Plan Review Details - Permit 17110499
Plan Review Stops For Permit 17110499
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-16 Cont ID  
Sent By tklarge Date 2017-11-16 Time 10:51 Rev Time 0.00
Received By tklarge Date 2017-11-15 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By tklarge Date 2017-11-14 Time 13:57 Rev Time 0.00
Received By tklarge Date 2017-11-14 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-16 Cont ID  
Sent By tklarge Date 2017-11-16 Time 10:51 Rev Time 0.00
Received By tklarge Date 2017-11-15 Time 10:50 Sent To  
Notes
2017-11-15 10:51:12APPROVED BY PLUMBING. SENT TO UTILITIES FOR REVIEW.TKL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By tklarge Date 2017-11-14 Time 13:56 Rev Time 0.00
Received By tklarge Date 2017-11-14 Time 13:35 Sent To  
Notes
2017-11-14 13:49:101) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE
 SUBMITTED SPECIFICATIONS DO NOT SHOW THAT THIS DEVICE
 IS LEAD FREE. CITY OF WPB MANUAL FOR CROSS CONNECTION
 CONTROL.
 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 THE SUBMITTED SPECIFICATIONS DO NOT SHOW THAT THIS
 DEVICE IS LISTED ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL
 LIST OF APPROVED DEVICES.
 3) IDENTIFY THE SIZE OF THE DEVICE ON THE PERMIT
 APPLICATION AND ON THE SPECIFICATIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  