Plan Review Details - Permit 17110339
Plan Review Stops For Permit 17110339
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-29 Cont ID  
Sent By jwitmer Date 2018-01-29 Time 11:54 Rev Time 0.00
Received By jwitmer Date 2018-01-29 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-18 Cont ID  
Sent By jwitmer Date 2017-11-18 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2017-11-18 Time 07:15 Sent To  
Notes
2017-11-18 08:11:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110339
 ADD: 4600 N. FLAGLER DR.
 CONT: MICHAEL ENNIS CONSTRUCTION CO.
 TEL: 772-486-2373
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 18/ 2017
 ACTION: DENIED
  
 1) IT WOULD APPEAR THE CONTRACTOR NEEDS TO TAKE
 OWNERSHIP OF THE PLANS, SINCE THE CONSTRUCTION COMPANY
 NAME APPEARS IN THE TITLE BLOCK.
 CERTIFICATION BY CONTRACTOR. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR.
  
 2) SHEET # 1 THE COVERSHEET INDICATES THE CLOSING IN OF
 A WINDOW ON A WOOD FRAME STRUCTURE, THE PLANS INDICATE
 2 X 6 STUDS TO BE INSTALLED AT 16 INCHES ON CENTER BUT
 THE PLANS DOES NOT INDICATE HOW THE STUDS WILL BE
 ANCHORED (STRAPPED) TO THE FRAMING MEMBERS AROUND THE
 EXISTING WINDOW TO BECOME PART OF THE
 MAIN WIND FORCE RESISTING SYSTEM (MWFRS)? THE WIND
 SPEED AT THE JOBSITE LOCATION IS 170 VULT MPH, 3SECOND
 GUST & EXPOSURE D.
  
 2014 FBC-B 2308.2.1 ULTIMATE DESIGN WIND SPEED GREATER
 THAN 115 MPH (3-SECOND GUST).
 WHERE THE ULTIMATE DESIGN WIND SPEED, VULT EXCEEDS 115
 MPH (3-SECOND GUST), THE PROVISIONS OF EITHER AF&PA
 WFCM OR ICC 600 ARE PERMITTED TO BE USED. WIND SPEEDS
 IN FIGURES 1609A, 1609B, AND 1609C SHALL BE CONVERTED
 IN ACCORDANCE WITH SECTION 1609.3.1 FOR USE WITH ICC
 600.
  
 3) SHEET # 1 THE COVERSHEET INDICATES THE CLOSING IN OF
 A WINDOW ON A WOOD FRAME STRUCTURE, THE PLANS INDICATE
 WIRE LATH AND STUCCO TO BE INSTALLED WHERE THE INFILL
 OF THE WINDOW WILL OCCUR.
 PLEASE SHOW COMPLIANCE WITH 2 LAYERS OF WATER RESISTANT
 BARRIERS INSTALLED INDEPENDENTLY. SEE 2014 FBC-B 2510.6
 WATER-RESISTANT BARRRIERS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-14 Cont ID  
Sent By jpearson Date 2018-03-14 Time 15:20 Rev Time 0.00
Received By jpearson Date 2018-03-14 Time 15:20 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-02-07 Cont ID  
Sent By jpearson Date 2018-02-07 Time 15:10 Rev Time 0.00
Received By jpearson Date 2018-02-07 Time 15:10 Sent To I
Notes
2018-02-07 15:10:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. NEW COMMENTS
 ARE ADDED BELOW PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 (NOT
 PROVIDED.)
 3. ALL KITCHEN RECEPTACLE OUTLETS ARE REQUIRED TO BE
 GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8 (ONE
 OUTLET STILL IS SHOWN WITH NO GFCI PROTECTION.)
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED.)
 5. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 (NOT
 PROVIDED.)
  
 NEW COMMENTS:
  
 6. PROVIDE LOCATION OF PANEL FOR KITCHEN. FBC 107.2.1
 7. CONDUIT FROM EXTERIOR DISCONNECT TO INTERIOR PANEL
 IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTION. NEC 250.122
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By jpearson Date 2017-11-29 Time 09:15 Rev Time 0.00
Received By jpearson Date 2017-11-29 Time 07:57 Sent To I
Notes
2017-11-29 09:15:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN NEEDS TO BE PREPARED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 3. ALL KITCHEN RECEPTACLE OUTLETS ARE REQUIRED TO BE
 GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2
 5. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-26 Cont ID  
Sent By pleduc Date 2018-01-26 Time   Rev Time 0.00
Received By pleduc Date 2018-01-25 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By pleduc Date 2017-11-14 Time   Rev Time 0.00
Received By pleduc Date 2017-11-13 Time 15:28 Sent To  
Notes
2017-11-14 12:51:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PLEASE ENSURE THAT THE LOCKS AND LATCHES ON BOTH
 EXIT DDORS COMPLY WITH NFPA 101, CHAPTER 7 MEANS OF
 EGRESS.
  
