Plan Review Details - Permit 17110362
Plan Review Stops For Permit 17110362
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tklarge Date 2017-12-06 Time 02:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By tklarge Date 2017-11-14 Time 04:45 Rev Time 0.00
Received By tklarge Date 2017-11-14 Time 04:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-07 Cont ID  
Sent By tklarge Date 2017-12-07 Time 11:31 Rev Time 0.00
Received By tklarge Date 2017-12-07 Time 11:31 Sent To  
Notes
2017-12-06 02:58:01APPROVED BY PLUMBING. SENT TO UTILITIES FOR REVIEW.TKL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By tklarge Date 2017-11-14 Time 04:44 Rev Time 0.00
Received By tklarge Date 2017-11-14 Time 04:33 Sent To  
Notes
2017-11-14 04:41:151) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE
 SUBMITTED DOCUMENTS DO NOT SHOW THIS DEVICE IS LEAD
 FREE. THE 975 XL2 IS LEAD FREE BUT NOT THIS DEVICE.
 2014 FBC-PLUMBING SEC.605.2.1 AND CITY OF WEST PALM
 BEACH MANUAL FOR CROSS CONNECTION CONTROL.
 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 CITY OF WEST PALM BEACH MANUAL FOR CROSS CONNECTION
 CONTROL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  