Plan Review Details - Permit 17110340
Plan Review Stops For Permit 17110340
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-20 Cont ID  
Sent By aclange Date 2017-11-20 Time 16:32 Rev Time 0.00
Received By aclange Date 2017-11-20 Time 15:53 Sent To E
Notes
2017-11-20 16:32:06****PLAN REVIEW COMMENTS****
  
 ART LANGE ? BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2. IN THE GENERAL NOTES, UPDATE THE CODE SECTIONS TO
 THE CURRENT ADOPTED CODE CYCLES.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 10:16 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 10:16 Sent To FIRE
Notes
2017-11-21 10:16:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROPOSED WORK IS NOT WITHIN THE SCOPE OF WORK
 PERMITTED FOR THE LICENSE TYPE OF CONTRACTOR. PROVIDE
 ELECTRICAL CONTRACTOR THAT HAS THE PROPER LICENSING FOR
 THIS TYPE OF WORK. FBC 105.1; FS 489.105(3), 489.505
 2. ADDRESS LISTED ON PLAN DOES NOT MATCH THE ADDRESS
 STATED ON PERMIT APPLICATION. PROVIDE CORRECT ADDRESS
 ON PLANS. FBC 107.2.1
 3. GENERAL NOTES ON SHEET PS-1 STATES THAT THE
 ELECTRICAL CODE FOR THIS PROJECT IS THE 2012 NATIONAL
 ELECTRICAL CODE, WHICH DOES NOT EXIST. PROVIDE CORRECT
 CODE REFERENCES. 2014 FBC PREFACE
 4. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-21 Cont ID  
Sent By pleduc Date 2017-11-21 Time   Rev Time 0.00
Received By pleduc Date 2017-11-21 Time 11:03 Sent To I
Notes
2017-11-21 12:11:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROVIDE THE TESTING RESULTS IN DOCUMENT FORM THAT IS
 COMPLIANT WITH APPLICABLE INDUSTRY STANDARDS FOR REVIEW
 OF FIRE INSPECTION.
  
  
 2) THE SYSTEM SHALL BE TESTED WITH FIRE DEPARTMENT
 PORTABLE RADIOS OF FIRE INSPECTION VERIFICATION.
  
  
 3) ADDRESS ALL COMMENTS BY OTHER CITY DEPARTMENTS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-21 Cont ID  
Sent By lmarchan Date 2017-11-21 Time 15:10 Rev Time 0.00
Received By lmarchan Date 2017-11-08 Time 14:46 Sent To  
Notes
2017-11-20 13:10:20TO MISC 2 BOX.
2017-11-09 14:46:20ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2017-11-20 Cont ID  
Sent By AA Date 2017-11-20 Time 13:07 Rev Time 0.00
Received By aaponte Date 2017-11-14 Time 10:53 Sent To  
Notes
2017-11-20 13:09:46A WIRELESS COMMUNICATION FACILITY APPROVAL SHALL BE
 OBTAINED BEFORE A BUILDING PERMIT CAN BE APPROVED.
 PLEASE SUBMIT A WCF APPLICATION TO THE PLANNING
 DEPARTMENT FOR REVIEW AND APPROVAL. THE APPLICATION CAN
 BE FOUND IN THE CITY'S WEBSITE.
 FOR ADDITIONAL INFORMAITON PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.