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN
 THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING
 OPERATION, UNLESS OTHERWISE SPECIFIED IN 7.2.1.5.10.3,
 7.2.1.5.10.4, OR 7.2.1.5.10.6.
  
 7.2.1.5.12* DEVICES SHALL NOT BE INSTALLED IN
 CONNECTION WITH ANY DOOR ASSEMBLY ON WHICH PANIC
 HARDWARE OR FIRE EXIT HARDWARE IS REQUIRED WHERE SUCH
 DEVICES PREVENT OR ARE INTENDED TO PREVENT THE FREE USE
 OF THE LEAF FOR PURPOSES OF EGRESS, UNLESS OTHERWISE
 PROVIDED IN 7.2.1.6.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 16:11 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 16:11 Sent To  
Notes
2017-11-28 16:12:33GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-03-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-12 Time 13:36 Sent To  
Notes
2018-03-13 13:37:04RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-23 Time 11:06 Sent To  
Notes
2018-01-24 11:06:28B24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-29 Cont ID  
Sent By jpearson Date 2017-11-29 Time 09:16 Rev Time 0.00
Received By jpearson Date 2017-11-08 Time 12:50 Sent To  
Notes
2017-11-09 12:50:51B24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-11-18 Cont ID  
Sent By jwitmer Date 2017-11-18 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2017-11-18 Time 07:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-02-02 Cont ID  
Sent By ccole Date 2018-02-02 Time 12:11 Rev Time 0.00
Received By ccole Date 2018-02-02 Time 11:44 Sent To  
Notes
2018-02-02 12:13:25SEPARATE PERMITS FOR GAS AND GAS APPLIANCES, KITCHEN
 HOOD AND FIRE SUPPRESSION SYSTEM.
 COMBUSTION AIR CALCULATIONS REQUIRED ON GAS PLAN.
  
 CCOLE-2/2/18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-18 Cont ID  
Sent By ccole Date 2017-11-18 Time 09:08 Rev Time 0.00
Received By ccole Date 2017-11-18 Time 09:08 Sent To  
Notes
2017-11-18 09:12:221ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110339
 11/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE MECHANICAL ALTERATIONS RELATED TO THE
 DEMOLITION AND RECONFIGURATION OF THE NEW KITCHEN.
  
 2) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC. COMPLIANCE WITH
 SECTION 508.1.1 MAKEUP AIR TEMPERATURE WILL BE
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By gjohnson Date 2018-02-07 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 16:13 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 15:14 Sent To  
Notes
2017-11-28 16:11:481ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GREASE INTERCEPTOR SPECIFICATIONS AND SANITARY
 RISER ARE TO SMALL PLEASE ENLARGE ON PLAN SHEET. PER
 WPB AMEND TO FBC 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  
 2. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR
 GREASE INTERCEPTOR. PER FBC PL 1003.2
  
 3. THE RISER DIAGRAM DOES NOT MATCH FLOOR PLAN THE HAND
 SINK IS NOT SHOWN ON FLOOR PLAN AND THE 3" VENT IS NOT
 SHOWN ON RISER. PER WPB AMEND TO FBC 107.2.1
  
 4. A TRAP PRIMER IS REQUIRED ON FLOOR DRAINS. PER FBC
 PL 1002.4
  
 5. PLEASE PROVIDE WATER RISER DIAGRAM. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 6. SHOW LOCATION OF WATER HEATER ON PLAN SHALL COMPLY
 WITH FBC PL 607.2 HOT OR TEMPERED WATER SUPPLY TO
 FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 7. A CLEANOUT IS REQUIRED ON INLET SIDE OF GREASE
 INTERCEPTOR AND A TESTPORT/ CLEAN OUT MIN 4" REQUIRED
 ON OUTLET SIDE. PER WPB UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2018-02-07 Cont ID  
Sent By gjohnson Date 2018-02-07 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 14:01 Sent To  
Notes
***NONE***