Plan Review Details - Permit 17110512
| Plan Review Stops For Permit 17110512 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-15 |
Time |
16:56 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-11-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-11-09 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2018-11-13 14:42:49 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-10-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-10-09 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2018-10-11 09:13:51 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-11-14 |
Time |
16:10 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-19 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-19 |
Time |
12:12 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-10-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-18 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-18 |
Time |
17:22 |
Sent To |
I |
|
| Notes |
| 2018-10-18 17:39:17 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110512 | | | 10/18/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #4 FROM THE1ST REVIEW PRINTED BELOW STILL | | | EXISTS. A) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED IN | | | RESPONSE WITH A COPIED, AND REDUCED SIZE ENGINEER'S INK | | | SIGNATURE AND SEAL. PLEASE NOTE THAT ALL ENGINEERING | | | DOCUMENTS FILED FOR PUBLIC RECORD SHALL BEAR THE | | | ORIGNINAL SIGNATURE AND SEAL OF THE ENGINEER- SECTION | | | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. | | | B) PLEASE CLARIFY HOW SUBMITTAL OF THESE AC LOAD | | | CACLULATIONS ARE PROVING THE CLAIM THAT THE TEMPERATURE | | | DIFFERENTIAL BETWEEN THE HOOD MAKEUP AIR AND THE AIR IN | | | THE KITCHEN DOES NOT EXCEED 10 DEGREES FAHRENTHEIT. | | | THERE IS NO SPECIFIC MAKEUP AIR LOAD REFERENCED IN THE | | | CALCULATION AND THE EQUIPMENT SCHEDULE FOR THE SYSTEM | | | CONDITIONING THE KITCHEN HAS NOT BEEN PROVIDED. | | | | | | 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE | | | EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED | | | SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-11-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-22 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-22 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2017-11-22 08:57:49 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110512 | | | 11/22/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT MANUIFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE THERMAL CERAMICS | | | GREASE DUCT WRAP. | | | | | | 2) PROVIDE THE WIND DESIGN CRITERIA FOR INSTALLATION OF | | | THE ROOF TOP FANS IN ACCORDANCE WITH SECTION 1603.1.4 | | | WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | | STRUCTURE: | | | | | | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, | | | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | | 1609.3.1. | | | 2. RISK CATEGORY. | | | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | | THAN ONE WIND EXPOSURE IS UTILIZED. | | | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ | | | M2). | | | | | | 3) SUBMIT THE MIAMI-DADE NOA'S FOR THE ROOFTOP FANS. | | | | | | 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE | | | EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED | | | SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
|