Plan Review Details - Permit 17110388
Plan Review Stops For Permit 17110388
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By pleduc Date 2017-11-13 Time   Rev Time 0.00
Received By pleduc Date 2017-11-13 Time 12:25 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-09-05 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-21 Time 14:24 Sent To  
Notes
2018-09-04 13:16:12TO L MARCHANT
2018-08-22 14:24:42RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-08-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-07 Time 14:53 Sent To  
Notes
2018-08-10 14:30:18TO LMARCHAN.
2018-08-08 14:53:45RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-01 Cont ID  
Sent By cpuell Date 2018-03-01 Time 13:24 Rev Time 0.00
Received By cpuell Date 2018-02-07 Time 13:59 Sent To  
Notes
2018-02-28 17:06:322/28 TO AA DESK
  
  
2018-02-28 14:00:032/28 TO CC DESK
  
2018-02-08 13:59:41RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-04 Cont ID  
Sent By cpuell Date 2017-12-04 Time 15:21 Rev Time 0.00
Received By cpuell Date 2017-11-09 Time 10:06 Sent To  
Notes
2017-11-13 10:06:44ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-09-05 Cont ID  
Sent By ccole Date 2018-09-05 Time 11:07 Rev Time 0.00
Received By ccole Date 2018-09-05 Time 10:30 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-08-13 Cont ID  
Sent By ccole Date 2018-08-13 Time 15:59 Rev Time 0.00
Received By ccole Date 2018-08-13 Time 13:43 Sent To I
Notes
2018-08-13 16:05:473RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17110388
 8/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BASED ON THE SUBMITTED AC SIZING CALCULATIONS FOR
 THE KITCHEN, ALEX KHAROSKA OF CREDO CONSULTING
 ENGINEERS IS STATING IN HIS LETTER THAT THE EXISTING
 8-TON COOLING SYSTEM PERMITTED UNDER THE MASTER PERMIT
 #17020359, MUST BE ENLARGED TO A 10-TON SYSTEM TO
 ABSORB THE ADDITIONAL HEAT LOAD IN THE KITCHEN FROM THE
 EXHAUST HOOD MAKE UP AIR. PLEASE PROVIDE A PERMIT
 APPLICATION AND PLAN FOR ENLARGING THE SYSTEM.- SECTION
 107.2.1 WEST PALM BEACH AMENDMENTS TO THE FBC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 16:56 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 14:05 Sent To  
Notes
2018-02-28 17:04:292ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17110388
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN AN EFFORT TO SHOW THE COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE FOR THE KITCHEN HOOD
 EXHAUST SYSTEM, THE ENGINEER HAS SUBMITTED AC LOAD
 CALCULATIONS , HOWEVER THE CALCULATIONS PROVIDE GENERAL
 HEAT LOAD DATA FOR THE KITCHEN IN BTUH, BUT DO NOT
 SPECIFICALLY INDICATE THE HEAT LOAD FROM THE MAKEUP
 AIR, OR INDICATE THAT THE AC SYSTEM HAS BEEN SIZED TO
  
 ACCOMODATE THE ADDED LOAD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-18 Cont ID  
Sent By ccole Date 2017-11-18 Time 08:48 Rev Time 0.00
Received By ccole Date 2017-11-18 Time 08:48 Sent To Z
Notes
2017-11-18 08:55:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110388
 11/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) VERIFY COMPLIANCE WITH SECTION 508.1.1: MAKEUP AIR
 TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ROOFTOP FANS AND THE MAKEUP AIR DUCT ON THE
 EXTERIOR WALL. PLEASE PROVIDE THE DESIGN CRITERIA PER
 SECTION 1609 FBC-014 BUILDING, AND THE MIAMI-DADE NOA'S
 FOR THE FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-09-04 Cont ID  
Sent By aaponte Date 2018-09-04 Time 13:00 Rev Time 0.00
Received By aaponte Date 2018-09-04 Time 13:00 Sent To  
Notes
2018-09-04 13:15:48PROVISO:1. DUCT SHALL BE PAINTED IN THE SAME COLOR THAN
 THE WALL TO MINIMIZE IMPACT.
 2. PARAPET WALL SHALL BE THE SAME HEIGHT THAN
 EQUIPEMENT.

Review Stop Z ZONING
Rev No 3 Status F Date 2018-08-10 Cont ID  
Sent By aaponte Date 2018-08-10 Time 14:29 Rev Time 0.00
Received By aaponte Date 2018-08-10 Time 14:28 Sent To M
Notes
2018-08-10 14:29:521. REPEAT COMMENT: PARAPET WALL SHALL BE RAISED TO BE
 THE SAME HEIGHT OF PROPOSED EQUIPMENT TO COMPLY WITH
 MECHANICAL SCREENING.
 2. PLEASE INDICATE IN WHICH ELEVATION IS THE GALVANIZED
 DUCT PROPOSED. DUCT WILL NOT BE ALLOWED ON THE STREET
 FRONTAGES.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-03-01 Cont ID  
Sent By AA Date 2018-03-01 Time 11:40 Rev Time 0.00
Received By aaponte Date 2018-02-13 Time 11:34 Sent To  
Notes
2018-03-01 11:47:181. REPEAT COMMENT: PARAPET WALL SHALL BE RAISED TO BE
 THE SAME HEIGHT OF PROPOSED EQUIPMENT TO COMPLY WITH
 MECHANICAL SCREENING.
 2. PLEASE INDICATE IN WHICH ELEVATION IS THE GALVANIZED
 DUCT PROPOSED. WHAT IS THE PROPOSED SCREENING FOR SUCH
 MECHANICAL EQUIPMENT?
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By KM Date 2017-12-04 Time   Rev Time 0.00
Received By kmartin Date 2017-12-04 Time 14:13 Sent To I
Notes
2017-12-04 14:15:48PARAPET SHALL BE RAISED TO MATCH THE MECHANICAL
 EQUIPMENT.
  
 FOR MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN
 -URBAN DESIGN PLANNER AT [email protected].