Plan Review Details - Permit 17110283
Plan Review Stops For Permit 17110283
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-21 Cont ID  
Sent By jwitmer Date 2018-11-21 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2018-11-21 Time 06:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-16 Cont ID  
Sent By jgomez Date 2018-05-15 Time 08:47 Rev Time 0.00
Received By jgomez Date 2018-05-14 Time 08:35 Sent To  
Notes
2018-05-14 19:27:35SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 1) SHEET 100-A0.0 HEADING GOVERNING CODES:
  
 1A) ORIGINAL COMMENT:
 BUILDING CONSTRUCTION TYPE IS LISTED AS III-B
 SPRINKLERED. PLEASE NOTE THIS IS A 13 STORY HIGH RISE
 BUILDING. THE BUILDING CONSTRUCTION TYPE WOULD BE TYPE
 I-A. 2014 FBC-B TABLE 503.
  
 RESPONSE:
 SEMI-COMPLIED. CONSTRUCTION TYPE WAS REVISED TO I-A BUT
 IS MISSING THE SPRINKLER INFORMATION. THIS BUILDING IS
 REQUIRED TO BE SPRINKLERED. REVISE AS REQUIRED.
  
 2) COMPLIED.
  
 3A) COMPLIED.
  
 3B) COMPLIED.
  
 4) ORIGINAL COMMENT:
 PLEASE NOTE ON SHEETS 110-A1.0 & 130-A1.2 THE LIFE
 SAFETY PLAN, BOTH PLANS SHOW ONLY ONE ACCESSIBLE SPACE
 AT A TABLE. PLEASE REFER TO THE 2014 FBC-ACCESSIBILITY
 CODE SECTION 226.1. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. 50X 0.05%=
 2.5 REQUIRED TO ROUND UP TO 3 SEATS.
  
 RESPONSE:
 REPEAT COMMENT. PLANS LAYOUT AND NUMBER OF PEOPLE WAS
 REVISED. NOW 72 SEATS ARE SHOWN. NOW NEEDS AT LEAST 4
 SEATS.
  
 5) ORIGINAL COMMENT:
 PLEASE SHOW THE ACCESSIBLE SEATS DISPERSED THROUGHOUT
 ALL CATEGORIES OF SEATING INCLUDING THE BAR AREA. 2014
 FBC-ACCESS. CODE SECTION 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 RESPONSE:
 REPEAT COMMENT. NEED TO DISPERSE SEATS THROUGHOUT ALL
 SEATING CATEGORIES, INCLUDING THE BOOTHS.
  
 6) SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE
 SECTION 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2
 AND 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES
 INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH
 COUNTERS, AND BOOTHS.
  
 ORIGINAL COMMENT:
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 RESPONSE:
 REPEAT COMMENT. SHOW THE CLEAR FLOOR OR GROUND SPACE ON
 FLOOR PLAN FOR ALL DISPERSED ACCESSIBLE SEATS.
  
 ORIGINAL COMMENT:
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 RESPONSE:
 SEMI-COMPLIED. TABLE, BOOTH AND BAR DETAILS WERE
 PROVIDE ON SHEET 110-A1.0. NEED TO SHOW ACCESSIBLE
 BOOTH LOCATION ON FLOOR PLAN.
  
 7A) ORIGINAL COMMENT:
 SHEET 110-A1.0 IN THE UPPER LEFT HAND CORNER OF THE
 SHEET THERE IS A DOOR SCHEDULE AND DOOR D1 IN THE NOTES
 INDICATES SEE FLOOR PLAN A1.0. NEITHER DOOR IS
 IDENTIFIED ON THIS SHEET. D1 IS LABELED A 2 FOOT 10
 INCH DOOR. SEE SIZE OF DOORS IN THE 2014 FBC-B
 1008.1.1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL
 BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES (1.57 RAD).
  
 RESPONSE:
 SEMI-COMPLIED. THE WIND LOADS SPECIFIED FOR DOOR D3
 SEEM TO BE LOW. THIS BUILDING IS LOCATED IN EXPOSURE
 "D". REVISE AS REQUIRED OR PROVIDE ENGINEERED
 CALCULATIONS. SEC. 1609.4 FBC.
  
