Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-15 Cont ID  
Sent By pleduc Date 2017-12-15 Time   Rev Time 0.00
Received By pleduc Date 2017-12-14 Time 15:11 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By pleduc Date 2017-11-14 Time   Rev Time 0.00
Received By pleduc Date 2017-11-13 Time 15:28 Sent To I
Notes
2017-11-14 12:26:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE CALCULATIONS FOR THE DESIGN AREA FOR FL # 2
 INDICATES 4 HEADS. THE PLAN SHEET DOES NOT HAVE THE
 CORRESPONDING AREAS INDICATED.
  
 PLEASE INDICATED THE DESIGN AREA WITH LINES/BOUNDARIES
 AND INCLUDE DIMENSIONS.
  
  
 2) THE DESIGN AREA ON THE 2ND FLOOR INDICATES 4 HEADS.
 THE SQ/FT OF THIS AREA IS NOT INDICATED.
  
 WHAT NFPA 13 CODE ARE YOU USING FOR THIS CALCULATION?
 WHERE IS THIS AREA?
  
 PLEASE PROVIDE DETAILS
  
  
 3) THE COMPUTER DESIGN FACE SHEETS INDICATE REMOTE AREA
 1 ON EACH SHEET. THE REMOTE AREAS, THOUGH ON SEPARATE
 FLOORS, SHOULD NOT BE INDICATED AS THE SAME; SHOULD BE
 # 1 & # 2
  
 PLEASE CORRECT
  
  
 4) THE COMPUTER DESIGN OF 1ST FL, PAGE # 1, DOES NOT
 INDICATE THE TYPE OF CALCULATION.
  
 PLEASE CORRECT OR JUSTIFY.
  
  
 5) THE COMPUTER DESIGN OF 1ST FL, PAGE # 1, UNDER
 "SIZE: INDICATES 3/4". SHEET FP -1 INDICATES TYCO EC-14
 AS "SIZE 1/2".
  
 PLEASE CORRECT OF JUSTIFY.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-12-12 Time 15:00 Sent To  
Notes
2017-12-13 15:00:25RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-13 Cont ID  
Sent By lmarchan Date 2017-12-13 Time 14:58 Rev Time 0.00
Received By lmarchan Date 2017-11-13 Time 12:36 Sent To  
Notes
2017-11-13 12:36:30ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved