOR TO SUBMITTAL.
  
 10- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR
 THE CARBON MONOXIDE ALARMS REQUIRED FOR ALL EXISTING
 BEDROOM AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 11- NOTE #1 BELOW WALL TYPE LEGEND ON SHEET A.04
 SPECIFIES ROOF INSULATION TO BE ICYNENE. CLARIFY WHAT'S
 R3.6/INCH=R30 STANDS FOR? IS THIS 3.6 INCHES EQUIVALENT
 TO R-30 INSULATION?. NOTE: R-30 ICYNENE INSULATION
 REQUIRES MORE THAN 3.6 THICKNESS. SEE ICYNENE
 EVALUATION REPORT AND REVISE AS REQUIRED. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 12- ROOF PLAN ON SHEET A.05: SPECIFY THE ROOF SLOPE OF
 THE FLAT ROOF AS REQUIRED BY SEC. R905.11.1
 FBC-RESIDENTIAL.
  
 13- WINDOW SCHEDULE ON SHEET A.11 IS INCOMPLETE. IT
 DOESN'T SPECIFY TYPE OF WINDOWS AND NOT ALL THE WINDOWS
 SHOWN ON THE FLOOR PLAN ARE SPECIFIED ON THE WINDOW
 SCHEDULE. PROVIDE COMPLETE INFORMATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
 14- STAIR PLAN ON SHEET A.12: SPECIFY ALL DIMENSIONS.
 SEC. R311.7 FBC-RESIDENTIAL.
  
 15- ORIENTATION OF EXTERIOR ELEVATIONS SPECIFIED ON
 DRAWINGS A.06, A.07, A.08 AND A.09 SEEMS TO BE
 INCORRECT. ACCORDING TO SURVEY AND AERIAL VIEW FROM THE
 PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE THE
 EXTERIOR ELEVATIONS ARE FACING MORE LIKE NORTHEAST,
 SOUTHEAST, SOUTHWEST AND NORTHWEST. REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE: THIS IS AFFECTING HOW THE ENERGY CALCULATIONS
 WERE CALCULATED. ENERGY CALCULATIONS NEED TO BE REVISED
 AS WELL.
  
 16- ENERGY CALCULATIONS SUBMITTED;
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF THE FORM SUBMITTED AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) WALL INSULATION R VALUE SPECIFIED ON ITEM #9 DOESN'T
 MATCH R VALUE SPECIFIED BY THE ARCHITECT UNDER THE WALL
 TYPE LEGEND ON SHEET A.04. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) CEILING INFORMATION R VALUE SPECIFIED ON ITEM #10
 DOESN'T MATCH R VALUE SPECIFIED BY THE ARCHITECT UNDER
 THE WALL TYPE LEGEND ON SHEET A.04. REVISE AS REQUIRED
 TO MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) CLARIFY WHY THE CEILING R-VALUE IN PAGE 2 OF 4 IS
 0.1?. IT DOESN'T MATCH INFORMATION SHOWN ON ITEM #10 ON
 PAGE 1 OF 4. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) ORIENTATION OF BUILDING DOESN'T MATCH THE ACTUAL
 ORIENTATION OF THE BUILDING. SEE SURVEY AND AERIAL VIEW
 FROM THE PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION. COORDINATE WITH ITEM #15 ABOVE.
 (EQUIPMENT SIZING CALCULATIONS SHOW THE CORRECT
 BUILDING ORIENTATION: FRONT DOOR FACES SOUTHEAST).
  
 F) WINDOWS INFORMATION SPECIFIED ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED. COORDINATE WITH ITEM
 #16(E) ABOVE. ALSO, REVISE THE WINDOWS AREA, AND
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) INSWING ENTRY DOOR WITH SIDELITES AS SHOWN ON PLANS.
 NOTE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO DRAWINGS NO 1779 SUBMITTED. IF THERE IS
 NOT FLORIDA PRODUCT APPROVAL, THEN MANUFACTURER MAY
 SUBMIT COMPLETE ORIGINAL ENGINEERING PACKAGE FOR
 BUILDING OFFICIAL APPROVAL. PLEASE CONTACT ME FOR MORE
 INFORMATION REGARDING SUBMITTAL PACKAGE FOR BUILDING
 OFFICIAL APPROVAL.
  
 B) FRENCH DOORS: ONLY ONE COPY OF NOA 14-1015.04 FOR
 SERIES "160 SENTINEL" ALUMINUM DOORS WAS SUBMITTED.
 PROVIDE 2 COPIES.
  
 C) SINGLE HUNG WINDOWS. ONLY ONE COPY OF NOA 15-0512.10
 FOR SERIES "SENTINEL 110" ALUMINUM SINGLE HUNG WINDOW
 WAS SUBMITTED. PROVIDE 2 COPIES.
  
 D) FIXED WINDOWS. ONLY ONE COPY OF NOA 15-0413.03 FOR
 SERIES "SENTINEL 130" ALUMINUM FIXED WINDOW WAS
 SUBMITTED. PROVIDE 2 COPIES.
  
 E) WINDOW MULLIONS. ONLY ONE COPY OF NOA 14-1103.09 WAS
 SUBMITTED. PROVIDE 2 COPIES.
  
 F) ROOF TILE AS SPECIFIED ON PLANS.
  
 G) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 H) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY MARK
 SPECIFIC ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES. NOTE: IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS MAY
 BE NEED IT.
  
 I) HARDIE BOARD SOFFIT AS SHOWN ON DETAIL 7/A.05.
  
 J) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PROVIDE REVIEW STAMP ON THE
 FRONT OF THE COVER (OR ANY OTHER FRONT PAGE) OF THE
 PRODUCT APPROVAL NOT ON THE BACK OF THE PAGE. THIS IS
 REQUIRED FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS
 RETENTION.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-01 Cont ID  
Sent By jpearson Date 2018-03-01 Time 12:57 Rev Time 0.00
Received By jpearson Date 2018-03-01 Time 08:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-08 Cont ID  
Sent By jpearson Date 2017-12-08 Time 10:08 Rev Time 0.00
Received By jpearson Date 2017-12-08 Time 10:08 Sent To  
Notes
2017-12-08 10:07:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE FLOOR PLAN FOR ENTIRE DWELLING SHOWING
 SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3,
 315.1; FBC 107.2.1
 2. PLAN SHOWS AN ELECTRICAL J-BOX ABOVE TUB. SINCE THIS
 IS ONLY A 9 FOOT CEILING, AND THE RESTRICTED ZONE ABOVE
 A TUB EXTENDS 8 FEET FROM THE TOP OF THE BATHTUB RIM,
 THIS WOULD BE A VIOLATION. NO PARTS OF CORD-CONNECTED
 LUMINAIRES, CHAIN-, CABLE-, OR CORD-SUSPENDED
 LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC
 RE 4003.11
 3. PLAN SHOWS STANDARD RECESS LIGHTS IN HIS AND HER
 CLOSETS. HER CLOSET ALSO SHOWS AN ELECTRICAL J-BOX THAT
 WOULD APPEAR TO BE FOR CHANDELIERS OR PENDANT FIXTURES.
 PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. A NOTE WILL
 SUFFICE. NEC 210.12; FBC RE3902.12
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 7. PROVIDE LIGHT AND RECEPTACLE IN ATTIC FOR AHU. A
 LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34. FBC RE M1305.1.3.1
 8. OUTSIDE A/C DISCONNECTS ARE SHOWN BEHIND THE A/C
 UNITS IN 2 LOCATIONS. PROVIDE CLEARANCE FOR
 DISCONNECTS. NEC 110.26
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 11:44 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 15:26 Sent To I
Notes
2018-03-20 15:26:44RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-13 Cont ID  
Sent By cpuell Date 2018-03-13 Time 11:12 Rev Time 0.00
Received By cpuell Date 2018-02-07 Time 15:31 Sent To  
Notes
2018-02-08 15:31:26R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-15 Cont ID  
Sent By jgomez Date 2017-12-15 Time 15:37 Rev Time 0.00
Received By jgomez Date 2017-11-14 Time 18:20 Sent To I
Notes
2017-11-14 18:20:33R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 11:36 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 11:36 Sent To  
Notes
2018-03-21 11:37:22NO FEES DUE. MU-2018-008835.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-07 Cont ID  
Sent By jgomez Date 2018-03-07 Time 16:32 Rev Time 0.00
Received By jgomez Date 2018-03-07 Time 16:32 Sent To  
Notes
2018-03-07 16:33:291- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By jgomez Date 2017-12-13 Time 17:05 Rev Time 0.00
Received By jgomez Date 2017-12-13 Time 17:05 Sent To  
Notes
2017-12-13 17:05:331- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-05 Cont ID  
Sent By hmoser Date 2018-03-05 Time 11:19 Rev Time 0.00
Received By hmoser Date 2018-03-05 Time 09:15 Sent To B
Notes
2018-03-05 10:42:06PASS PROVISO
 1) REFER TO SECTION M1307.2 ANCHORAGE
 OF APPLIANCES. 2014 RESIDENTIAL CODE
 2) REFER TO SECTION R403.2.4 AIR HANDLING
 UNITS # 1 2014 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-12-11 Cont ID  
Sent By hmoser Date 2017-12-11 Time 12:36 Rev Time 0.00
Received By hmoser Date 2017-12-11 Time 11:22 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2020-04-15 Cont ID  
Sent By jgomez Date 2020-04-15 Time 09:36 Rev Time 0.00
Received By jgomez Date 2020-04-15 Time 09:21 Sent To  
Notes
2020-04-15 09:40:54NOT SUBSTANTIAL IMPROVEMENT DETERMINED BASED ON
 PROPERTY APPRAISAL FROM JOHN B TRUAX (TRUACCESS
 APPRAISALS, INC) DATED 02/02/2018. APPRAISAL FILED WITH
 CITY 'S RECORDS.
 PROPERTY APPRAISAL WAS DISCUSSED WITH ROBERT BROWN
 (BUILDING OFFICIAL).
  
  
 ADDED THIS REVIEW STOP AS REQUESTED BY SAMANTHA HILL
 FOR CLARIFICATION. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-01 Cont ID  
Sent By tklarge Date 2017-12-01 Time 10:58 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 10:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By jgomez Date 2018-03-08 Time 08:49 Rev Time 0.00
Received By jgomez Date 2018-03-08 Time 08:49 Sent To  
Notes
2018-03-08 08:52:551) FLAT ROOF FL16709-R4. (CERTAINTEED)
 2) CONCRETE TILE NOA 16-0711.05 (BORAL ROOFING)
 3) ROOF TILE ADHESIVE NOA 17-0322.03. (AH-160)
 4) ROOF TILE UNDERLAYMENT NOA 17-614.22. (POLYGLASS)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-12-15 Cont ID  
Sent By jgomez Date 2017-12-15 Time 15:36 Rev Time 0.00
Received By jgomez Date 2017-12-15 Time 13:28 Sent To  
Notes
2017-12-15 15:37:251- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY MARK
 SPECIFIC ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES. NOTE: IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS MAY
 BE NEED IT.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PROVIDE REVIEW STAMP ON THE
 FRONT OF THE COVER (OR ANY OTHER FRONT PAGE) OF THE
 PRODUCT APPROVAL NOT ON THE BACK OF THE PAGE. THIS IS
 REQUIRED FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS
 RETENTION.
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-03-13 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-13 Time 10:10 Sent To  
Notes
2018-03-13 10:10:57PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-02-15 Cont ID  
Sent By AW Date 2018-02-15 Time 09:54 Rev Time 0.00
Received By awooten Date 2018-02-15 Time   Sent To  
Notes
2018-02-15 09:54:10****************************ZONING REVIEW
 FAILED**********************************
  
 PLEASE CLEARLY LABEL ALL SETBACKS ON SITE PLAN (BOTH
 REQUIRED AND PROPOSED).
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AW Date 2017-11-30 Time   Rev Time  
Received By   Date 2017-11-30 Time   Sent To  
Notes
2017-11-30 11:36:35*********************************ZONING REVIEW
 FAILED******************************
  
 PROVIDE A COPY OF THE SURVEY.
  
 PROVIDE SETBACKS FOR AC UNITS (RELOCATED AND NEW).
  
 MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK.
  