Plan Review Details - Permit 17110439
Plan Review Stops For Permit 17110439
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-05 Cont ID  
Sent By cthroop Date 2017-12-05 Time 15:41 Rev Time 0.00
Received By cthroop Date 2017-12-05 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By cthroop Date 2017-11-21 Time 10:14 Rev Time 0.00
Received By cthroop Date 2017-11-21 Time 09:58 Sent To E
Notes
2017-11-21 10:19:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PLAN DESIGNED, SIGNED AND SEALED BY A
 FLORIDA LICENSED DESIGN PROFESSIONAL.
 2. PROVIDE DESIGN WIND LOADS FOR PROPOSED CONTAINERS.
 3. PROVIDE DETAIL FOR FOUNDATION.
 4. PROVIDE DETAIL FOR STRUCTURAL ATTACHMENMT TO
 FOUNDATION.
 5. PROVIDE SITE PLAN. DEMONSTRATE SETBACKS TO PROPERTY
 LINES AND OTHER STRUCTURES ON SITE.
  
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-12 Cont ID  
Sent By jpearson Date 2017-12-12 Time 12:47 Rev Time 0.00
Received By jpearson Date 2017-12-12 Time 12:47 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-05 Cont ID  
Sent By jpearson Date 2017-12-05 Time 11:48 Rev Time 0.00
Received By jpearson Date 2017-12-05 Time 11:48 Sent To  
Notes
2017-12-05 11:49:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENT NOT ADDRESSED, NO ELECTRICAL PLAN
 PROVIDED.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 10:44 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 10:44 Sent To M
Notes
2017-11-21 10:44:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-17 Cont ID  
Sent By pleduc Date 2017-11-17 Time   Rev Time 0.00
Received By pleduc Date 2017-11-16 Time 15:06 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-12 Cont ID  
Sent By jpearson Date 2017-12-12 Time 12:48 Rev Time 0.00
Received By jpearson Date 2017-12-08 Time 13:34 Sent To  
Notes
2017-12-11 13:34:13RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-06 Cont ID  
Sent By cpuell Date 2017-12-06 Time 16:31 Rev Time 0.00
Received By cpuell Date 2017-12-01 Time 10:32 Sent To  
Notes
2017-12-04 10:32:40B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 08:35 Rev Time 0.00
Received By gjohnson Date 2017-11-09 Time 08:22 Sent To  
Notes
2017-11-13 08:22:54ROUTED TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-12-05 Cont ID  
Sent By ccole Date 2017-12-05 Time 07:39 Rev Time 0.00
Received By ccole Date 2017-12-05 Time 07:33 Sent To  
Notes
2017-12-05 07:42:36SEPARATE PERMITS REQUIRED FOR ANY ONSITE MECHANICAL
 WORK.
 CCOLE-12/5/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By ccole Date 2017-11-21 Time 12:35 Rev Time 0.00
Received By ccole Date 2017-11-21 Time 12:35 Sent To  
Notes
2017-11-21 12:49:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110439
 11/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BAG STORAGE BUILDING IS OMITTED FROM THE
 DESCRIPTION OF WORK ON THE PERMIT APPLICATION - PLEASE
 ADD THE BUILDING.
  
 2) THE JOB VALUE OF $800.00 ON THE APPLICATION APPEARS
 LOW FOR THE SCOPE OF WORK. IN ACCORDANCE WITH SECTION
 109.3 WPB AMENDMENTS TO THE FBC, PROVIDE A VALUE THAT
 INCLUDES LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN
 FEES, AND PROFIT
  
 AND OVERHEAD.
  
 3) NO MECHANICAL PLANS WERE SUBMITTED TO CLARIFY HOW
 THE BUIDINGS WILL BE VENTILATED. PLEASE PROVIDE PLANS
 THAT INCLUDE A SCOPE OF WORK OUTLINE, VENTILATION
 CALCULATIONS, AND INSTALLATION DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-12-05 Cont ID  
Sent By gjohnson Date 2017-12-05 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2017-12-05 Time 15:44 Sent To  
Notes
2017-12-05 15:47:43NO PLUMBING PER PLAN FILE STORAGE AND BAG STORAGE ONLY
 FOOD TRUCK UNDER SEPARATE PERMIT/ GPJ 12/5/17

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 08:29 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 08:29 Sent To  
Notes
2017-11-28 08:35:221ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE FLOOR PLAN OF FOOD TRAILER AND STATE
 CERTIFICATION. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE A SITE PLAN THAT SHOWS SANITARY AND POTABLE
 WATER CONNECTIONS. PER WPB AMEND TO FBC 107.2.1
  
 3. A BACKFLOW IS REQUIRED ON WATER SUPPLY TO TRAILER.
 FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-12-06 Cont ID  
Sent By JR Date 2017-12-06 Time 16:17 Rev Time 0.00
Received By jroach Date 2017-12-06 Time 16:00 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By JR Date 2017-11-15 Time 08:38 Rev Time 0.00
Received By jroach Date 2017-11-14 Time 11:39 Sent To FIRE
Notes
2017-11-15 08:38:48ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.15.2017
 PERMIT NO.: 17110439
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SITE PLAN PROVIDED IS NOT THE CURRENT SITE PLAN, AND
 IS NOT AN ACCURATE REFLECTION OF WHAT WAS BUILT IN THE
 FIELD. BE SURE TO PROVIDE A CURRENT AND ACCURATE SITE
 PLAN.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH