Plan Review Details - Permit 17110437
| Plan Review Stops For Permit 17110437 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-12-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-12-08 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-12-08 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2017-12-08 14:21:09 | VALUE SET BY OWNER AT $17,000. CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-12-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-12-08 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-12-07 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2017-12-08 10:13:28 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. CANNOT DETERMINE VALUE. 2ND REQUEST. PROVIDE A | | | CONTRACT, SIGNED BY OWNER OR VALUE WILL BE SET BY | | | BUILDING OFFICIAL BASED ON THE MARSHALL-SWIFT | | | CONSTRUCTION VALUE GUIDE. | | | 2. 4X FEE WILL BE ASSED AFTER VALUE HAS BEEN | | | DETERMINED. | | | | | | BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE | | | DETERMINED AT THIS TIME. | | | THE PERMIT VALUATION AND PERMIT FEE MUST BE | | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | | CONTRACTOR WOULD PROVIDE. | | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | | RENTAL TO VERIFY VALUE. | | | | | | CITY OF WPB CHPT. 1 - VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-11-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-11-22 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-11-22 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2017-11-22 10:15:02 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PLAN SIGNED AND SEALED BY A FLORIDA LICENSED | | | DESIGN PROFESSIONAL. | | | 2. DESIGN SHALL COMPLY WITH FBC SECTION 3102. INCLUDE | | | DESIGN WIND LOADS FOR STRUCTURE. | | | 3. PROVIDE FLAME SPREAD TEST RESULTS PER ASTM E-84 FOR | | | TENT FABRIC. | | | 4. PROVIDE ANCHORING DETAIL PER FLORIDA LICENSED | | | PROFESSIONAL ENGINEER. | | | 5. IF TENT IS TO REMAIN FOR A PERIOD OF 180 DAYS OR | | | LONGER IT CANNOT BE CLASSIFIED AS A TEMPORARY | | | STRUCTURE, SEE SECTION FBC 3103. PLEASE RE-CLASSIFY | | | STRUCTURE. | | | 6. IF TENT IS OPEN TO THE GENERAL PUBLIC IT MUST MEET | | | ADA REQUIREMENTS (PARKING, ACCESSIBLE ROUTE, ACCESSIBLE | | | ENTRANCE, ETC. PER FBC ACCESSIBILITY CODE). | | | 7. VALUE CANNOT BE DETERMINED. PROVIDE A COPY OF | | | CONTRACT SIGNED BY OWNER. | | | 8. ONCE VALUE HAS BEEN DETERMINED, 4X FEE SHALL BE | | | APPLIED PER ROBERT BROWN, B.O. FOR WORK WITHOUT PERMIT. | | | | | | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY | | | CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA | | | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES& | | | 61G1 FLORIDA ADMINISTRATIVE CODE. | | | | | | 3102.1 GENERAL. | | | THE PROVISIONS OF SECTIONS 3102.1 THROUGH 3102.8 SHALL | | | APPLY TO AIR-SUPPORTED, AIR-INFLATED, MEMBRANE-COVERED | | | CABLE AND MEMBRANE-COVERED FRAME STRUCTURES, | | | COLLECTIVELY KNOWN AS MEMBRANE STRUCTURES, ERECTED FOR | | | A PERIOD OF 180 DAYS OR LONGER. | | | | | | FBC 603.1 FLAME SPREAD ? ASTM E-84-09. | | | | | | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING | | | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA | | | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION | | | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL | | | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING | | | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: | | | | | | BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE | | | DETERMINED AT THIS TIME. | | | THE PERMIT VALUATION AND PERMIT FEE MUST BE | | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | | CONTRACTOR WOULD PROVIDE. | | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | | RENTAL TO VERIFY VALUE. | | | | | | | | | CITY OF WPB CHPT. 1 - VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-21 |
Time |
11:04 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-11-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-14 |
Time |
13:56 |
Sent To |
I |
|
| Notes |
| 2017-11-15 09:08:08 | THE RESUBMITTED PLANS ARE IDENTICAL FROM THE PREVIOUS. | | | THERE ARE 7 COMMENTS THAT HAVE NOT BEEN PROPERLY | | | ADDRESSED. NEW COMMENTS HAVE BEEN PROVIDED AND THE | | | PREVIOUS ONES HAVE BEEN RE-POSTED. | | | | | | NEW COMMENTS: | | | | | | 1) THE SUBMITTED PLANS INDICATE A TENT SIZE OF 72' | | | X110'. THE PRINTED SPEC SHEET INDICATES 40' X 100'. | | | WHICH IS CORRECT. | | | | | | FOR OFFICIAL AND FINAL LOCATION PURPOSES, THE PLANS | | | SHALL INDICATE THE ACTUAL SIZE AND OUTLINED WITH THAT | | | MEASUREMENT. ADDITIONALLY, ANY SUPPORTING MATERIAL | | | SHALL INDICATE THE THE ACTUAL SIZE FOR THE INFORMATION | | | DOES NOT CONFLICT. | | | | | | | | | 2) THE PREVIOUS COMMENTS LISTED BELOW SHALL BE | | | ADDRESSED FOR OFFICIAL DOCUMETATION PURPOSES. | | | | | | ORIGINAL COMMENTS: | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO LOCATION INDICATED ON THE SITE PLAN | | | WHERE THE PROPOSED TENT WILL BE LOCATED. PROVIDING A | | | CLOUD AROUND A LARGE AREA WITH MULTIPLE BUILDINGS IS | | | INSUFFICIENT. | | | | | | PLEASE PROVIDE THE EXACT LOCATION. | | | | | | | | | 2) THE APPLICATION INDICATES THIS PROPOSED TENT FOR | | | TEMPRARY PARKING FOR GOLF CART PARKING. | | | | | | HOW LONG A TIME PERIOD IS BEING PROPOSED? | | | | | | PLEASE PROVIDE AN ENDING DATE. | | | | | | | | | | | | 3) THE APPLICATION INDICATES THIS PROPOSED TENT FOR | | | TEMPRARY PARKING FOR GOLF CART PARKING. | | | | | | ARE THESE ELECTRIC CARTS OR GASOLINE? | | | | | | IS THERE ANY ELECTRICITY BEING PROPOSED? USE OF | | | EXTENSION CORDS? GASOLINE STORAGE CANS? | | | | | | | | | | | | 4) THERE IS NO INDICATIONS OF ANY TIE-DOWN INFORMATION | | | OR DIAGRAMS. | | | | | | HOW WILL THIS PROPOSED TENT BE SECURED? | | | | | | | | | | | | 5) THERE IS A PICTURE OF A SIDE-WALL TENT INFORMATION | | | PATCH. WILL THIS PROPOSED TENT HAVE SIDEWALLS ALL | | | AROUND? | | | | | | IF SO, WHERE WILL THE EXIT DOORS BE LOCATED? A MINIMUM | | | OF TWO IS REQUIRED AND THEY SHALL BE SEPARATED PER NFPA | | | 101, CHAPTER 7 MEANS OF EGRESS. | | | | | | | | | | | | 6) PER # 5 ABOVE, HOW WILL THE EXITS BE IDENTIFIED? | | | | | | PLEASE PROVIDE REQUIRED EXIT IDENTIFICATION. | | | | | | | | | | | | 7) THERE ARE NO FIRE EXTINGUISHERS INDICATED. | | | | | | PLEASE PROVIDE A MINIMUM OF ONE 10 ABC FE, HOWEVER, | | | BASED ON # # 3 ABOVE 2 OR MORE MAY BE REQUIRED. | | | | | | | | | | | | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-11-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-13 |
Time |
12:25 |
Sent To |
I |
|
| Notes |
| 2017-11-13 13:30:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO LOCATION INDICATED ON THE SITE PLAN | | | WHERE THE PROPOSED TENT WILL BE LOCATED. PROVIDING A | | | CLOUD AROUND A LARGE AREA WITH MULTIPLE BUILDINGS IS | | | INSUFFICIENT. | | | | | | PLEASE PROVIDE THE EXACT LOCATION. | | | | | | | | | 2) THE APPLICATION INDICATES THIS PROPOSED TENT FOR | | | TEMPRARY PARKING FOR GALF CART PARKING. | | | | | | HOW LONG A TIME PERIOD IS BEING PROPOSED? | | | | | | PLEASE PROVIDE AN ENDING DATE. | | | | | | | | | | | | 3) THE APPLICATION INDICATES THIS PROPOSED TENT FOR | | | TEMPRARY PARKING FOR GALF CART PARKING. | | | | | | ARE THESE ELECTRIC CARTS OR GASOLINE? | | | | | | IS THERE ANY ELECTRICITY BEING PROPOSED? USE OF | | | EXTENSION CORDS? GASOLINE STORAGE CANS? | | | | | | | | | | | | 4) THERE IS NO INDICATIONS OF ANY TIE-DOWN INFORMATION | | | OR DIAGRAMS. | | | | | | HOW WILL THIS PROPOSED TENT BE SECURED? | | | | | | | | | | | | 5) THERE IS A PICTURE OF A SIDE-WALL TENT INFORMATION | | | PATCH. WILL THIS PROPOSED TENT HAVE SIDEWALLS ALL | | | AROUND? | | | | | | IF SO, WHERE WILL THE EXIT DOORS BE LOCATED? A MINIMUM | | | OF TWO IS REQUIRED AND THEY SHALL BE SEPARATED PER NFPA | | | 101, CHAPTER 7 MEANS OF EGRESS. | | | | | | | | | | | | 6) PER # 5 ABOVE, HOW WILL THE EXITS BE IDENTIFIED? | | | | | | PLEASE PROVIDE REQUIRED EXIT IDENTIFICATION. | | | | | | | | | | | | 7) THERE ARE NO FIRE EXTINGUISHERS INDICATED. | | | | | | PLEASE PROVIDE A MINIMUM OF ONE 10 ABC FE, HOWEVER, | | | BASED ON # # 3 ABOVE 2 OR MORE MAY BE REQUIRED. | | | | | | | | | | | | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-12-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-12-08 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-12-06 |
Time |
09:55 |
Sent To |
I |
|
| Notes |
| 2017-12-07 09:55:45 | RESUB ROUTED TO CTHROOP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-11-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-11-22 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-11-17 |
Time |
13:44 |
Sent To |
I |
|
| Notes |
| 2017-11-20 13:45:07 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-11-15 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-11-13 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2017-11-13 14:54:36 | RESUB ROUTED TO TEMP TENT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-11-13 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-11-09 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2017-11-13 08:15:47 | ROUTED TO TEMP TENT |
|
|
|