Plan Review Details - Permit 17110363
Plan Review Stops For Permit 17110363
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-12-15 Cont ID  
Sent By lcrespo Date 2017-12-15 Time 16:06 Rev Time 0.00
Received By lcrespo Date 2017-12-15 Time 16:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-12-07 Cont ID  
Sent By tklarge Date 2017-12-07 Time 05:58 Rev Time 0.00
Received By tklarge Date 2017-12-07 Time 05:07 Sent To I
Notes
2017-12-07 05:14:271.) NOTE ON THE PLANS THE TYPE AND SIZE OF THE PIPE ON
 THE OUTLET OF THE GAS METER. PIPE SHALL BE SIZED FOR
 THE TOTAL BTU LOAD OF THE SYSTEM INCLUDING FUTURE
 APPLIANCES. FBC-FUEL GAS SEC.402.2.
 2) SHOW THE SIZE AND TYPE OF PIPE DOWNSTREAM OF EACH
 PRESSURE REGULATOR AT EACH APPLIANCE.
 3) SHOW THE DISTANCE FROM EACH PRESSURE REGULATOR TO
 THE APPLIANCE. IF ALL ARE LESS THAN 10 FEET INDICATE SO
 ON THE PLANS.
 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.YOU HAVE SUBMITTED
 A COPY OF THE TABLE FOR THE PE BUT WHAT ABOUT THE LOW
 PRESSURE SYSTEM? THE TYPE OF PIPING BEING USED FOR THE
 LOW PRESSURE SYSTEM IS NOT EVEN NOTED ON THE PLANS SO A
 COMPLETE REVIEW COULD NOT BE DONE. 2ND REQUEST.
 5) SIZE THE PE BRANCHES TO THE BBQ AND THE FUTURE
 STOVE.
 6) REGULATORS INSTALLED OUTDOORS SHALL BE APPROVED FOR
 EXTERIOR USE. FBC-FUEL GAS SEC.410.1. MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS SHALL BE
 ONSITE FOR FINAL INSPECTION. FBC FUEL GAS SEC.410.1,
 305.1.
 7) FUTURE OUTLETS FOR APPLIANCES SHALL BE EQUIPEED WITH
 A LISTED SHUTOFF VALVE, A LINE PRESSURE REGULATOR AND A
 PLUG OR NIPPLE AND CAP.
 NOTE** THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES
 / EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION.
 FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By tklarge Date 2017-11-14 Time 04:25 Rev Time 0.00
Received By tklarge Date 2017-11-14 Time 04:15 Sent To  
Notes
2017-11-14 04:25:471.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 2.) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 3) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES ( WHERE APPLICABLE). WHERE COMBUSTION AIR IS
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. FGC SEC.304.9.3 OR FBCR G2407.9.3.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-15 Cont ID  
Sent By lcrespo Date 2017-12-15 Time 16:06 Rev Time 0.00
Received By lcrespo Date 2017-12-07 Time 18:19 Sent To  
Notes
2017-12-07 18:19:26TKLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-07 Cont ID  
Sent By tklarge Date 2017-12-07 Time 05:58 Rev Time 0.00
Received By tklarge Date 2017-12-05 Time 11:25 Sent To I
Notes
2017-12-06 11:25:30RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By tklarge Date 2017-11-14 Time 04:26 Rev Time 0.00
Received By tklarge Date 2017-11-08 Time 09:27 Sent To  
Notes
2017-11-13 09:28:11PLUMB <5K