Plan Review Details - Permit 17110495
Plan Review Stops For Permit 17110495
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-12-14 Cont ID  
Sent By shill Date 2017-12-14 Time 16:55 Rev Time 0.00
Received By shill Date 2017-12-14 Time 16:55 Sent To  
Notes
2017-12-14 16:56:08PROVISO: DEPT HOTEL & RESTAURANT AND FL DOH APPROVAL
 REQUIRED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-07 Cont ID  
Sent By jwitmer Date 2017-12-07 Time 07:13 Rev Time 0.00
Received By jwitmer Date 2017-12-07 Time 06:27 Sent To P
Notes
2017-12-07 07:13:442014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110495
 ADD: 2302 PRESIDENTIAL WAY
 CONT: MEP CONSTRUCTION GROUP
 TEL: 561-557-5840
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. DEC. 06/ 2017
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE STEWARTS MOBILE
 KITCHEN CONCEPT IS TEMPORARY. THE 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION 108.1
 STATES TEMPORARY STRUCTURES AND TEMPORARY USE PERMITS
 ARE LIMITED AS TO THE TIME OF SERVICE, BUT SHALL NOT BE
 PERMITTED FOR MORE THAN 6 MONTHS.
 IT IS THE CITYS UNDERSTANDING THIS UNIT MAY BE THERE UP
 TO A MINIMUM OF 2 YEARS MAKING THE INSTALLATION A
 PERMANENT STRUCTURE.
  
 1A)2ND REQUEST. PLEASE REVIEW THE M-E-P & GAS COMMENTS.
 PLEASE PROVIDE WHAT AGENCY HAS LISTED OR CERTIFIED THE
 INSTALLATION OF THE ELECTRICAL, PLUMBING AND MECHANICAL
 EQUIPMENT WITHIN THE UNIT ITSELF. WITH THIS
 DOCUMENTATION THE CITYS RESPONSIBILITY WILL BE THE
 ATTACHMENT OF THE ELECTRICAL FROM THE UNIT AS WELL AS
 THE PLUMBING FROM THE UNIT ITSELF.
 110.1.1 MANUFACTURERS AND FABRICATORS. WHEN DEEMED
 NECESSARY BY THE BUILDING OFFICIAL, HE/SHE SHALL MAKE,
 OR CAUSE TO BE MADE, AN INSPECTION OF MATERIALS OR
 ASSEMBLIES AT THE POINT OF MANUFACTURE OR FABRICATION.
 A RECORD SHALL BE MADE OF EVERY SUCH EXAMINATION AND
 INSPECTION AND OF ALL VIOLATIONS OF THE TECHNICAL
 CODES.
  
 1B) 2ND REQUEST, NOT ADDRESSED. THE STEWARTS MOBILE
 KITCHEN WILL NEED TO BE TIED DOWN, ANCHORED TO THE
 GROUND TO RESIST THE MOMENT OF OVERTURNING, SLIDING
 ETC.? STEWARTS BROCHURE FOR THE MODEL K-100 -40 X8
 MOBILE KITCHEN PAGE 2 UNDER THE HEADING CLIENTS
 RESPONSIBILITIES DOES INCLUDE THAT OF DEVELOPING A
 LEVEL AND COMPACTED GROUND SURFACE CAPABLE OF HOLDING A
 COMBINED TOTAL WEIGHT OF 60,000 LBS. PLEASE HAVE
 ENGINEERING FROM A FLORIDA P. E. FOR THE ANCHORING OF
 THIS UNIT SINCE IT IS NO LONGER TO BE CONSIDERED
 TEMPORARY. PROVIDE ANCHORING DETAILS FOR 170 MPH, 3
 SECOND GUST, VULT. PLEASE ALSO PROVIDE AN ANALYSIS FOR
 THE RESISTING THE MOMENT OF OVERTURNING FROM THE EARTH
 ANCHORS SIZE AND DEPTH, STRAP SIZE AND SPACING AND PAD
 SIZE FOR THE UPRIGHT STATIONS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 WIND REQUIREMENTS
 FOUNDATION AND ANCHORING OF UNIT/ STRUCTURAL
 CALCULATIONS
  
 2) THE SUBMITTED PLANS DOES NOT INDICATE IF THE FOOD IS
 SERVED DIRECTLY FROM THE UNIT OR IF THE FOOD IS
 PREPARED IN THE MOBILE UNIT AND TAKEN ELSEWHERE HERE
 ARE OUR CONCERNS:
  
 2A) COMPLIED; CLIENTS DO NOT USE THE STRUCTURE TO GET
 THEIR FOOD, SERVERS.
  
