| 2017-11-17 14:46:15 | |
| | |
| | |
| | |
| | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THERE IS A CARD READER INDICATED ON THE ELEVATOR |
| | LOBBY EXIT ACCESS DOOR. |
| | |
| | PER NFPA 101, CHAPTER 39, EXISITNG BUSINESS OCCUPANCIES |
| | |
| | 39.2.2.2.3 ELEVATOR LOBBY EXIT ACCESS DOOR-LOCKING |
| | ARRANGEMENTS |
| | IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE PERMITTED. |
| | |
| | 7.2.1.6.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES |
| | LOCKING. |
| | WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR |
| | ASSEMBLIES |
| | SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS |
| | REQUIRED BY |
| | 7.4.1.6.1 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED, |
| | PROVIDED THAT ALL |
| | THE FOLLOWING CRITERIA ARE MET: |
| | (1) THE LOCK IS LISTED IN ACCORDANCE WITH ANSI/UL 294, |
| | STANDARD |
| | FOR ACCESS CONTROL SYSTEM UNITS. |
| | (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE |
| | ALARM SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.6. |
| | (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7. |
| | (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY |
| | 7.2.1.6.3(3) IS |
| | ARRANGED TO INITIATE THE BUILDING FIRE ALARM SYSTEM. |
| | (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED, |
| | SUPERVISED |
| | SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| | (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED |
| | BY |
| | 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING FIRE |
| | ALARM SYSTEM |
| | AND NOTIFY BUILDING OCCUPANTS. |
| | (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY |
| | OTHER THAN MANUAL |
| | FIRE ALARM BOXES UNLOCKS THE ELEVATOR LOBBY DOOR |
| | ASSEMBLY. |
| | (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK |
| | SYSTEM |
| | UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES. |
| | (9) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES |
| | REMAIN UNLOCKED |
| | UNTIL THE BUILDING FIRE ALARM SYSTEM HAS BEEN MANUALLY |
| | RESET. |
| | (10) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN |
| | LATCHED AFTER |
| | BEING UNLOCKED, LATCH-RELEASING HARDWARE IN ACCORDANCE |
| | WITH |
| | 7.2.1.5.10 IS AFFIXED TO THE DOOR LEAVES. |
| | (11) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR |
| | COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL |
| | CONTROL |
| | POINT THAT IS CONSTANTLY STAFFED. |
| | (12) THE CENTRAL CONTROL POINT STAFF REQUIRED BY |
| | 7.2.1.6.3(11) IS CAPABLE, |
| | TRAINED, AND AUTHORIZED TO PROVIDE EMERGENCY |
| | ASSISTANCE. |
| | (13) THE PROVISIONS OF 7.2.1.6.1 FOR DELAYED-EGRESS |
| | LOCKING SYSTEMS |
| | ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES. |
| | (14)*THE PROVISIONS OF 7.2.1.6.2 FOR ACCESS-CONTROLLED |
| | EGRESS DOOR |
| | ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR |
| | ASSEMBLIES. |
| | |
| | A.7.2.1.6.3(14) IT IS NOT THE INTENT TO PROHIBIT |
| | ELEVATOR LOBBY |
| | DOORS FROM BEING EQUIPPED WITH CARD ACCESS SYSTEMS FOR |
| | GAINING |
| | ACCESS, FOR EXAMPLE, TO TENANT SPACES. IT IS THE ACCESS |
| | CONTROLLED |
| | EGRESS DOOR SYSTEM DESCRIBED IN 7.2.1.6.2 THAT IS |
| | PROHIBITED FROM BEING INSTALLED ON THE SAME DOOR AS THE |
| | LOCK |
| | ADDRESSED BY 7.2.1.6.3. |
| | |
| | PLEASE ENSURE THAT THE CARD READER COMPLIAS WITH ALL OF |
| | THE REQUIREMENTS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |