 |
Plan Review Details - Permit 17110283
| Plan Review Stops For Permit 17110283 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-11-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-11-21 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-11-21 |
Time |
06:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-15 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-14 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2018-05-14 19:27:35 | SECOND BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | | | | ARCHITECTS-ENGINEERS | | | FLORIDA STATUTE 553.80(2)(B): | | | ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW | | | | | | 1) SHEET 100-A0.0 HEADING GOVERNING CODES: | | | | | | 1A) ORIGINAL COMMENT: | | | BUILDING CONSTRUCTION TYPE IS LISTED AS III-B | | | SPRINKLERED. PLEASE NOTE THIS IS A 13 STORY HIGH RISE | | | BUILDING. THE BUILDING CONSTRUCTION TYPE WOULD BE TYPE | | | I-A. 2014 FBC-B TABLE 503. | | | | | | RESPONSE: | | | SEMI-COMPLIED. CONSTRUCTION TYPE WAS REVISED TO I-A BUT | | | IS MISSING THE SPRINKLER INFORMATION. THIS BUILDING IS | | | REQUIRED TO BE SPRINKLERED. REVISE AS REQUIRED. | | | | | | 2) COMPLIED. | | | | | | 3A) COMPLIED. | | | | | | 3B) COMPLIED. | | | | | | 4) ORIGINAL COMMENT: | | | PLEASE NOTE ON SHEETS 110-A1.0 & 130-A1.2 THE LIFE | | | SAFETY PLAN, BOTH PLANS SHOW ONLY ONE ACCESSIBLE SPACE | | | AT A TABLE. PLEASE REFER TO THE 2014 FBC-ACCESSIBILITY | | | CODE SECTION 226.1. WHERE DINING SURFACES ARE PROVIDED | | | FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 | | | PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. 50X 0.05%= | | | 2.5 REQUIRED TO ROUND UP TO 3 SEATS. | | | | | | RESPONSE: | | | REPEAT COMMENT. PLANS LAYOUT AND NUMBER OF PEOPLE WAS | | | REVISED. NOW 72 SEATS ARE SHOWN. NOW NEEDS AT LEAST 4 | | | SEATS. | | | | | | 5) ORIGINAL COMMENT: | | | PLEASE SHOW THE ACCESSIBLE SEATS DISPERSED THROUGHOUT | | | ALL CATEGORIES OF SEATING INCLUDING THE BAR AREA. 2014 | | | FBC-ACCESS. CODE SECTION 226.2 DISPERSION. DINING | | | SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902 | | | SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY | | | CONTAINING DINING SURFACES AND WORK SURFACES. | | | | | | RESPONSE: | | | REPEAT COMMENT. NEED TO DISPERSE SEATS THROUGHOUT ALL | | | SEATING CATEGORIES, INCLUDING THE BOOTHS. | | | | | | 6) SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE | | | SECTION 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2 | | | AND 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES | | | INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH | | | COUNTERS, AND BOOTHS. | | | | | | ORIGINAL COMMENT: | | | 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | RESPONSE: | | | REPEAT COMMENT. SHOW THE CLEAR FLOOR OR GROUND SPACE ON | | | FLOOR PLAN FOR ALL DISPERSED ACCESSIBLE SEATS. | | | | | | ORIGINAL COMMENT: | | | 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | RESPONSE: | | | SEMI-COMPLIED. TABLE, BOOTH AND BAR DETAILS WERE | | | PROVIDE ON SHEET 110-A1.0. NEED TO SHOW ACCESSIBLE | | | BOOTH LOCATION ON FLOOR PLAN. | | | | | | 7A) ORIGINAL COMMENT: | | | SHEET 110-A1.0 IN THE UPPER LEFT HAND CORNER OF THE | | | SHEET THERE IS A DOOR SCHEDULE AND DOOR D1 IN THE NOTES | | | INDICATES SEE FLOOR PLAN A1.0. NEITHER DOOR IS | | | IDENTIFIED ON THIS SHEET. D1 IS LABELED A 2 FOOT 10 | | | INCH DOOR. SEE SIZE OF DOORS IN THE 2014 FBC-B | | | 1008.1.1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL | | | BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL | | | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR | | | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE | | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, | | | WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). | | | | | | RESPONSE: | | | SEMI-COMPLIED. THE WIND LOADS SPECIFIED FOR DOOR D3 | | | SEEM TO BE LOW. THIS BUILDING IS LOCATED IN EXPOSURE | | | "D". REVISE AS REQUIRED OR PROVIDE ENGINEERED | | | CALCULATIONS. SEC. 1609.4 FBC. | | | | | | 7B) COMPLIED. DOOR D14 WAS DELETED. | | | | | | 8) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | ARCHITECTS-ENGINEERS | | | FLORIDA STATUTE 553.80(2)(B): | | | ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW | | | | | | | | | NEW COMMENTS: | | | 10-LIFE SAFETY PLAN SHEET 130-A1.2: | | | A) PLAN NEED TO SHOW THE REQUIRED ASSEMBLY AISLES AND | | | DIMENSIONS (NON FIXED TABLES AREA AND BOOTHS AREA). SEE | | | SEC. 1028.9 FBC. CROSSING THRU TABLES AND CHAIRS IS NOT | | | ALLOWED FOR THE EGRESS PATH. (COORDINATE WITH SEATING | | | AND TABLES SEC. 1028.10.1 FOR PROPER ARRANGEMENT OF OF | | | DINING AREA AND REQUIRED AISLES). | | | NOTE: ALSO CONSIDER THE MANEUVERING CLEARANCES REQUIRED | | | AT THE EGRESS DOOR. | | | | | | B) EXIT TRAVEL DISTANCE IS MEASURED FROM THE MOST | | | REMOTE POINT OF THE ROOM ALONG THE NATURAL AND | | | UNOBSTRUCTED PATH TO THE EXIT. SEC. 1016.3 FBC. REVISE | | | TRAVEL DISTANCE FROM KITCHEN STORAGE ROOM, FREEZER | | | REACH-IN AREA, PIZZA PREP AND BAR AREA. ALSO, REVISE | | | OVERALL DISTANCES. COORDINATE WITH ITEM #10A) ABOVE. | | | | | | C) NUMBER OF PEOPLE SHOWN ON THE 6'-0" LONG BOOTHS IS | | | INCORRECT. REVISE AS REQUIRED. SEC. 1004.4 FBC. | | | | | | D) REVISED OCCUPANT LOAD ON SHEET 100-A0.0 SPECIFIES 73 | | | SEATS. LIFE SAFETY PLAN SHOWS 72. REVISE AS REQUIRED TO | | | MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | E) SCOPE OF WORK ON SHEET 100-A0.0 SPECIFIES BUILT OUT | | | TO INCLUDE PAIR OF ENTRY DOORS. DOOR SCHEDULE ON SHEET | | | 110-A1.0 DOESN'T PROVIDE SPECIFICATIONS FOR THE ENTRY | | | DOORS. PROVIDE COMPLETE INFORMATION. ALSO, SPECIFY THE | | | PANIC HARDWARE. SEC. 1008.1 FBC. | | | NOTE: STOREFRONT PERMIT #18020691 ONLY SHOWS ONE ENTRY | | | DOOR. | | | | | | F) SECOND EXIT DOOR BY THE PARKING GARAGE SIDE IS USING | | | THE RAMP AS PART OF A MEANS OF EGRESS. THIS RAMP SHALL | | | COMPLY WITH SEC. 1010 FBC. PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS SHOWING HOW THE RAMP COMPLIES WITH THIS | | | SECTION. SHOW COMPLIANCE WITH ALL REQUIREMENTS | | | INCLUDING SLOPE, CROSS SLOPE, VERTICAL RISE, LANDINGS, | | | , HANDRAILS, ETC. | | | | | | | | | 11- BASED ON THE LAYOUT OF NON FIXED TABLES AND CHAIRS | | | IT LOOKS LIKE THERE IS NOT AN ACCESSIBLE ROUTE TO THE | | | RESTROOMS . SEC. 202.4 FBC-ACCESSIBILITY. REVISE AS | | | REQUIRED TO PROVIDE THE ACCESSIBLE ROUTE. COORDINATE | | | WITH ITEM #10A) ABOVE. | | | | | | 12-VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | REVISE AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS. | | | | | | SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 13- CODE CLASSIFICATIONS TABLE ON SHEET 100-A0.0: | | | A) THE KITCHEN AREA NUMBER OF OCCUPANTS IS BASED ON THE | | | GROSS AREA NOT NET AREA. REVISE AS REQUIRED BY TABLE | | | 1004.1.2 FBC. | | | NOTE: CLARIFY NUMBER OF EMPLOYEES. ONLY 5 EMPLOYEES FOR | | | ENTIRE ASSEMBLY? | | | | | | B) PROVIDE SEPARATE OCCUPANT LOAD FOR THE FIXED SEATS | | | (BOOTHS, BAR STOOLS) AND FOR NON FIXED SEATS AS | | | REQUIRED BY SEC. 1004.4 FBC. | | | | | | C) CLEARLY SPECIFY THE MAXIMUM OCCUPANT LOAD. SEC. | | | 1004.3 FBC. | | | | | | D) REVISE THE EXIT WIDTH INFORMATION ON THE CODE | | | CLASSIFICATION TABLE. SEE SEC. 1008.1.1 AND SEC. 1005.3 | | | FBC. THE INCHES PROVIDED IS INCORRECT. SEE NUMBER AND | | | SIZE OF DOORS PROVIDED AND REVISE AS REQUIRED. SEE SEC. | | | 1008.1.1 FOR CORRECT WAY TO DETERMINE THE DOOR CLEAR | | | OPENING. | | | | | | E) LEFT HAND SIDE COLUMN OF THE CODE CLASSIFICATION | | | TABLE IS CALLING FOR BUSINESS OCCUPANCY. THIS IS | | | ASSEMBLY A-2. REVISE AS REQUIRED. SEC. 303.3 FBC. | | | | | | 14- CLARIFY WHAT IS THE HATCHED PARTITION SHOWN IN ALL | | | PLANS BY THE ACCESSIBLE RESTROOM. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 15- SHEET 110-A1.0: | | | A) PROVIDE COMPLETE FRAMING DETAIL AND SPECIFICATIONS | | | FOR THE NEW SINGLE FIRE RATED EXIT DOOR ON THE EXISTING | | | FIRE RATED WALL. SEC. 701.1 FB AND SEC. 1609.1 FBC. | | | | | | B) RESTROOM GRAB BARS NEED TO BE MEASURED TO THE TOP OF | | | THE GRIPPING SURFACE NOT THE CENTER LINE. REVISE AS | | | REQUIRED. SEC. 609.4 FBC ACCESSIBILITY. | | | | | | C) PROVIDE DETAILS AND SPECIFICATIONS FOR THE SERVICE | | | COUNTER BY THE PIZZA PREP AREA SHOWING COMPLIANCE WITH | | | SEC. 227.3 FBC ACCESSIBILITY. | | | | | | 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL) | | | A) NEW FIRE RATED EXIT DOOR. | | | | | | B) NEW DOUBLE ENTRY DOORS. (NOTE: COORDINATE WITH | | | STOREFRONT PERMIT) | | | | | | 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN | | | WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS | | | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-11-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-11-18 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-11-17 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2017-11-18 07:14:05 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17110283 | | | ADD: 777 S. FLAGLER DR. SUITE 132 WEST | | | CONT: CONSTRUCTION SOLUTIONS | | | TEL: 561-337-7793 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SAT. NOV. 18/ 2017 | | | ACTION: DENIED | | | | | | 1) SHEET 100-A0.0 HEADING GOVERNING CODES: | | | | | | 1A) BUILDING CONSTRUCTION TYPE IS LISTED AS III-B | | | SPRINKLERED. PLEASE NOTE THIS IS A 13 STORY HIGH RISE | | | BUILDING. THE BUILDING CONSTRUCTION TYPE WOULD BE TYPE | | | I-A. 2014 FBC-B TABLE 503. | | | | | | 2) SHEET 130-A1.2 THE LIFE SAFETY PLAN DOES NOT SHOW | | | THE SWING OF THE MAIN ENTRY DOORS. THE COVERSHEET LIST | | | OVER 50 OCCUPANTS THE DOORS SHOULD SWING OUT PER | | | SECTION 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA | | | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS. | | | | | | 3A) THE COVERSHEET SHOWS AN OCCUPANT LOAD OF 61 | | | OCCUPANTS AND THE LIFE SAFETY PLAN SHEET 130-A1.2 SHOWS | | | 3 EXITS FROM THE TENANT SPACE, THE ONLY ISSUE IS 2 OF | | | THE 3 EXITS ARE IN KITCHEN / DISH ROOM AREAS LEAVING | | | ONLY ONE EXIT FOR THE GENERAL PUBLIC TO EXIT BY. WITH | | | AN OCCUPANT LOAD GREATER THAN 49 THEN 2 EXITS FOR THAT | | | SPACE ARE REQUIRED. SEE 2014 FBC-B TABLE 1015.1. | | | | | | 3B) WITH A FIRE SPRINKLERED BUILDING THE 2 REQUIRED | | | EXITS OR EXIT ACCESS DOORWAYS WOULD NEED TO BE A | | | SEPARATION DISTANCE OF THE EXIT DOORS OR EXIT ACCESS | | | DOORWAYS SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH | | | OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA | | | SERVED. | | | | | | 4) PLEASE NOTE ON SHEETS 110-A1.0 & 130-A1.2 THE LIFE | | | SAFETY PLAN, BOTH PLANS SHOW ONLY ONE ACCESSIBLE SPACE | | | AT A TABLE. PLEASE REFER TO THE 2014 FBC-ACCESSIBILITY | | | CODE SECTION 226.1. WHERE DINING SURFACES ARE PROVIDED | | | FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 | | | PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. 50X 0.05%= | | | 2.5 REQUIRED TO ROUND UP TO 3 SEATS. | | | | | | 5) PLEASE SHOW THE ACCESSIBLE SEATS DISPERSED | | | THROUGHOUT ALL CATEGORIES OF SEATING INCLUDING THE BAR | | | AREA. 2014 FBC-ACCESS. CODE SECTION 226.2 DISPERSION. | | | DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY | | | WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR | | | FACILITY CONTAINING DINING SURFACES AND WORK SURFACES. | | | | | | 6) SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE | | | SECTION 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2 | | | AND 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES | | | INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH | | | COUNTERS, AND BOOTHS. | | | | | | 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 7A) SHEET 110-A1.0 IN THE UPPER LEFT HAND CORNER OF THE | | | SHEET THERE IS A DOOR SCHEDULE AND DOOR D1 IN THE NOTES | | | INDICATES SEE FLOOR PLAN A1.0. NEITHER DOOR IS | | | IDENTIFIED ON THIS SHEET. D1 IS LABELED A 2 FOOT 10 | | | INCH DOOR. SEE SIZE OF DOORS IN THE 2014 FBC-B | | | 1008.1.1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL | | | BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL | | | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR | | | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE | | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, | | | WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). | | | | | | 7B) UNKNOWN LOCATION FOR DOOR D14, SIZE 1 FOOT 91/2 | | | INCHES WIDE? 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 8) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-11-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-08 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-08 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-05-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-05 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-05 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2018-05-05 08:17:20 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD | | | CALCULATION IS NOT ACCURATE FOR PANEL KX. FEEDERS MUST | | | BE SIZED TO HANDLE 125% OF THE CONTINUOUS LOAD AND 100% | | | OF THE NON-CONTINUOUS LOAD. FACTORS IMPORTED FROM PANEL | | | KA AND KB DO NOT INCLUDE THOSE DEMAND FACTORS.SHOW | | | WINDOW LIGHTING IS NOT INCLUDED.) | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62. | | | (PER THIS CODE, AT LEAST ONE RECEPTACLE OUTLET SHALL BE | | | INSTALLED FOR EVERY 12 FEET OR MAJOR FRACTION THEREOF. | | | THESE RECEPTACLES ALSO REQUIRE AUTOMATIC CONTROL PER | | | ENERGY CODE AND THEY ARE CURRENTLY SHOWN TIED TO | | | REGULAR RECEPTACLE CIRCUIT. PROVIDE CORRECTION.) | | | 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS | | | REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 | | | (NOT PROVIDED.) | | | 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR | | | RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION | | | 10.4.1, FBC 107.2.1 (NOT PROVIDED) | | | 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | | CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS | | | ADEQUATE. NEC 110.10 (NOT PROVIDED) | | | 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN | | | REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 | | | (NOT PROVIDED) | | | 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE | | | LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT | | | INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A | | | BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND | | | DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE | | | SYSTEMS PRESENT. FBC 105.1, 107.2.1(NOT PROVIDED) | | | | | | NEW COMMENT: | | | | | | 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE | | | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD | | | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN | | | A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN | | | REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH | | | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-11-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-27 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-27 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2017-11-27 15:18:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 | | | 2. PROVIDE AUTOMATIC LIGHTING CONTROL FOR EXTERIOR | | | LIGHTING AND SIGN CIRCUIT. ENERGY CODE STATES: LIGHTING | | | NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE | | | 405.2.4 | | | 3. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) | | | 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER | | | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE | | | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH | | | CODE. FBC CE 405.5 | | | 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62. | | | 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS | | | REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 | | | 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR | | | RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION | | | 10.4.1, FBC 107.2.1 | | | 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | | CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS | | | ADEQUATE. NEC 110.10 | | | 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN | | | REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 | | | 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE | | | LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT | | | INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A | | | BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND | | | DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE | | | SYSTEMS PRESENT. FBC 105.1, 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2018-11-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-08 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-08 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-10-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-10-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-10-16 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-04-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-04-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-04-25 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2018-04-25 15:00:23 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ALL KITCHEN HOOD SYSTEMS SHALL BE PER NFPA 96 AND | | | SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS. | | | | | | | | | 2) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS WORK SHALL | | | BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-11-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-09 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2017-11-09 17:02:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE IS NO NOTE INDICATING COMPLAINCE WITH ANY LIFE | | | SAFETY CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | | | | | | | | | | 2) SHEET 130 A 1.2 - THERE IN NO INDICATION OF ANY | | | EXISTING OR PROPOSED BUILDING INFORMATION. I.E. TYPE OF | | | CONSTRUCTION, FIRE SPRINKLER, FIRE ALARM, INTEIOR | | | FINISHES, ETC. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 3) SHEET 110 A 1.0 - THE DOOR SCHEDULE DOES NOT | | | INDICATE ANY INFORMATION REGARDING EXISITNG DOORS AND | | | HARDWARE.. | | | | | | PLEASE PROVIDE DOOR DETAILS, INCLUDING, TYPE, SIZE, | | | LOCKS, LATCHES, HARDWARE, ETC. THAT MEET THE | | | REQUIRMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. | | | | | | | | | | | | 4) SHEET 130 A 1.2 - A KITCHEN IS INDICATED. THERE IS | | | NO INFORMATION REGARDING COMPLIANCE WITH NFPA 96, | | | STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF | | | COMMERCIAL COOKING OPERATIONS, 2011 EDITION, EITHER | | | EXISITNG OR PROPOSED. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANT EXISITNG | | | OR PROPOSED SHOP DRAWINGS UNDER SEPARATE PERMIT. | | | | | | | | | | | | 5) SHEET 120 A 1.1 - A PIZZA OVEN IS INDICATED. THERE | | | ARE NO SPECIFICATION SHEETS OF PROPTECTION PER NFPA 96 | | | OR INSTALLTION & VENTILATION REQUIRERMENTS. | | | | | | PLEASE PROVIDE MANUFACTURES DETAIL SHEETS INCLUDING | | | INSTALLATION INSTRUCTIONS. | | | | | | | | | | | | 6) SHEET 130 A 1.2 - THERE IS ONLY ONE EXIT FROM THE | | | MAIN AREA AND TWO ARE REQUIRED. THE EXIT FROM THE MAIN | | | AREA CAN NOT PASS THRU THE KITCHEN AREA. | | | | | | PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES, | | | | | | 12.2 MEANS OF EGRESS REQUIREMENTS. | | | 12.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN | | | ACCORDANCE WITH CHAPTER 7 AND THIS CHAPTER. | | | | | | 12.2.4* NUMBER OF MEANS OF EGRESS. | | | 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN | | | ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR | | | FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH | | | 12.2.4.4. | | | | | | 7.4* NUMBER OF MEANS OF EGRESS. | | | 7.4.1 GENERAL. | | | 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY, | | | MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS | | | THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS: | | | (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE | | | PERMITTED IN CHAPTERS 11 THROUGH 43. | | | (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A | | | MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL | | | LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET. | | | | | | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND | | | 7.2.1.5. | | | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH | | | KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS | | | 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR | | | SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO | | | LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS | | | PERMITTED FOR THE OCCUPANCY BY CHAPTER | | | 18, 19, 22, OR 23. | | | | | | PLEASE CORRECT OR PROVIDE FFPC REFERENCE FOR THE | | | EXCEPTION. | | | | | | | | | | | | 7) SHEE 120 A 1.1 - THERE ARE NO INDICATIONS OF FIRE | | | SPRINKLER OR FIRE ALARM WORK. ALL WORK ON ANY EXISTING | | | FIRE SPRINKLER OR FIRE ALARM SYSTEM SHALL BE DONE UNDER | | | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | | CONTRACTORS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. | | | | | | | | | | | | 8) SHEET 100 A 0.0 - THERE IS INDICATIONS OF OCCUPANCY | | | LOADS CALCULATION. THERE IS NO INDICATIONS OF THE | | | OCCUPANCY LOAD FOR THE BAR COUNTER AREA. | | | | | | PLEASE PROVIDE | | | | | | | | | | | | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2019-01-22 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-01-22 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-01-22 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2019-01-22 11:55:05 | APPROVED | | | PROVISO | | | RE: MANUFACTURER'S SPCIFICATION SHEETS FOR KITCHEN GAS | | | EQUIPMENT; PER WPB FBC 107.3.4.1 MAY BE PROVIDED AS | | | DEFERRED SUBMITTALS. SUBMITTALS SHALL BE SUBMITTED, | | | APPROVED AND IN PLACE PRIUOR TO FINAL INSPECTION. | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-11-27 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-11-27 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2018-11-27 12:42:43 | 3RD REVIEW: DENIED | | | GAS COMMENTS | | | REVIEWED PLAN SHEETS FG1.1, FG1.2 AND FG2.1 | | | | | | AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING | | | COMMENTS APPLY. | | | | | | 1. THIRD REQUEST; SUBMIT MANUFACTURER'S SPECIFICATION | | | SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. | | | 402.2 | | | 2. THIRD REQUEST; SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR PER THE FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | NEW COMMENT | | | | | | 1. RE: PLAN SHEET FG1.1; CONCERNING THE EMERGENCY GAS | | | SHUTOFF VALVE, VALVE SHALL SHUT OFF AUTOMATICALLY IN | | | ACCORDANCE WITH NFPA 96, SECTION 10.4.1. | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-04 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-04 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2018-05-04 11:32:27 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | | | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. PROVIDE THE LONGEST RUN FROM THE METER TO THE | | | FURTHEST APPLIANCE. PER THE FBC-2014 FUEL GAS APPENDIX | | | A ? USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS | | | CODE SEC. 402.4.1 | | | | | | 4. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP | | | WITH 100' BASED ON THAT THE MANIFOLD SHALL BE 11/2" PER | | | TABLE 402.4.2 SHOWN ON THE PLAN. | | | | | | 5. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP | | | WITH 100' BASED ON THAT THE THE BRANCH FOR THE TANKLESS | | | HEATER K5, K4 SHALL BE 11/4 PER TABLE 402.4.2 SHOWN ON | | | THE PLAN. | | | | | | 6. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP | | | WITH 100' BASED ON THAT THE THE MANIFOLD K5, K4 SHALL | | | BE 11/4 PER TABLE 402.4.2 SHOWN ON THE PLAN. | | | | | | 7. PROVIDE SIZE AND LENGTH OF VENT PIPING FOR TANKLESS | | | HEATER. PER FBC-2014 FUEL GAS CODE SEC. 502 THRU 505. | | | SHALL COMPLY WITH MANUFACTURE SPECIFICATIONS. | | | | | | 8. PROVIDE ELEVATION DRAWING SHOWING THE TERMINATION OF | | | THE VENT FOR TANLESS WATER HEATER SHOW DISTANCE TO ANY | | | OPENINGS IN THE BUILDING AND THE GROUND. PER FBC-2014 | | | FUEL GAS CODE SEC. 502 THRU 505. SHALL COMPLY WITH | | | MANUFACTURE SPECIFICATIONS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-29 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-29 |
Time |
07:27 |
