Plan Review Details - Permit 17110437
Plan Review Stops For Permit 17110437
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-12-08 Cont ID  
Sent By cthroop Date 2017-12-08 Time 14:20 Rev Time 0.00
Received By cthroop Date 2017-12-08 Time 14:20 Sent To  
Notes
2017-12-08 14:21:09VALUE SET BY OWNER AT $17,000. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-08 Cont ID  
Sent By cthroop Date 2017-12-08 Time 10:08 Rev Time 0.00
Received By cthroop Date 2017-12-07 Time 16:50 Sent To  
Notes
2017-12-08 10:13:28BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT DETERMINE VALUE. 2ND REQUEST. PROVIDE A
 CONTRACT, SIGNED BY OWNER OR VALUE WILL BE SET BY
 BUILDING OFFICIAL BASED ON THE MARSHALL-SWIFT
 CONSTRUCTION VALUE GUIDE.
 2. 4X FEE WILL BE ASSED AFTER VALUE HAS BEEN
 DETERMINED.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 09:32 Rev Time 0.00
Received By cthroop Date 2017-11-22 Time 09:09 Sent To  
Notes
2017-11-22 10:15:02BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PLAN SIGNED AND SEALED BY A FLORIDA LICENSED
 DESIGN PROFESSIONAL.
 2. DESIGN SHALL COMPLY WITH FBC SECTION 3102. INCLUDE
 DESIGN WIND LOADS FOR STRUCTURE.
 3. PROVIDE FLAME SPREAD TEST RESULTS PER ASTM E-84 FOR
 TENT FABRIC.
 4. PROVIDE ANCHORING DETAIL PER FLORIDA LICENSED
 PROFESSIONAL ENGINEER.
 5. IF TENT IS TO REMAIN FOR A PERIOD OF 180 DAYS OR
 LONGER IT CANNOT BE CLASSIFIED AS A TEMPORARY
 STRUCTURE, SEE SECTION FBC 3103. PLEASE RE-CLASSIFY
 STRUCTURE.
 6. IF TENT IS OPEN TO THE GENERAL PUBLIC IT MUST MEET
 ADA REQUIREMENTS (PARKING, ACCESSIBLE ROUTE, ACCESSIBLE
 ENTRANCE, ETC. PER FBC ACCESSIBILITY CODE).
 7. VALUE CANNOT BE DETERMINED. PROVIDE A COPY OF
 CONTRACT SIGNED BY OWNER.
 8. ONCE VALUE HAS BEEN DETERMINED, 4X FEE SHALL BE
 APPLIED PER ROBERT BROWN, B.O. FOR WORK WITHOUT PERMIT.
  
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 3102.1 GENERAL.
 THE PROVISIONS OF SECTIONS 3102.1 THROUGH 3102.8 SHALL
 APPLY TO AIR-SUPPORTED, AIR-INFLATED, MEMBRANE-COVERED
 CABLE AND MEMBRANE-COVERED FRAME STRUCTURES,
 COLLECTIVELY KNOWN AS MEMBRANE STRUCTURES, ERECTED FOR
 A PERIOD OF 180 DAYS OR LONGER.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-21 Cont ID  
Sent By pleduc Date 2017-11-21 Time   Rev Time 0.00
Received By pleduc Date 2017-11-21 Time 11:04 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-11-15 Cont ID  
Sent By pleduc Date 2017-11-15 Time   Rev Time 0.00
Received By pleduc Date 2017-11-14 Time 13:56 Sent To I
Notes
2017-11-15 09:08:08THE RESUBMITTED PLANS ARE IDENTICAL FROM THE PREVIOUS.
 THERE ARE 7 COMMENTS THAT HAVE NOT BEEN PROPERLY
 ADDRESSED. NEW COMMENTS HAVE BEEN PROVIDED AND THE
 PREVIOUS ONES HAVE BEEN RE-POSTED.
  
 NEW COMMENTS:
  
 1) THE SUBMITTED PLANS INDICATE A TENT SIZE OF 72'
 X110'. THE PRINTED SPEC SHEET INDICATES 40' X 100'.
 WHICH IS CORRECT.
  
 FOR OFFICIAL AND FINAL LOCATION PURPOSES, THE PLANS
 SHALL INDICATE THE ACTUAL SIZE AND OUTLINED WITH THAT
 MEASUREMENT. ADDITIONALLY, ANY SUPPORTING MATERIAL
 SHALL INDICATE THE THE ACTUAL SIZE FOR THE INFORMATION
 DOES NOT CONFLICT.
  
  
 2) THE PREVIOUS COMMENTS LISTED BELOW SHALL BE
 ADDRESSED FOR OFFICIAL DOCUMETATION PURPOSES.
  
 ORIGINAL COMMENTS:
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO LOCATION INDICATED ON THE SITE PLAN
 WHERE THE PROPOSED TENT WILL BE LOCATED. PROVIDING A
 CLOUD AROUND A LARGE AREA WITH MULTIPLE BUILDINGS IS
 INSUFFICIENT.
  
 PLEASE PROVIDE THE EXACT LOCATION.
  
  
 2) THE APPLICATION INDICATES THIS PROPOSED TENT FOR
 TEMPRARY PARKING FOR GOLF CART PARKING.
  
 HOW LONG A TIME PERIOD IS BEING PROPOSED?
  
 PLEASE PROVIDE AN ENDING DATE.
  
  
  
 3) THE APPLICATION INDICATES THIS PROPOSED TENT FOR
 TEMPRARY PARKING FOR GOLF CART PARKING.
  
 ARE THESE ELECTRIC CARTS OR GASOLINE?
  
 IS THERE ANY ELECTRICITY BEING PROPOSED? USE OF
 EXTENSION CORDS? GASOLINE STORAGE CANS?
  
  
  
 4) THERE IS NO INDICATIONS OF ANY TIE-DOWN INFORMATION
 OR DIAGRAMS.
  
 HOW WILL THIS PROPOSED TENT BE SECURED?
  
  
  
 5) THERE IS A PICTURE OF A SIDE-WALL TENT INFORMATION
 PATCH. WILL THIS PROPOSED TENT HAVE SIDEWALLS ALL
 AROUND?
  
 IF SO, WHERE WILL THE EXIT DOORS BE LOCATED? A MINIMUM
 OF TWO IS REQUIRED AND THEY SHALL BE SEPARATED PER NFPA
 101, CHAPTER 7 MEANS OF EGRESS.
  
  
  
 6) PER # 5 ABOVE, HOW WILL THE EXITS BE IDENTIFIED?
  
 PLEASE PROVIDE REQUIRED EXIT IDENTIFICATION.
  
  
  
 7) THERE ARE NO FIRE EXTINGUISHERS INDICATED.
  
 PLEASE PROVIDE A MINIMUM OF ONE 10 ABC FE, HOWEVER,
 BASED ON # # 3 ABOVE 2 OR MORE MAY BE REQUIRED.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-13 Cont ID  
Sent By pleduc Date 2017-11-13 Time   Rev Time 0.00
Received By pleduc Date 2017-11-13 Time 12:25 Sent To I
Notes
2017-11-13 13:30:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO LOCATION INDICATED ON THE SITE PLAN
 WHERE THE PROPOSED TENT WILL BE LOCATED. PROVIDING A
 CLOUD AROUND A LARGE AREA WITH MULTIPLE BUILDINGS IS
 INSUFFICIENT.
  
 PLEASE PROVIDE THE EXACT LOCATION.
  
  
 2) THE APPLICATION INDICATES THIS PROPOSED TENT FOR
 TEMPRARY PARKING FOR GALF CART PARKING.
  
 HOW LONG A TIME PERIOD IS BEING PROPOSED?
  
 PLEASE PROVIDE AN ENDING DATE.
  
  
  
 3) THE APPLICATION INDICATES THIS PROPOSED TENT FOR
 TEMPRARY PARKING FOR GALF CART PARKING.
  
 ARE THESE ELECTRIC CARTS OR GASOLINE?
  
 IS THERE ANY ELECTRICITY BEING PROPOSED? USE OF
 EXTENSION CORDS? GASOLINE STORAGE CANS?
  
  
  
 4) THERE IS NO INDICATIONS OF ANY TIE-DOWN INFORMATION
 OR DIAGRAMS.
  
 HOW WILL THIS PROPOSED TENT BE SECURED?
  
  
  
 5) THERE IS A PICTURE OF A SIDE-WALL TENT INFORMATION
 PATCH. WILL THIS PROPOSED TENT HAVE SIDEWALLS ALL
 AROUND?
  
 IF SO, WHERE WILL THE EXIT DOORS BE LOCATED? A MINIMUM
 OF TWO IS REQUIRED AND THEY SHALL BE SEPARATED PER NFPA
 101, CHAPTER 7 MEANS OF EGRESS.
  
  
  
 6) PER # 5 ABOVE, HOW WILL THE EXITS BE IDENTIFIED?
  
 PLEASE PROVIDE REQUIRED EXIT IDENTIFICATION.
  
  
  
 7) THERE ARE NO FIRE EXTINGUISHERS INDICATED.
  
 PLEASE PROVIDE A MINIMUM OF ONE 10 ABC FE, HOWEVER,
 BASED ON # # 3 ABOVE 2 OR MORE MAY BE REQUIRED.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-08 Cont ID  
Sent By cthroop Date 2017-12-08 Time 10:13 Rev Time 0.00
Received By cthroop Date 2017-12-06 Time 09:55 Sent To I
Notes
2017-12-07 09:55:45RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 10:15 Rev Time 0.00
Received By cthroop Date 2017-11-17 Time 13:44 Sent To I
Notes
2017-11-20 13:45:07RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-15 Cont ID  
Sent By cpuell Date 2017-11-15 Time 11:28 Rev Time 0.00
Received By cpuell Date 2017-11-13 Time 14:54 Sent To  
Notes
2017-11-13 14:54:36RESUB ROUTED TO TEMP TENT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-13 Cont ID  
Sent By lmarchan Date 2017-11-13 Time 14:54 Rev Time 0.00
Received By lmarchan Date 2017-11-09 Time 08:15 Sent To  
Notes
2017-11-13 08:15:47ROUTED TO TEMP TENT