Plan Review Details - Permit 17110391
Plan Review Stops For Permit 17110391
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-01 Cont ID  
Sent By jpearson Date 2018-02-01 Time 14:48 Rev Time 0.00
Received By jpearson Date 2018-02-01 Time 14:47 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 08:44 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 08:44 Sent To I
Notes
2017-11-21 08:46:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-17 Cont ID  
Sent By pleduc Date 2017-11-17 Time   Rev Time 0.00
Received By pleduc Date 2017-11-17 Time 09:28 Sent To E
Notes
2017-11-17 14:46:15 
  
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS A CARD READER INDICATED ON THE ELEVATOR
 LOBBY EXIT ACCESS DOOR.
  
 PER NFPA 101, CHAPTER 39, EXISITNG BUSINESS OCCUPANCIES
  
 39.2.2.2.3 ELEVATOR LOBBY EXIT ACCESS DOOR-LOCKING
 ARRANGEMENTS
 IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE PERMITTED.
  
 7.2.1.6.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES
 LOCKING.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 REQUIRED BY
 7.4.1.6.1 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED,
 PROVIDED THAT ALL
 THE FOLLOWING CRITERIA ARE MET:
 (1) THE LOCK IS LISTED IN ACCORDANCE WITH ANSI/UL 294,
 STANDARD
 FOR ACCESS CONTROL SYSTEM UNITS.
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM IN
 ACCORDANCE WITH SECTION 9.6.
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7.
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS
 ARRANGED TO INITIATE THE BUILDING FIRE ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED
 SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 9.6.
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY
 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM
 AND NOTIFY BUILDING OCCUPANTS.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL
 FIRE ALARM BOXES UNLOCKS THE ELEVATOR LOBBY DOOR
 ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM
 UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED
 UNTIL THE BUILDING FIRE ALARM SYSTEM HAS BEEN MANUALLY
 RESET.
 (10) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER
 BEING UNLOCKED, LATCH-RELEASING HARDWARE IN ACCORDANCE
 WITH
 7.2.1.5.10 IS AFFIXED TO THE DOOR LEAVES.
 (11) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL
 POINT THAT IS CONSTANTLY STAFFED.
 (12) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(11) IS CAPABLE,
 TRAINED, AND AUTHORIZED TO PROVIDE EMERGENCY
 ASSISTANCE.
 (13) THE PROVISIONS OF 7.2.1.6.1 FOR DELAYED-EGRESS
 LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (14)*THE PROVISIONS OF 7.2.1.6.2 FOR ACCESS-CONTROLLED
 EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 A.7.2.1.6.3(14) IT IS NOT THE INTENT TO PROHIBIT
 ELEVATOR LOBBY
 DOORS FROM BEING EQUIPPED WITH CARD ACCESS SYSTEMS FOR
 GAINING
 ACCESS, FOR EXAMPLE, TO TENANT SPACES. IT IS THE ACCESS
 CONTROLLED
 EGRESS DOOR SYSTEM DESCRIBED IN 7.2.1.6.2 THAT IS
 PROHIBITED FROM BEING INSTALLED ON THE SAME DOOR AS THE
 LOCK
 ADDRESSED BY 7.2.1.6.3.
  
 PLEASE ENSURE THAT THE CARD READER COMPLIAS WITH ALL OF
 THE REQUIREMENTS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-01 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-31 Time 10:11 Sent To  
Notes
2018-02-01 10:11:10RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 08:45 Rev Time 0.00
Received By jpearson Date 2017-11-09 Time 08:25 Sent To  
Notes
2017-11-13 08:25:15ROUTED TO FIRE INBOX