Plan Review Details - Permit 17110512
Plan Review Stops For Permit 17110512
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-16 Cont ID  
Sent By pleduc Date 2017-11-16 Time   Rev Time 0.00
Received By pleduc Date 2017-11-15 Time 16:56 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-11-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-09 Time 14:42 Sent To  
Notes
2018-11-13 14:42:49RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-10-18 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-09 Time 09:13 Sent To  
Notes
2018-10-11 09:13:51RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-11-22 Time   Rev Time 0.00
Received By cpuell Date 2017-11-14 Time 16:10 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-19 Cont ID  
Sent By ccole Date 2018-11-19 Time 12:12 Rev Time 0.00
Received By ccole Date 2018-11-19 Time 12:12 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-18 Cont ID  
Sent By ccole Date 2018-10-18 Time 17:22 Rev Time 0.00
Received By ccole Date 2018-10-18 Time 17:22 Sent To I
Notes
2018-10-18 17:39:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17110512
 10/18/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #4 FROM THE1ST REVIEW PRINTED BELOW STILL
 EXISTS. A) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED IN
 RESPONSE WITH A COPIED, AND REDUCED SIZE ENGINEER'S INK
 SIGNATURE AND SEAL. PLEASE NOTE THAT ALL ENGINEERING
 DOCUMENTS FILED FOR PUBLIC RECORD SHALL BEAR THE
 ORIGNINAL SIGNATURE AND SEAL OF THE ENGINEER- SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
 B) PLEASE CLARIFY HOW SUBMITTAL OF THESE AC LOAD
 CACLULATIONS ARE PROVING THE CLAIM THAT THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE HOOD MAKEUP AIR AND THE AIR IN
 THE KITCHEN DOES NOT EXCEED 10 DEGREES FAHRENTHEIT.
 THERE IS NO SPECIFIC MAKEUP AIR LOAD REFERENCED IN THE
 CALCULATION AND THE EQUIPMENT SCHEDULE FOR THE SYSTEM
 CONDITIONING THE KITCHEN HAS NOT BEEN PROVIDED.
  
 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED
 SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By ccole Date 2017-11-22 Time 08:26 Rev Time 0.00
Received By ccole Date 2017-11-22 Time 08:26 Sent To  
Notes
2017-11-22 08:57:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110512
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUIFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE THERMAL CERAMICS
 GREASE DUCT WRAP.
  
 2) PROVIDE THE WIND DESIGN CRITERIA FOR INSTALLATION OF
 THE ROOF TOP FANS IN ACCORDANCE WITH SECTION 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 3) SUBMIT THE MIAMI-DADE NOA'S FOR THE ROOFTOP FANS.
  
 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED
 SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  