Sent To |
|
|
| Notes |
| 2017-11-29 07:49:49 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | GAS COMMENTS: | | | | | | (1). SHT. 200-P2.0 GAS SUPPLY DIAGRAM KEYNOTES | | | A) # 109 DIRT LEGS SHALL BE LOCATED UPSTREAM OF | | | APPLIANCES WHERE THE PIPING GOES FROM VERTICAL TO | | | HORIZONTAL. PER FBC FG 408.4 | | | B) # 111 ALL BRANCHES INCLUDING FUTURE SHALL BE LABELED | | | WITH SIZE, TYPE OF PIPE, LENGTH AND BTU LOAD. PER FBC | | | FG 402 | | | C) #112 THE COMPLETE SYSTEM SHALL BE LABELED WITH SIZE | | | OF PIP, TYPE OF PIPE, LENGTH OF EACH SECTION AND BTU | | | LOAD BEFORE IT CAN BE APPROVED. IF A COMPLETED SYSTEM | | | CAN NOT BE COMPLETED PLEASE REMOVE FROM PLAN AND SUBMIT | | | UNDER THE SEPARATE GAS PERMIT AND PLANS OTHERWISE IT | | | MIGHT HOLD UP APPROVAL OF THE MASTER PERMIT. | | | | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND | | | INSTALLATION GUIDES FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 10. PLEASE SUBMIT SIZING TABLES FROM FBC FG CODE USED | | | TO SIZE SYSTEM. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-01-24 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-01-24 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-01-17 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2019-01-22 14:51:51 | ON CMONTELL DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-11-27 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-11-27 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2018-10-22 15:04:43 | B24 | | 2018-10-15 15:55:45 | LIBRARY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-16 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-20 |
Time |
14:38 |
Sent To |
I |
|
| Notes |
| 2018-06-19 11:18:17 | APPROVED BY ZONING, SENT TO LMARCHAN | | 2018-06-04 18:01:09 | CHANGE OF OCCUPANCY - NEEDS ZONING REVIEW | | | SENT TO ZONING BOX ON 6/4 | | | | | 2018-04-23 14:38:56 | B28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-29 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-07 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2018-11-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-11-21 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-11-21 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2018-11-21 10:37:42 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-05-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-11 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-11 |
Time |
18:37 |
Sent To |
|
|
| Notes |
| 2018-05-11 18:37:51 | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-16 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-16 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2017-11-18 07:12:57 | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2019-01-24 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-01-24 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-01-24 |
Time |
13:46 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-11-08 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-11-08 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-11-08 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2018-11-08 11:19:36 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODE | | | PERMIT #17110283 | | | 11/8/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | | | | 1 - PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL | | | GAS. | | | | | | 2 - PROVIDE CUT SHEETS FOR COOKING APPLIANCES | | | | | | 3 - BE ADVISED 2014 FLORIDA MECHANICAL CODE 508.1.1 | | | MAKEUP AIR TEMPERATURE. | | | | | | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE | | | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F | | | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS | | | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE | | | HVAC SYSTEM. | | | | | | | | | | | | CHRIS MONTELLO | | | 561-805-6733 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-02 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-02 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2018-05-02 12:13:51 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODE | | | PERMIT #17110283 | | | 5/2/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ENERGYGAUGE FORM: A) PROVIDE COMPLIANCE DATA FOR THE | | | AC HEATING SYSTEMS SPECIFED AS 10 KW ON THE PLANS.. B) | | | CORRECT THE COMPLIANCE DATA FOR SYSTEM 3 SPECIFYING THE | | | COOLING SYSTEM AT 57 BTUH. | | | | | | 2) M-1: SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE | | | DETECTORS IN THE RETURN SYSTEMS OF THE AIR HANDLERS- | | | SECTION 606.2.1. | | | | | | 3) M-1: PROVIDE AN AIR BALANCE CALCULATION THAT TAKES | | | INTO ACCOUNT THE KITCHEN HOOD EXHAUST AND MAKEUP AIR | | | CFMS, AND THE TOILET ROOM EXHAUST CFMS (NOTE- NO MAKEUP | | | AIR SYSTEMS SHOWN FOR THE HOODS). PLEASE NOTE TWO HOODS | | | ARE SHOWN ON THE PLAN- ONE RECIRCULATING AND ANOTHER | | | THAT APPEARS TO BE A CONVENTIONAL HOOD. BOTH THESE | | | HOODS ARE UNDER SEPARATE PERMIT HOWEVER | | | | | | PLEASE NOTE THAT THE RECIRCULATION HOOD SHALL BE UL | | | 710B LISTED AND LABELED. CONCERNING THE SECOND HOOD, | | | THE PLAN DOES NOT SHOW THE LOCATION OF THE HOOD EXHAUST | | | WHICH NEEDS TO BE CLARIFIED. | | | | | | 4) M-1: SHOW THE O/A DUCT RUNS AN AIR INLET LOCATIONS- | | | SECTION 401.4. INDICATE HOW THE OPENINGS WILL BE | | | PROTECTED PER SECTION 401.5. | | | | | | 5) M-1: REFER TO SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION AND PROVIDE AUTOMATICALLY CONTROLLED | | | SHUTOFF DAMPERS FOR THE O/A INTAKE DUCTS. | | | | | | 6) M-1: PROVIDE TOILET EXHAUST FAN SCHEDULES, AND SHOW | | | THE EXHAUST DUCT RUNS AND DISCHARGE LOCATIONS- SECTION | | | 501.3. | | | | | | 7) M-1: PROVIDE AN AIR DEVICE SCHEDULE. | | | | | | 8) M-1: SHOW THE LOCATION OF THE CONDENSERS AND THE | | | REFRIGERANT PIPING RUNS. PLEASE INCLUDE THE TYPES AND | | | SIZES OF REFRIGERANT PIPINGS, PIPING INSULATION, AND | | | TOTAL RUN LENGTHS OF THE PIPING | | | | | | 9) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL | | | GAS. | | | | | | 9) SUBMIT THE NOA FOR THE AC STANDS WITH APPROVAL STAMP | | | BY THE EOR. | | | | | | 10) PLACE A CLEAR NOTE ON THE PLAN THAT INDICATES THE | | | KITCHEN HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN | | | COOLER WILL BE UNDER SEPARATE PERMIT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-17 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-17 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2017-11-17 15:35:45 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110283 | | | 11/17/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. | | | PLEASE NOTE THAT SEPARATE PLANS AND PERMITS ARE | | | REQUIRED FOR THE KITCHEN HOOD EXHAUST SYSTEMS, THE FIRE | | | SUPPRESSION SYSTEMS, AND THE WALK-IN COOLER. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-01-22 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-01-22 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-01-22 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2019-01-22 11:47:44 | APPROVED | | | PLUMBING PROVISO | | | 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL | | | EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER | | | CHECK VALVE PER FBC PL 607.3. SEE RED LINED COMMENTS ON | | | DETAIL 5 OF PLAN PAGE P5.1 FOR CLARIFICATION. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-11-27 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-11-27 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2018-11-27 14:11:42 | 3RD REVIEW: DENIED | | | PLUMBING COMMENTS | | | REVIEWED PLAN SHEETS PO.1, P1.1, P1.2, P2.1, P3.1, | | | P4.1, P5.1, P5.2 & P6.1 | | | | | | AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING | | | COMMENTS APPLY. | | | | | | 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL | | | EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER | | | CHECK VALVE PER FBC PL 607.3. | | | 2. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1 SHOWS 140 | | | DEGREE HOT WATER TO FIXTURES. EWH SCHEDULE ON PLAN PAGE | | | P6.1 CALLS FOR TEMPERATURE TO BE SET AT 110 DEGREES. | | | PLEASE CLARIFY. | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-02 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2018-05-04 09:32:41 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PREVIOUS COMMENT #12 NOT COMPLIED COMPLETELY THE | | | GREASE PIPING IS SHOWN AS CPVC WHICH-IS NOT AN APPROVED | | | MATERIAL FOR USE AS UNDERGROUND SANITARY LINES PIPING | | | SHALL COMPLY WITH 1 OF THE MATERIALS FOUND IN | | | FBC PL TABLE 702.2 AND 702.3 | | | | | | 2. PREVIOUS COMMENT #17 NOT COMPLIED PROVIDE PIPING | | | DETAIL FOR GREASE INTERCEPTOR SHOWING CLEANOUTS AND | | | TEST PORT. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE MANUFACTURE SPEC FOR THE GREASE INTERCEPTOR DOES | | | NOT MEET THE WPB REQUIREMENTS FOR GREASE INTERCEPTORS | | | PLEASE SEE CITY OF WEST PALM BEACH PUBLIC WORKS DEPT. | | | STANDARD DETAIL G-7 IT CAN BY FOUND ONLINE. | | | | | | 4. ON THE GREASE ISOMETRIC A VENT IS REQUIRED BETWEEN | | | THE MOP SINK AND THE FLOOR DRAIN UPSTREAM OF IT. PER | | | FBC PL 901.2.1 | | | | | | 5. A SOLIDS SEPARATOR SHALL BE REQUIRED FOR THE | | | DISPOSAL SINK. PER FBC PL 1003.3.2 FOOD WASTE GRINDERS. | | | WHERE FOOD WASTE GRINDERS CONNECT TO GREASE | | | INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE | | | DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR. | | | SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE | | | SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE | | | GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA | | | SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER. | | | | | | 6. ON THE SANITARY ISOMETRIC THE TOILET AND FLOOR DRAIN | | | IN THE MENS BATHROOM SHALL BE VENTED WITH THE LAVATORY | | | BEFORE IT CONNECTS WITH THE BUILDING DRAIN. PER FBC PL | | | 912.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-29 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-11-28 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2017-11-29 09:08:11 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. ACCESSIBILITY PLEASE SHOW COMPLIANCE WITH THE | | | FOLLOWING: FBC ACC | | | | | | 609.4 POSITION OF GRAB BARS. | | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE | | | FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING | | | SURFACE.VERTICAL GRAB BARS ARE NOT APPROVED. | | | | | | 604.5.1 SIDE WALL. | | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, | | | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND | | | EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. | | | | | | 604.5.2 REAR WALL. | | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM | | | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 | | | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE | | | OTHER SIDE. | | | | | | 604.2 LOCATION. | | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION, | | | | | | 606.3 HEIGHT. | | | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT | | | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THIS IS | | | UNCLEAR ON THE PLAN | | | | | | 2. SHT. 110-A1.0 ON THE FLOOR PLAN IT APPEARS THE CLEAR | | | FLOOR SPACE FOR THE WATER CLOSET IN WOMENS BATHROOM IS | | | ENCROACHING OVER INTO THE KITCHEN WHERE THE 3 COMP SINK | | | IS LOCATED PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. PLEASE LABEL THE CLEAR FLOOR SPACE IN BATHROOMS. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 4. SHT 120-A1.1 ON THE ENLARGED KITCHEN PLAN THE ICE | | | CUBER B4 IS NOT LABELED PLEASE CLARIFY. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 5. SHT. 120-A1.1 K10 IS THE HOT FOOD TABLE ELECTRIC OR | | | GAS IT DOES NOT INDICATE ON THE EQUIPMENT SCHEDULE | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 6. SHT. 120-A1.1 K21 IS NOT LISTED ON THE EQUIPMENT | | | SCHEDULE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 7. SHT. 190-P1.0 ON THE WATER ISOMETRIC THE AIR | | | CHAMBERS ARE NOT APPROVED THEY SHALL COMPLY WITH FBC PL | | | 604.9 WATER HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. | | | | | | 8. SHT. 190-P1.0 ON THE WATER ISOMETRIC IT SHOWS THE | | | TANKLESS WATER HEATER ABOVE THE MOP AND HAND SINK ON | | | THE FLOOR PLAN IT SHOWS ABOVE THE 3 COMP SINK PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 9. SHT. 190-P1.0 ON THE WATER ISOMETRIC PLEASE SHOW | | | SIZE OF ALL DROPS. PER WPB AMEND TO FBC 107.2.1 | | | | | | 10. SHT. 190-P1.0 ON THE WATER ISOMETRIC VALVES ARE | | | REQUIRED AT EACH DROP AND THE MAIN FEED COMING INTO THE | | | BUILDING .PER FBC PL 606.1 LOCATION OF FULL-OPEN | | | VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: 2. ON THE WATER DISTRIBUTION SUPPLY PIPE AT | | | THE ENTRANCE INTO THE STRUCTURE. 5. ON THE TOP OF EVERY | | | WATER DOWN-FEED PIPE IN OCCUPANCIES OTHER THAN ONE- AND | | | TWO-FAMILY RESIDENTIAL OCCUPANCIES. | | | | | | 11. SHT. 190-P1.0 ON THE WATER ISOMETRIC A BACK FLOW IS | | | REQUIRED ON THE SUPPLY FOR ICE MACHINES, BEVERAGE | | | DISPENSERS AND WATER FILTERS. PER FBC PL 608.3, | | | 608.16.1 AND 608.16.10 | | | | | | 12. SHT. 190-P1.0 THE NOTE UNDER PLUMBING GENERAL NOTES | | | STATES THE GREASE WASTE PIPE SHALL BE CPVC BUT THE | | | ISOMETRIC SHOWS THE BRANCH PIPING AS PVC PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 13. THE 3 COMP SINK SHALL BE INDIRECTLY WASTED TO FLOOR | | | SINK. PER FBC PL 802.1.1 | | | | | | 14. THE BRANCH DRAIN FOR THE DRINKING FOUNTAIN SHALL | | | CONNECT TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM | | | GROUPS. PER FBC PL 912.1 | | | | | | 15. THE GLASS WASHER IN BAR AREA, THE FLOOR DRAINS IN | | | THE BATHROOMS AND DRAINS FROM THE ICE MACHINES SHALL | | | NOT DISCHARGE INTO THE GREASY WASTE SYSTEM. PER FBC PL | | | 1003.2 | | | | | | 16. PLEASE PROVIDE SPECIFICATIONS FOR THE GREASE | | | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 | | | | | | 17. PLEASE PROVIDE A PIPING DETAIL FOR GREASE | | | INTERCEPTOR SHOWING TWO WAY CLEANOUTS ON INLET AND | | | OUTLET ALSO TEST PORT ON OUTLET. PER WPB UTILITIES DEPT | | | | | | 18. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTOR. PER FBC PL 1003.2 | | | | | | 19. SHT. 210-P2.1 DETAIL A1 SHOWS A 2" WATER MAIN | | | BREAKING DOWN TO 11/2" THE WATER ISOMETRIC ON SHT-P1.0 | | | ONLY SHOWS A 3/4" MAIN PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 20. IF A WATER FILTER SYSTEM IS BEING USED PLEASE SHOW | | | ON WATER ISOMETRIC AND PROVIDE A PIPING DETAIL. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-06-19 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2018-06-19 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2018-06-19 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |