Plan Review Details - Permit 17110445
| Plan Review Stops For Permit 17110445 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-12-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-14 |
Time |
15:11 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-11-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-13 |
Time |
15:28 |
Sent To |
I |
|
| Notes |
| 2017-11-14 12:26:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE CALCULATIONS FOR THE DESIGN AREA FOR FL # 2 | | | INDICATES 4 HEADS. THE PLAN SHEET DOES NOT HAVE THE | | | CORRESPONDING AREAS INDICATED. | | | | | | PLEASE INDICATED THE DESIGN AREA WITH LINES/BOUNDARIES | | | AND INCLUDE DIMENSIONS. | | | | | | | | | 2) THE DESIGN AREA ON THE 2ND FLOOR INDICATES 4 HEADS. | | | THE SQ/FT OF THIS AREA IS NOT INDICATED. | | | | | | WHAT NFPA 13 CODE ARE YOU USING FOR THIS CALCULATION? | | | WHERE IS THIS AREA? | | | | | | PLEASE PROVIDE DETAILS | | | | | | | | | 3) THE COMPUTER DESIGN FACE SHEETS INDICATE REMOTE AREA | | | 1 ON EACH SHEET. THE REMOTE AREAS, THOUGH ON SEPARATE | | | FLOORS, SHOULD NOT BE INDICATED AS THE SAME; SHOULD BE | | | # 1 & # 2 | | | | | | PLEASE CORRECT | | | | | | | | | 4) THE COMPUTER DESIGN OF 1ST FL, PAGE # 1, DOES NOT | | | INDICATE THE TYPE OF CALCULATION. | | | | | | PLEASE CORRECT OR JUSTIFY. | | | | | | | | | 5) THE COMPUTER DESIGN OF 1ST FL, PAGE # 1, UNDER | | | "SIZE: INDICATES 3/4". SHEET FP -1 INDICATES TYCO EC-14 | | | AS "SIZE 1/2". | | | | | | PLEASE CORRECT OF JUSTIFY. | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-12 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2017-12-13 15:00:25 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-12-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-12-13 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-11-13 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2017-11-13 12:36:30 | ROUTED TO FIRE INBOX |
|
|
|