 2B) 2ND REQUEST. THE OTHER CONCERN IS UNDER THE CLIENTS
 RESPONSIBILITY IS TO PROVIDE DETAILS FOR AN ACCESSIBLE
 RAMPS, STAIRS, DECKS, GUARD RAILS AND HANDRAILS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 RAMP
 STAIRS
 DECKS
 HANDRAILS
 GUARDRAILS
  
 201.3 TEMPORARY AND PERMANENT STRUCTURES.
 THESE REQUIREMENTS SHALL APPLY TO TEMPORARY AND
 PERMANENT BUILDINGS AND FACILITIES.
  
 ADVISORY 201.3. TEMPORARY AND PERMANENT STRUCTURES.
 TEMPORARY BUILDINGS OR FACILITIES COVERED BY THESE
 REQUIREMENTS INCLUDE, BUT ARE NOT LIMITED TO, REVIEWING
 STANDS, TEMPORARY CLASSROOMS, BLEACHER AREAS, STAGES,
 PLATFORMS AND DAISES, FIXED FURNITURE SYSTEMS, WALL
 SYSTEMS, AND EXHIBIT AREAS, TEMPORARY BANKING
 FACILITIES, AND TEMPORARY HEALTH SCREENING FACILITIES.
 201.4 SCOPE OF COVERAGE. THIS CODE APPLIES TO FIXED OR
 BUILT-IN ELEMENTS OF BUILDINGS, STRUCTURES, SITE
 IMPROVEMENTS AND PEDESTRIAN ROUTES OR VEHICULAR WAYS
 LOCATED ON A SITE.
  
 2C) NEW COMMENT. THIS UNIT IS TO BE SET OVER 6 MONTHS
 WHICH MEANS IT IS NO LONGER CONSIDERED TEMPORARY, IT IS
 CONSIDERED PERMANENT, WAS NOT MANUFACTURED UNDER THE
 FLORIDA MANUFACTURED BUILDING PROGRAM AND HAS TO COMPLY
 WITH ALL OF THE CODE REQUIREMENTS OF THE 2014 FBC-B.
 2014 FBC-B 1001.1BUILDINGS OR PORTIONS THEREOF SHALL BE
 PROVIDED WITH A MEANS OF EGRESS SYSTEM AS REQUIRED BY
 THIS CHAPTER. THE PROVISIONS OF THIS CHAPTER SHALL
 CONTROL THE DESIGN, CONSTRUCTION AND ARRANGEMENT OF
 MEANS OF EGRESS COMPONENTS REQUIRED TO PROVIDE AN
 APPROVED MEANS OF EGRESS FROM STRUCTURES AND PORTIONS
 THEREOF.
 FBC-B 1009 STAIRWAYS & LANDINGS
 1010 RAMPS
 1012 HANDRAILS
 1013 GUARDS
 1607 & TABLE 1607 LIVE LOADS DECKS AND STAIRS
 1607.8.1 HANDRAILS AND GUARDS.
 1607.8.1.1 CONCENTRATED LOAD.
 1607.8.1.2 INTERMEDIATE RAILS.
  
 2D) EXTERIOR COOLER. STEWARTS MOBILE CONCEPT LEASE
 QUOTE LIST (1) 8 X 12 FOOT MODULAR DUAL TEMP WALK IN
 UNIT, GROUND LEVEL ACCESS. THIS UNIT BEING A MODULAR
 BUILDING SHOULD HAVE BEEN BUILT UNDER THE STATE OF
 FLORIDA MODULAR BUILDING PROGRAM UNDER F. S. 553 PART
 I, 553.35-553.42.
  
 3) COMPLIED. P. B. COUNTY FOR IMPACT FEE REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By jwitmer Date 2017-11-17 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2017-11-17 Time 16:54 Sent To  
Notes
2017-11-17 16:55:202014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110495
 ADD: 2302 PRESIDENTIAL WAY
 CONT: MEP CONSTRUCTION GROUP
 TEL: 561-557-5840
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. NOV. 17/17
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE STEWARTS MOBILE
 KITCHEN CONCEPT IS TEMPORARY. THE 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION 108.1
 STATES TEMPORARY STRUCTURES AND TEMPORARY USE PERMITS
 ARE LIMITED AS TO THE TIME OF SERVICE, BUT SHALL NOT BE
 PERMITTED FOR MORE THAN 6 MONTHS.
 IT IS THE CITYS UNDERSTANDING THIS UNIT MAY BE THERE UP
 TO A MINIMUM OF 2 YEARS MAKING THE INSTALLATION A
 PERMANENT STRUCTURE.
  
 1A) PLEASE PROVIDE WHAT AGENCY HAS LISTED OR CERTIFIED
 THE INSTALLATION OF THE ELECTRICAL, PLUMBING AND
 MECHANICAL EQUIPMENT WITHIN THE UNIT ITSELF. WITH THIS
 DOCUMENTATION THE CITYS RESPONSIBILITY WILL BE THE
 ATTACHMENT OF THE ELECTRICAL FROM THE UNIT AS WELL AS
 THE PLUMBING FROM THE UNIT ITSELF.
 110.1.1 MANUFACTURERS AND FABRICATORS. WHEN DEEMED
 NECESSARY BY THE BUILDING OFFICIAL, HE/SHE SHALL MAKE,
 OR CAUSE TO BE MADE, AN INSPECTION OF MATERIALS OR
 ASSEMBLIES AT THE POINT OF MANUFACTURE OR FABRICATION.
 A RECORD SHALL BE MADE OF EVERY SUCH EXAMINATION AND
 INSPECTION AND OF ALL VIOLATIONS OF THE TECHNICAL
 CODES.
  
 1B) THE STEWARTS MOBILE KITCHEN WILL NEED TO BE TIED
 DOWN, ANCHORED TO THE GROUND TO RESIST THE MOMENT OF
 OVERTURNING, SLIDING ETC.? STEWARTS BROCHURE FOR THE
 MODEL K-100 -40 X8 MOBILE KITCHEN PAGE 2 UNDER THE
 HEADING CLIENTS RESPONSIBILITIES DOES INCLUDE THAT OF
 DEVELOPING A LEVEL AND COMPACTED GROUND SURFACE CAPABLE
 OF HOLDING A COMBINED TOTAL WEIGHT OF 60,000 LBS.
 PLEASE HAVE ENGINEERING FROM A FLORIDA P. E. FOR THE
 ANCHORING OF THIS UNIT SINCE IT IS NO LONGER TO BE
 CONSIDERED TEMPORARY. PROVIDE ANCHORING DETAILS FOR 170
 MPH, 3 SECOND GUST, VULT. PLEASE ALSO PROVIDE AN
 ANALYSIS FOR THE RESISTING THE MOMENT OF OVERTURNING
 FROM THE EARTH ANCHORS SIZE AND DEPTH, STRAP SIZE AND
 SPACING AND PAD SIZE FOR THE UPRIGHT STATIONS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 WIND REQUIREMENTS
 FOUNDATION AND ANCHORING OF UNIT/ STRUCTURAL
 CALCULATIONS
  
 2) THE SUBMITTED PLANS DOES NOT INDICATE IF THE FOOD IS
 SERVED DIRECTLY FROM THE UNIT OR IF THE FOOD IS
 PREPARED IN THE MOBILE UNIT AND TAKEN ELSEWHERE THERE
 IS (2) CONCERNS:
  
 2A) IF THE FOOD IS SERVED FROM THE MOBILE UNIT ITSELF
 HOW DOES A PERSON IN A WHEEL CHAIR GET THEIR FOOD,
 REACH RANGES OF THE 2014 FBC-ACCESSIBILITY CODE IS A
 CONCERN SEE:
 308.2.1 UNOBSTRUCTED FORWARD REACH.
 308.3.1 UNOBSTRUCTED SIDE REACH RANGES.
  
 2B) THE OTHER CONCERN IS UNDER THE CLIENTS
 RESPONSIBILITY IS TO PROVIDE DETAILS FOR AN ACCESSIBLE
 RAMPS, STAIRS, DECKS, GUARD RAILS AND HANDRAILS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 RAMP
 STAIRS
 DECKS
 HANDRAILS
 GUARDRAILS
  
 3) MAY REQUIRE REVIEW FROM P. B. COUNTY FOR IMPACT FEE
 REVIEW. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-12 Cont ID  
Sent By jpearson Date 2017-12-12 Time 07:52 Rev Time 0.00
Received By jpearson Date 2017-12-12 Time 06:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-06 Cont ID  
Sent By jpearson Date 2017-12-06 Time 10:42 Rev Time 0.00
Received By jpearson Date 2017-12-06 Time 10:42 Sent To  
Notes
2017-12-06 10:42:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A CONFLICT EXIST BETWEEN THE RISER DIAGRAM AND THE
 PANEL SCHEDULE FOR PANEL A. RISER SHOWS 3 - #3 COPPER
 GOING TO EACH STORAGE TRAILER, WHILE THE PANEL SCHEDULE
 SHOWS # 6 ON A 60 AMP BREAKER. ADDITIONALLY, THIS FEED
 IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTIONS. NEC 250.122; FBC 107.2.1
 2. PROVIDE PANELS SCHEDULES AND LOADS FOR THE STORAGE
 CONTAINER PANELS TO CONFIRM MAIN PANEL WILL NOT BE
 OVERLOADED. NEC 408.4, 408.30; FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By jpearson Date 2017-11-27 Time 09:42 Rev Time 0.00
Received By jpearson Date 2017-11-27 Time 09:42 Sent To  
Notes
2017-11-27 09:41:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-12-13 Cont ID  
Sent By pleduc Date 2017-12-13 Time   Rev Time 0.00
Received By pleduc Date 2017-12-12 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-12-05 Cont ID  
Sent By pleduc Date 2017-12-05 Time   Rev Time 0.00
Received By pleduc Date 2017-12-05 Time 11:48 Sent To  
Notes
2017-12-05 15:59:422 ND REVIEW RESPONSE:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 DUE TO THIS PLAN BEING FAILED BY OTHER CITY DEPARTMENT
 AND TO ENSURE PREVIOUS FIRE COMMENTS ARE ADDRESSED, THE
 PREVIOUS PROVISO COMMENTS SHALL BE ADDRESSED ON ALL
 FUTURE SUBMITTALS.
  
  
  
 1) PLEASE PROVIDE ALL THE APPLICABLE DOCUMENTS OF THE
 HOOD SUPPRESSION SYSTEM TESTING. A TEST OF THE SYSTEM
 MAY BE REQUIRED BASED ON THE INSPECTION FINDINGS.
  
 PROVIDE APPLICABLE DOCUMENTS OF TESTING AND COMPLIANCE.
  
  
  
 2) THE INSTALLATION OF THE LP TANKS SHALL BE UNDER
 SEPARATE SHOP DRAWINGS.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) PLEASE ENSURE THERE IS A TYPE K AND ABC FIRE
 EXTINGUISHER INSTALLED IN A APPLICABLE LOCATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS TO THE ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-16 Cont ID  
Sent By pleduc Date 2017-11-16 Time   Rev Time 0.00
Received By pleduc Date 2017-11-15 Time 16:56 Sent To  
Notes
2017-11-16 12:59:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PLEASE PROVIDE ALL THE APPLICABLE DOCUMENTS OF THE
 HOOD SUPPRESSION SYSTEM TESTING. A TEST OF THE SYSTEM
 MAY BE REQUIRED BASED ON THE INSPECTION FINDINGS.
  
  
 2) THE INSTALLATION OF THE LP TANKS SHALL BE UNDER
 SEPARATE SHOP DRAWINGS.
  
  
 3) PLEASE ENSURE THERE IS A TYPE K AND ABC FIRE
 EXTINGUISHER INSTALLED IN A APPLICABLE LOCATION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 14:37 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 14:37 Sent To  
Notes
2017-11-28 14:38:41GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-14 Cont ID  
Sent By shill Date 2017-12-14 Time 16:56 Rev Time 0.00
Received By shill Date 2017-12-08 Time 15:24 Sent To  
Notes
2017-12-11 15:24:16B17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-07 Cont ID  
Sent By gjohnson Date 2017-12-07 Time 12:36 Rev Time 0.00
Received By gjohnson Date 2017-12-01 Time 10:30 Sent To  
Notes
2017-12-04 10:30:21B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-04 Cont ID  
Sent By lmarchan Date 2017-12-04 Time 10:25 Rev Time 0.00
Received By lmarchan Date 2017-11-13 Time 10:30 Sent To  
Notes
2017-11-14 10:32:30B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-12-07 Cont ID  
Sent By jwitmer Date 2017-12-07 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-12-07 Time 06:27 Sent To  
Notes
2017-12-07 07:15:33P. B. C. IMPACT FEE OFFICE
 RECEIPT NUMBER 2017-1129-367
 TRACKING NUMBER MU-2017-032404-0000
 FEES PAID: $2,048.94

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By jwitmer Date 2017-11-17 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2017-11-17 Time 16:55 Sent To  
Notes
2017-11-17 16:56:24) MAY REQUIRE REVIEW FROM P. B. COUNTY FOR IMPACT FEE
 REVIEW. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-12-14 Cont ID  
Sent By ccole Date 2017-12-13 Time 16:27 Rev Time 0.00
Received By ccole Date 2017-12-13 Time 16:27 Sent To  
Notes
2017-12-13 16:31:56MECHANICAL PROVISO:
  
 THE PERMIT IS FOR A TEMPORARY MOBILE KITCHEN TO BE ON
 SITE AT THE FACILITY FOR NO LONGER THAN 180 DAYS.
  
 A SEPARATE PERMIT AND INSPECTIONS ARE REQUIRED FOR ANY
 ONSITE MECHANICAL WORK.
  
 NO EVIDENCE OF LICENSURE BY THE DBPR FOOD LICENSING
 DIVISON FOR THE MOBILE KITCHEN HAS BEEN PROVIDED TO THE
 WPB BUILDING DEPARTMENT.
  
 THE OWNERSHIP AND CONTRACTOR HAVE BEEN ADVISED THAT THE
 TRAILER NEEDS TO STATE LICENSED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
 \

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By ccole Date 2017-12-05 Time 08:16 Rev Time 0.00
Received By ccole Date 2017-12-05 Time 08:16 Sent To  
Notes
2017-12-05 08:40:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110495
 12/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I HAVE REVIEWED THE STATEMENT OF COMPLIANCE DOCUMENT
 FROM MEP CONSULTING ENGINEERS FOR THE MOBILE KITCHEN.
 PLEASE ADDRESS THE FOLLOWING COMMENTS:
  
 A) THE LETTER DOES NOT INCLUDE THE FBC MECHANICAL CODE
 5TH EDITION -2014 IN THE CODE COMPLIANCE STATEMENT.
  
 B) PLEASE CLARIFY THE FOLLOWING STATEMENT IN THE
 DOCUMENT- "STRUCTURE AND EQUIPMENT ARE IN ACCORDANCE TO
 MINIMUM STANDARDS FOR AUXILIARY KITCHEN USE". PLEASE
 INDICATE FROM WHICH CODE OR STANDARD THE "MINIMUM
 STANDARDS" ARE DERIVED FROM, AND PROVIDE AN ITEMIZED
 CHECKLIST OF ALL THE MECHANICAL EQUIPMENT AND SYSTEMS
 THAT WERE INSPECTED AND TESTED IN ACCORDANCE WITH THOSE
  
 STANDARDS.
  
 C) CLARIFY IF THE KITCHEN EXHAUST HOOD AND FIRE
 SUPPRESSION SYSTEMS WERE INSPECTED AS PART OF THE
 CERTIFICATION PROCEDURE. THE WEST PALM BEACH BUILDING
 DEPARTMENT POLICY REGARDING KITCHEN EXHAUST HOODS AND
 FIRE SUPPRESSION SYSTEMS IS THAT SEPARATE PERMITS ARE
 REQUIRED FOR EACH, AND COMPLETE ENGINEERED PLANS MUST
 BE SUBMITTED FOR REVIEW- PLEASE SEE SECTIONS 506, 507,
 508,
  
 AND 509 FOR COMPLETE COMPLIANCE INFORMATION, AND SUBMIT
 PLANS AND SPECIFICATIONS UNDER SEPARATE PERMITS.
  
 D) PROVIDE A COMPLETE KITCHEN APPLIANCE AND EQUIPMENT
 LIST THAT INCLUDES THE MAKES AND MODELS OF THE COOKING
 APPLIANCES, THE KITCHEN HOOD, HOOD EXHAUST AND SUPPLY
 FANS. REFER TO THE CODE SECTIONS LISTED IN COMMENT 1C,
 AND ALSO SECTION 623 FBC-14 FUEL GAS.
  
 E) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR
 THE GAS-FIRED COOKING APPLIANCES AND PROVIDE A
 CALCULATION- SECTION 304 FBC-14 FUEL GAS.
  
 2) THE SUBMITTED QUOTE FROM STEWART'S MOBILE CONCEPTS
 LTD. INCLUDES AN 8'X12' MODULAR DUAL TEMP WALK-IN UNIT.
 NO PLANS OR ENGINEERING CERTIFICATION HAS BEEN
 SUBMITTED FOR THE UNIT AND IT IS NOT SHOWN ON THE SITE
 PLAN. PLEASE NOTE THAT A FLORIDA PRODUCT APPROVAL FOR
 THE UNIT MUST BE SUBMITTED AS REQUIRED BY FAC RULE
 9N-3.
  
 3) PLEASE ADJUST THE PERMIT VALUE ON THE APPLICATION TO
 MATCH THE DELIVERY, INSTALLATION, AND LEASE FEES LISTED
 IN THE QUOTE- SECTION 109.3 WPB AMENDMENTS TO THE FBC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-12-14 Cont ID  
Sent By gjohnson Date 2017-12-14 Time 16:44 Rev Time 0.00
Received By gjohnson Date 2017-12-14 Time 16:44 Sent To  
Notes
2017-12-14 16:46:38PLUMBING PROVISO: 12/14/17
  
 PLUMBING COMMENTS: SANITARY AND WATER CONNECTIONS
 APPROVED PERMITTED UNDER 17100565
  
 1. PLEASE PROVIDE CERTIFICATION FROM FLORIDA DIVISION
 OF HOTELS AND RESTAURANTS. PER FS CH 509 REQUIRED FOR
 FINAL INSPECTION
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-12-07 Cont ID  
Sent By gjohnson Date 2017-12-07 Time 12:32 Rev Time 0.00
Received By gjohnson Date 2017-12-07 Time 12:32 Sent To  
Notes
2017-12-07 12:36:032ND REVIEW REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: SANITARY AND WATER CONNECTIONS
 APPROVED PERMITTED UNDER 17100565
  
 1. PLEASE PROVIDE CERTIFICATION FROM FLORIDA DIVISION
 OF HOTELS AND RESTAURANTS. PER FS CH 509
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 14:26 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 10:13 Sent To  
Notes
2017-11-28 14:37:191ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER SERVICE PIPING SHALL COMPLY WITH FBC PL
 603 AND TABLE 605.3
  
 2. A BACKFLOW IS REQUIRED ON THE WATER SERVICE PIPING.
 PER FBC PL 608.3
  
 3. PLEASE PROVIDE SITE PLAN SHOWING WATER SERVICE,
 GREASE INTERCEPTOR AND SANITARY SEWER. PER WPB AMEND TO
 FBC 107.2.1
  
 4. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-12-06 Cont ID  
Sent By jroach Date 2017-12-06 Time 15:43 Rev Time 0.00
Received By jroach Date 2017-12-06 Time 15:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-01 Cont ID  
Sent By JR Date 2017-12-01 Time 11:33 Rev Time 0.00
Received By jroach Date 2017-12-01 Time 11:33 Sent To  
Notes
***NONE***