Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-02-05 Cont ID  
Sent By cpuell Date 2018-02-05 Time 12:39 Rev Time 0.00
Received By cpuell Date 2018-02-05 Time 12:39 Sent To  
Notes
2018-02-05 12:40:10PASSED UNDER 17110370

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By thunt Date 2017-11-27 Time 14:51 Rev Time 0.00
Received By thunt Date 2017-11-27 Time 14:51 Sent To  
Notes
2017-11-27 15:01:0511-27-2017 1ST GAS REVIEW**DENIED**
  
 1) YOUR GAS RISER / ISOMETRIC CONFLICTS WITH CITY
 RECORDS. YOUR TOTAL P.E IS LISTED AS 40" BUT CITY
 RECORDS SHOWS 125' . ALSO CITY RECORDS SHOW THE FURTURE
 GENERATOR SIZE AS 500,000BTU BUT YOUR PROPOSING A
 750,000 BTU GENERATOR. PROVIDE A COMPLETE RISER/
 ISOMETRIC ON THE COMPLETE GAS SYSTEM.FGC SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3
  
 2) PROVIDE CORRECT FUEL TABLE OF SCH 40 METALLIC PIPING
 FOR .5LB. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695