Plan Review Details - Permit 17110294
Plan Review Stops For Permit 17110294
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-30 Cont ID  
Sent By shill Date 2017-11-30 Time 11:50 Rev Time 0.00
Received By shill Date 2017-11-30 Time 09:07 Sent To  
Notes
2017-11-30 09:10:13PROVISO:
  
 INSTALLATION OF GENERATOR IS IN CONFLICT WITH THE
 PERMIT DOCUMENTS. REVISE SLAB DETAIL TO SHOW ELEVATION
 OF 7.5' AND PROVIDE TO INSPECTOR AT INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By shill Date 2017-11-07 Time 15:55 Rev Time 0.00
Received By shill Date 2017-11-07 Time 15:55 Sent To I
Notes
2017-11-07 15:55:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ELEVATION CERTIFICATE FOR HOUSE:
  
 1. A7, OUR RECORDS SHOW THAT THIS SHOULD BE BUILDING
 TYPE 1B (STEM WALL); ALSO NOTE THAT ADJACENT GRADE IS
 LOWER THAN FINISHED FLOOR.
  
 2. COMMENTS SECTION ON PAGE 2 STATES "CABANA FLOOR
 ELEVATION = 7.6 AT REAR OF RESIDENCE"; PLEASE CHANGE
 LANGUE TO BE CONSISTENT WITH THE PLAN (COVERED TERRACE)
 OR REMOVE.
  
 FEMA'S NEW POLICY IS THAT ALL ELEVATION CERTIFICATES
 FOR ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENT
 ARE SENT TO A CENTRAL OUT OF STATE LOCATION AND AUDITED
 RANDOMLY. THE LANGUAGE "CABANA" APPEARS TO IMPLY AN
 ENCLOSED PORTION OF THE BUILDING. PLANS SHOW THIS AS
 HAVING TWO WALLS. IF YOU WISH TO DISCUSS, PLEASE CALL
 ME.
  
 ADDITIONAL PICTURES ARE REQUIRED BUT CAN BE PROVIDED BY
 THE PROPERTY OWNER.
 A SIGNED AND SEALED ORIGINAL ELEVATION CERTIFICATE IS
 REQUIRED.
  
 ********************
 ELEVATION CERTIFICATE FOR THE ACCESSORY STRUCTURE:
  
 1. PLEASE CONFIRM THAT THE ACCESSORY STRUCTURE IS THE
 GYM. IF NOT, PLEASE ADVISE.
  
 2. SEE SHEET A001 OF THE PLAN, ALL MECHANICAL EQUIPMENT
 TO BE AT 7.5' OR ABOVE. ELEVATION CERTIFICATE SHOWS THE
 AC UNIT AT 6.67, PLEASE ADDRESS.
  
 THE ISSUED PERMIT DID NOT SHOW EQUIPMENT AT THE
 LOCATION NOTED ON ELEVATION CERTIFICATE (AIR
 CONDITIONER ON SOUTH SIDE OF GYM). IS THIS INCLUDED IN
 A REVISION? PLEASE PROVIDE THE REVISION NUMBER. IF NOT
 INCLUDED IN A REVISION, PLEASE SUBMIT REVISION AT THIS
 TIME.
  
 3. SEE ELEVATION CERTIFICATE INSTRUCTIONS, "IF ANY ITEM
 DOES NOT APPLY TO THE BUILDING, ENTER "N/A" FOR NOT
 APPLICABLE." PLEASE ADD NA TO C2B THROUGH C2D.
  
 ADDITIONAL PICTURES ARE REQUIRED BUT CAN BE PROVIDED BY
 THE PROPERTY OWNER.
 A SIGNED AND SEALED ORIGINAL ELEVATION CERTIFICATE IS
 REQUIRED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-30 Cont ID  
Sent By shill Date 2017-11-30 Time 12:00 Rev Time 0.00
Received By shill Date 2017-11-28 Time 13:21 Sent To  
Notes
2017-11-29 13:21:34RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-07 Cont ID  
Sent By shill Date 2017-11-07 Time 15:56 Rev Time 0.00
Received By shill Date 2017-11-07 Time 15:56 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2017-11-30 Cont ID  
Sent By shill Date 2017-11-30 Time 11:13 Rev Time 0.00
Received By shill Date 2017-11-30 Time 11:13 Sent To  
Notes
2017-11-30 11:13:40MINIMUM DFE = 7.5'
 HOUSE IS AT 8', GARAGE AND EQUIPMENT AT 7.5'
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By shill Date 2017-11-07 Time 15:56 Rev Time 0.00
Received By shill Date 2017-11-07 Time 15:56 Sent To  
Notes
2017-11-07 15:56:48SEE BUILDING REVIEW
  