 7B) COMPLIED. DOOR D14 WAS DELETED.
  
 8) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NEW COMMENTS:
 10-LIFE SAFETY PLAN SHEET 130-A1.2:
 A) PLAN NEED TO SHOW THE REQUIRED ASSEMBLY AISLES AND
 DIMENSIONS (NON FIXED TABLES AREA AND BOOTHS AREA). SEE
 SEC. 1028.9 FBC. CROSSING THRU TABLES AND CHAIRS IS NOT
 ALLOWED FOR THE EGRESS PATH. (COORDINATE WITH SEATING
 AND TABLES SEC. 1028.10.1 FOR PROPER ARRANGEMENT OF OF
 DINING AREA AND REQUIRED AISLES).
 NOTE: ALSO CONSIDER THE MANEUVERING CLEARANCES REQUIRED
 AT THE EGRESS DOOR.
  
 B) EXIT TRAVEL DISTANCE IS MEASURED FROM THE MOST
 REMOTE POINT OF THE ROOM ALONG THE NATURAL AND
 UNOBSTRUCTED PATH TO THE EXIT. SEC. 1016.3 FBC. REVISE
 TRAVEL DISTANCE FROM KITCHEN STORAGE ROOM, FREEZER
 REACH-IN AREA, PIZZA PREP AND BAR AREA. ALSO, REVISE
 OVERALL DISTANCES. COORDINATE WITH ITEM #10A) ABOVE.
  
 C) NUMBER OF PEOPLE SHOWN ON THE 6'-0" LONG BOOTHS IS
 INCORRECT. REVISE AS REQUIRED. SEC. 1004.4 FBC.
  
 D) REVISED OCCUPANT LOAD ON SHEET 100-A0.0 SPECIFIES 73
 SEATS. LIFE SAFETY PLAN SHOWS 72. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 E) SCOPE OF WORK ON SHEET 100-A0.0 SPECIFIES BUILT OUT
 TO INCLUDE PAIR OF ENTRY DOORS. DOOR SCHEDULE ON SHEET
 110-A1.0 DOESN'T PROVIDE SPECIFICATIONS FOR THE ENTRY
 DOORS. PROVIDE COMPLETE INFORMATION. ALSO, SPECIFY THE
 PANIC HARDWARE. SEC. 1008.1 FBC.
 NOTE: STOREFRONT PERMIT #18020691 ONLY SHOWS ONE ENTRY
 DOOR.
  
 F) SECOND EXIT DOOR BY THE PARKING GARAGE SIDE IS USING
 THE RAMP AS PART OF A MEANS OF EGRESS. THIS RAMP SHALL
 COMPLY WITH SEC. 1010 FBC. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE RAMP COMPLIES WITH THIS
 SECTION. SHOW COMPLIANCE WITH ALL REQUIREMENTS
 INCLUDING SLOPE, CROSS SLOPE, VERTICAL RISE, LANDINGS,
 , HANDRAILS, ETC.
  
  
 11- BASED ON THE LAYOUT OF NON FIXED TABLES AND CHAIRS
 IT LOOKS LIKE THERE IS NOT AN ACCESSIBLE ROUTE TO THE
 RESTROOMS . SEC. 202.4 FBC-ACCESSIBILITY. REVISE AS
 REQUIRED TO PROVIDE THE ACCESSIBLE ROUTE. COORDINATE
 WITH ITEM #10A) ABOVE.
  
 12-VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 REVISE AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 13- CODE CLASSIFICATIONS TABLE ON SHEET 100-A0.0:
 A) THE KITCHEN AREA NUMBER OF OCCUPANTS IS BASED ON THE
 GROSS AREA NOT NET AREA. REVISE AS REQUIRED BY TABLE
 1004.1.2 FBC.
 NOTE: CLARIFY NUMBER OF EMPLOYEES. ONLY 5 EMPLOYEES FOR
 ENTIRE ASSEMBLY?
  
 B) PROVIDE SEPARATE OCCUPANT LOAD FOR THE FIXED SEATS
 (BOOTHS, BAR STOOLS) AND FOR NON FIXED SEATS AS
 REQUIRED BY SEC. 1004.4 FBC.
  
 C) CLEARLY SPECIFY THE MAXIMUM OCCUPANT LOAD. SEC.
 1004.3 FBC.
  
 D) REVISE THE EXIT WIDTH INFORMATION ON THE CODE
 CLASSIFICATION TABLE. SEE SEC. 1008.1.1 AND SEC. 1005.3
 FBC. THE INCHES PROVIDED IS INCORRECT. SEE NUMBER AND
 SIZE OF DOORS PROVIDED AND REVISE AS REQUIRED. SEE SEC.
 1008.1.1 FOR CORRECT WAY TO DETERMINE THE DOOR CLEAR
 OPENING.
  
  E) LEFT HAND SIDE COLUMN OF THE CODE CLASSIFICATION
 TABLE IS CALLING FOR BUSINESS OCCUPANCY. THIS IS
 ASSEMBLY A-2. REVISE AS REQUIRED. SEC. 303.3 FBC.
  
 14- CLARIFY WHAT IS THE HATCHED PARTITION SHOWN IN ALL
 PLANS BY THE ACCESSIBLE RESTROOM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 15- SHEET 110-A1.0:
 A) PROVIDE COMPLETE FRAMING DETAIL AND SPECIFICATIONS
 FOR THE NEW SINGLE FIRE RATED EXIT DOOR ON THE EXISTING
 FIRE RATED WALL. SEC. 701.1 FB AND SEC. 1609.1 FBC.
  
 B) RESTROOM GRAB BARS NEED TO BE MEASURED TO THE TOP OF
 THE GRIPPING SURFACE NOT THE CENTER LINE. REVISE AS
 REQUIRED. SEC. 609.4 FBC ACCESSIBILITY.
  
  C) PROVIDE DETAILS AND SPECIFICATIONS FOR THE SERVICE
 COUNTER BY THE PIZZA PREP AREA SHOWING COMPLIANCE WITH
 SEC. 227.3 FBC ACCESSIBILITY.
  
 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) NEW FIRE RATED EXIT DOOR.
  
  B) NEW DOUBLE ENTRY DOORS. (NOTE: COORDINATE WITH
 STOREFRONT PERMIT)
  
  17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-18 Cont ID  
Sent By jwitmer Date 2017-11-18 Time 07:14 Rev Time 0.00
Received By jwitmer Date 2017-11-17 Time 16:56 Sent To  
Notes
2017-11-18 07:14:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110283
 ADD: 777 S. FLAGLER DR. SUITE 132 WEST
 CONT: CONSTRUCTION SOLUTIONS
 TEL: 561-337-7793
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 18/ 2017
 ACTION: DENIED
  
 1) SHEET 100-A0.0 HEADING GOVERNING CODES:
  
 1A) BUILDING CONSTRUCTION TYPE IS LISTED AS III-B
 SPRINKLERED. PLEASE NOTE THIS IS A 13 STORY HIGH RISE
 BUILDING. THE BUILDING CONSTRUCTION TYPE WOULD BE TYPE
 I-A. 2014 FBC-B TABLE 503.
  
 2) SHEET 130-A1.2 THE LIFE SAFETY PLAN DOES NOT SHOW
 THE SWING OF THE MAIN ENTRY DOORS. THE COVERSHEET LIST
 OVER 50 OCCUPANTS THE DOORS SHOULD SWING OUT PER
 SECTION 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 3A) THE COVERSHEET SHOWS AN OCCUPANT LOAD OF 61
 OCCUPANTS AND THE LIFE SAFETY PLAN SHEET 130-A1.2 SHOWS
 3 EXITS FROM THE TENANT SPACE, THE ONLY ISSUE IS 2 OF
 THE 3 EXITS ARE IN KITCHEN / DISH ROOM AREAS LEAVING
 ONLY ONE EXIT FOR THE GENERAL PUBLIC TO EXIT BY. WITH
 AN OCCUPANT LOAD GREATER THAN 49 THEN 2 EXITS FOR THAT
 SPACE ARE REQUIRED. SEE 2014 FBC-B TABLE 1015.1.
  
 3B) WITH A FIRE SPRINKLERED BUILDING THE 2 REQUIRED
 EXITS OR EXIT ACCESS DOORWAYS WOULD NEED TO BE A
 SEPARATION DISTANCE OF THE EXIT DOORS OR EXIT ACCESS
 DOORWAYS SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH
 OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA
 SERVED.
  
 4) PLEASE NOTE ON SHEETS 110-A1.0 & 130-A1.2 THE LIFE
 SAFETY PLAN, BOTH PLANS SHOW ONLY ONE ACCESSIBLE SPACE
 AT A TABLE. PLEASE REFER TO THE 2014 FBC-ACCESSIBILITY
 CODE SECTION 226.1. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. 50X 0.05%=
 2.5 REQUIRED TO ROUND UP TO 3 SEATS.
  
 5) PLEASE SHOW THE ACCESSIBLE SEATS DISPERSED
 THROUGHOUT ALL CATEGORIES OF SEATING INCLUDING THE BAR
 AREA. 2014 FBC-ACCESS. CODE SECTION 226.2 DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES AND WORK SURFACES.
  
 6) SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE
 SECTION 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2
 AND 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES
 INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH
 COUNTERS, AND BOOTHS.
  
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7A) SHEET 110-A1.0 IN THE UPPER LEFT HAND CORNER OF THE
 SHEET THERE IS A DOOR SCHEDULE AND DOOR D1 IN THE NOTES
 INDICATES SEE FLOOR PLAN A1.0. NEITHER DOOR IS
 IDENTIFIED ON THIS SHEET. D1 IS LABELED A 2 FOOT 10
 INCH DOOR. SEE SIZE OF DOORS IN THE 2014 FBC-B
 1008.1.1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL
 BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES (1.57 RAD).
  
 7B) UNKNOWN LOCATION FOR DOOR D14, SIZE 1 FOOT 91/2
 INCHES WIDE? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 8) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-11-08 Cont ID  
Sent By jpearson Date 2018-11-08 Time 08:50 Rev Time 0.00
Received By jpearson Date 2018-11-08 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 08:17 Rev Time 0.00
Received By jpearson Date 2018-05-05 Time 08:17 Sent To  
Notes
2018-05-05 08:17:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD
 CALCULATION IS NOT ACCURATE FOR PANEL KX. FEEDERS MUST
 BE SIZED TO HANDLE 125% OF THE CONTINUOUS LOAD AND 100%
 OF THE NON-CONTINUOUS LOAD. FACTORS IMPORTED FROM PANEL
 KA AND KB DO NOT INCLUDE THOSE DEMAND FACTORS.SHOW
 WINDOW LIGHTING IS NOT INCLUDED.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62.
 (PER THIS CODE, AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED FOR EVERY 12 FEET OR MAJOR FRACTION THEREOF.
 THESE RECEPTACLES ALSO REQUIRE AUTOMATIC CONTROL PER
 ENERGY CODE AND THEY ARE CURRENTLY SHOWN TIED TO
 REGULAR RECEPTACLE CIRCUIT. PROVIDE CORRECTION.)
 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 (NOT PROVIDED.)
 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR
 RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION
 10.4.1, FBC 107.2.1 (NOT PROVIDED)
 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10 (NOT PROVIDED)
 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN
 REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 (NOT PROVIDED)
 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE
 LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT
 INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A
 BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND
 DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE
 SYSTEMS PRESENT. FBC 105.1, 107.2.1(NOT PROVIDED)
  
 NEW COMMENT:
  
 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By jpearson Date 2017-11-27 Time 15:18 Rev Time 0.00
Received By jpearson Date 2017-11-27 Time 11:35 Sent To  
Notes
2017-11-27 15:18:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 2. PROVIDE AUTOMATIC LIGHTING CONTROL FOR EXTERIOR
 LIGHTING AND SIGN CIRCUIT. ENERGY CODE STATES: LIGHTING
 NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE
 405.2.4
 3. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62.
 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR
 RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION
 10.4.1, FBC 107.2.1
 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN
 REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE
 LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT
 INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A
 BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND
 DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE
 SYSTEMS PRESENT. FBC 105.1, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-11-08 Cont ID  
Sent By jpearson Date 2018-11-08 Time 08:51 Rev Time 0.00
Received By jpearson Date 2018-11-08 Time 08:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-16 Cont ID  
Sent By pleduc Date 2018-10-16 Time   Rev Time 0.00
Received By pleduc Date 2018-10-16 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-25 Cont ID  
Sent By pleduc Date 2018-04-25 Time   Rev Time 0.00
Received By pleduc Date 2018-04-25 Time 14:30 Sent To  
Notes
2018-04-25 15:00:23THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL KITCHEN HOOD SYSTEMS SHALL BE PER NFPA 96 AND
 SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
  
 2) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS WORK SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-13 Cont ID  
Sent By pleduc Date 2017-11-13 Time   Rev Time 0.00
Received By pleduc Date 2017-11-09 Time 12:35 Sent To  
Notes
2017-11-09 17:02:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE IS NO NOTE INDICATING COMPLAINCE WITH ANY LIFE
 SAFETY CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
 2) SHEET 130 A 1.2 - THERE IN NO INDICATION OF ANY
 EXISTING OR PROPOSED BUILDING INFORMATION. I.E. TYPE OF
 CONSTRUCTION, FIRE SPRINKLER, FIRE ALARM, INTEIOR
 FINISHES, ETC.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET 110 A 1.0 - THE DOOR SCHEDULE DOES NOT
 INDICATE ANY INFORMATION REGARDING EXISITNG DOORS AND
 HARDWARE..
  
 PLEASE PROVIDE DOOR DETAILS, INCLUDING, TYPE, SIZE,
 LOCKS, LATCHES, HARDWARE, ETC. THAT MEET THE
 REQUIRMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
  
  
 4) SHEET 130 A 1.2 - A KITCHEN IS INDICATED. THERE IS
 NO INFORMATION REGARDING COMPLIANCE WITH NFPA 96,
 STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, 2011 EDITION, EITHER
 EXISITNG OR PROPOSED.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANT EXISITNG
 OR PROPOSED SHOP DRAWINGS UNDER SEPARATE PERMIT.
  
  
  
 5) SHEET 120 A 1.1 - A PIZZA OVEN IS INDICATED. THERE
 ARE NO SPECIFICATION SHEETS OF PROPTECTION PER NFPA 96
 OR INSTALLTION & VENTILATION REQUIRERMENTS.
  
 PLEASE PROVIDE MANUFACTURES DETAIL SHEETS INCLUDING
 INSTALLATION INSTRUCTIONS.
  
  
  
 6) SHEET 130 A 1.2 - THERE IS ONLY ONE EXIT FROM THE
 MAIN AREA AND TWO ARE REQUIRED. THE EXIT FROM THE MAIN
 AREA CAN NOT PASS THRU THE KITCHEN AREA.
  
 PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES,
  
 12.2 MEANS OF EGRESS REQUIREMENTS.
 12.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH CHAPTER 7 AND THIS CHAPTER.
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR
 FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH
 12.2.4.4.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET.
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER
 18, 19, 22, OR 23.
  
 PLEASE CORRECT OR PROVIDE FFPC REFERENCE FOR THE
 EXCEPTION.
  
  
  
 7) SHEE 120 A 1.1 - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLER OR FIRE ALARM WORK. ALL WORK ON ANY EXISTING
 FIRE SPRINKLER OR FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 8) SHEET 100 A 0.0 - THERE IS INDICATIONS OF OCCUPANCY
 LOADS CALCULATION. THERE IS NO INDICATIONS OF THE
 OCCUPANCY LOAD FOR THE BAR COUNTER AREA.
  
 PLEASE PROVIDE
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-01-22 Cont ID  
Sent By jesmith Date 2019-01-22 Time 11:55 Rev Time 0.00
Received By jesmith Date 2019-01-22 Time 11:48 Sent To  
Notes
2019-01-22 11:55:05APPROVED
 PROVISO
 RE: MANUFACTURER'S SPCIFICATION SHEETS FOR KITCHEN GAS
 EQUIPMENT; PER WPB FBC 107.3.4.1 MAY BE PROVIDED AS
 DEFERRED SUBMITTALS. SUBMITTALS SHALL BE SUBMITTED,
 APPROVED AND IN PLACE PRIUOR TO FINAL INSPECTION.
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-11-27 Cont ID  
Sent By jesmith Date 2018-11-27 Time 13:54 Rev Time 0.00
Received By jesmith Date 2018-11-27 Time 12:41 Sent To  
Notes
2018-11-27 12:42:433RD REVIEW: DENIED
 GAS COMMENTS
 REVIEWED PLAN SHEETS FG1.1, FG1.2 AND FG2.1
  
 AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING
 COMMENTS APPLY.
  
 1. THIRD REQUEST; SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2
 2. THIRD REQUEST; SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 NEW COMMENT
  
 1. RE: PLAN SHEET FG1.1; CONCERNING THE EMERGENCY GAS
 SHUTOFF VALVE, VALVE SHALL SHUT OFF AUTOMATICALLY IN
 ACCORDANCE WITH NFPA 96, SECTION 10.4.1.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-04 Cont ID  
Sent By gjohnson Date 2018-05-04 Time 09:33 Rev Time 0.00
Received By gjohnson Date 2018-05-04 Time 09:33 Sent To  
Notes
2018-05-04 11:32:271ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. PROVIDE THE LONGEST RUN FROM THE METER TO THE
 FURTHEST APPLIANCE. PER THE FBC-2014 FUEL GAS APPENDIX
 A ? USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS
 CODE SEC. 402.4.1
  
 4. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP
 WITH 100' BASED ON THAT THE MANIFOLD SHALL BE 11/2" PER
 TABLE 402.4.2 SHOWN ON THE PLAN.
  
 5. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP
 WITH 100' BASED ON THAT THE THE BRANCH FOR THE TANKLESS
 HEATER K5, K4 SHALL BE 11/4 PER TABLE 402.4.2 SHOWN ON
 THE PLAN.
  
 6. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP
 WITH 100' BASED ON THAT THE THE MANIFOLD K5, K4 SHALL
 BE 11/4 PER TABLE 402.4.2 SHOWN ON THE PLAN.
  
 7. PROVIDE SIZE AND LENGTH OF VENT PIPING FOR TANKLESS
 HEATER. PER FBC-2014 FUEL GAS CODE SEC. 502 THRU 505.
 SHALL COMPLY WITH MANUFACTURE SPECIFICATIONS.
  
 8. PROVIDE ELEVATION DRAWING SHOWING THE TERMINATION OF
 THE VENT FOR TANLESS WATER HEATER SHOW DISTANCE TO ANY
 OPENINGS IN THE BUILDING AND THE GROUND. PER FBC-2014
 FUEL GAS CODE SEC. 502 THRU 505. SHALL COMPLY WITH
 MANUFACTURE SPECIFICATIONS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 07:27 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 07:27 Sent To  
Notes
2017-11-29 07:49:491ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 (1). SHT. 200-P2.0 GAS SUPPLY DIAGRAM KEYNOTES
 A) # 109 DIRT LEGS SHALL BE LOCATED UPSTREAM OF
 APPLIANCES WHERE THE PIPING GOES FROM VERTICAL TO
 HORIZONTAL. PER FBC FG 408.4
 B) # 111 ALL BRANCHES INCLUDING FUTURE SHALL BE LABELED
 WITH SIZE, TYPE OF PIPE, LENGTH AND BTU LOAD. PER FBC
 FG 402
 C) #112 THE COMPLETE SYSTEM SHALL BE LABELED WITH SIZE
 OF PIP, TYPE OF PIPE, LENGTH OF EACH SECTION AND BTU
 LOAD BEFORE IT CAN BE APPROVED. IF A COMPLETED SYSTEM
 CAN NOT BE COMPLETED PLEASE REMOVE FROM PLAN AND SUBMIT
 UNDER THE SEPARATE GAS PERMIT AND PLANS OTHERWISE IT
 MIGHT HOLD UP APPROVAL OF THE MASTER PERMIT.
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 402.2
  
 10. PLEASE SUBMIT SIZING TABLES FROM FBC FG CODE USED
 TO SIZE SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-24 Cont ID  
Sent By cpuell Date 2019-01-24 Time 14:34 Rev Time 0.00
Received By cpuell Date 2019-01-17 Time 16:23 Sent To  
Notes
2019-01-22 14:51:51ON CMONTELL DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-27 Cont ID  
Sent By jesmith Date 2018-11-27 Time 14:15 Rev Time 0.00
Received By jesmith Date 2018-11-27 Time 14:27 Sent To  
Notes
2018-10-22 15:04:43B24
2018-10-15 15:55:45LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-16 Cont ID  
Sent By jgomez Date 2018-05-16 Time 10:51 Rev Time 0.00
Received By jgomez Date 2018-04-20 Time 14:38 Sent To I
Notes
2018-06-19 11:18:17APPROVED BY ZONING, SENT TO LMARCHAN
2018-06-04 18:01:09CHANGE OF OCCUPANCY - NEEDS ZONING REVIEW
 SENT TO ZONING BOX ON 6/4
  
2018-04-23 14:38:56B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 09:08 Rev Time 0.00
Received By gjohnson Date 2017-11-07 Time 14:58 Sent To  
Notes
2017-11-08 14:59:06B23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-11-21 Cont ID  
Sent By jwitmer Date 2018-11-21 Time 07:21 Rev Time 0.00
Received By jwitmer Date 2018-11-21 Time 07:21 Sent To  
Notes
2018-11-21 10:37:42BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-05-11 Cont ID  
Sent By jgomez Date 2018-05-11 Time 18:37 Rev Time 0.00
Received By jgomez Date 2018-05-11 Time 18:37 Sent To  
Notes
2018-05-11 18:37:51IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-16 Cont ID  
Sent By jgomez Date 2018-05-16 Time 10:50 Rev Time 0.00
Received By jgomez Date 2018-05-16 Time 10:50 Sent To  
Notes
2017-11-18 07:12:57IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-01-24 Cont ID  
Sent By cmontell Date 2019-01-24 Time 13:50 Rev Time 0.00
Received By cmontell Date 2019-01-24 Time 13:46 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-11-08 Cont ID  
Sent By cmontell Date 2018-11-08 Time 11:19 Rev Time 0.00
Received By cmontell Date 2018-11-08 Time 09:16 Sent To  
Notes
2018-11-08 11:19:362ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #17110283
 11/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1 - PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 2 - PROVIDE CUT SHEETS FOR COOKING APPLIANCES
  
 3 - BE ADVISED 2014 FLORIDA MECHANICAL CODE 508.1.1
 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By ccole Date 2018-05-02 Time 11:22 Rev Time 0.00
Received By ccole Date 2018-05-02 Time 11:14 Sent To  
Notes
2018-05-02 12:13:511ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #17110283
 5/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGYGAUGE FORM: A) PROVIDE COMPLIANCE DATA FOR THE
 AC HEATING SYSTEMS SPECIFED AS 10 KW ON THE PLANS.. B)
 CORRECT THE COMPLIANCE DATA FOR SYSTEM 3 SPECIFYING THE
 COOLING SYSTEM AT 57 BTUH.
  
 2) M-1: SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE
 DETECTORS IN THE RETURN SYSTEMS OF THE AIR HANDLERS-
 SECTION 606.2.1.
  
 3) M-1: PROVIDE AN AIR BALANCE CALCULATION THAT TAKES
 INTO ACCOUNT THE KITCHEN HOOD EXHAUST AND MAKEUP AIR
 CFMS, AND THE TOILET ROOM EXHAUST CFMS (NOTE- NO MAKEUP
 AIR SYSTEMS SHOWN FOR THE HOODS). PLEASE NOTE TWO HOODS
 ARE SHOWN ON THE PLAN- ONE RECIRCULATING AND ANOTHER
 THAT APPEARS TO BE A CONVENTIONAL HOOD. BOTH THESE
 HOODS ARE UNDER SEPARATE PERMIT HOWEVER
  
 PLEASE NOTE THAT THE RECIRCULATION HOOD SHALL BE UL
 710B LISTED AND LABELED. CONCERNING THE SECOND HOOD,
 THE PLAN DOES NOT SHOW THE LOCATION OF THE HOOD EXHAUST
 WHICH NEEDS TO BE CLARIFIED.
  
 4) M-1: SHOW THE O/A DUCT RUNS AN AIR INLET LOCATIONS-
 SECTION 401.4. INDICATE HOW THE OPENINGS WILL BE
 PROTECTED PER SECTION 401.5.
  
 5) M-1: REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND PROVIDE AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPERS FOR THE O/A INTAKE DUCTS.
  
 6) M-1: PROVIDE TOILET EXHAUST FAN SCHEDULES, AND SHOW
 THE EXHAUST DUCT RUNS AND DISCHARGE LOCATIONS- SECTION
 501.3.
  
 7) M-1: PROVIDE AN AIR DEVICE SCHEDULE.
  
 8) M-1: SHOW THE LOCATION OF THE CONDENSERS AND THE
 REFRIGERANT PIPING RUNS. PLEASE INCLUDE THE TYPES AND
 SIZES OF REFRIGERANT PIPINGS, PIPING INSULATION, AND
 TOTAL RUN LENGTHS OF THE PIPING
  
 9) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 9) SUBMIT THE NOA FOR THE AC STANDS WITH APPROVAL STAMP
 BY THE EOR.
  
 10) PLACE A CLEAR NOTE ON THE PLAN THAT INDICATES THE
 KITCHEN HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN
 COOLER WILL BE UNDER SEPARATE PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By ccole Date 2017-11-17 Time 15:30 Rev Time 0.00
Received By ccole Date 2017-11-17 Time 15:30 Sent To  
Notes
2017-11-17 15:35:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110283
 11/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE NOTE THAT SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE KITCHEN HOOD EXHAUST SYSTEMS, THE FIRE
 SUPPRESSION SYSTEMS, AND THE WALK-IN COOLER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-01-22 Cont ID  
Sent By jesmith Date 2019-01-22 Time 11:47 Rev Time 0.00
Received By jesmith Date 2019-01-22 Time 11:46 Sent To  
Notes
2019-01-22 11:47:44APPROVED
 PLUMBING PROVISO
 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL
 EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER
 CHECK VALVE PER FBC PL 607.3. SEE RED LINED COMMENTS ON
 DETAIL 5 OF PLAN PAGE P5.1 FOR CLARIFICATION.
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-11-27 Cont ID  
Sent By jesmith Date 2018-11-27 Time 14:11 Rev Time 0.00
Received By jesmith Date 2018-11-27 Time 07:59 Sent To  
Notes
2018-11-27 14:11:423RD REVIEW: DENIED
 PLUMBING COMMENTS
 REVIEWED PLAN SHEETS PO.1, P1.1, P1.2, P2.1, P3.1,
 P4.1, P5.1, P5.2 & P6.1
  
 AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING
 COMMENTS APPLY.
  
 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL
 EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER
 CHECK VALVE PER FBC PL 607.3.
 2. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1 SHOWS 140
 DEGREE HOT WATER TO FIXTURES. EWH SCHEDULE ON PLAN PAGE
 P6.1 CALLS FOR TEMPERATURE TO BE SET AT 110 DEGREES.
 PLEASE CLARIFY.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 08:58 Sent To  
Notes
2018-05-04 09:32:412ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PREVIOUS COMMENT #12 NOT COMPLIED COMPLETELY THE
 GREASE PIPING IS SHOWN AS CPVC WHICH-IS NOT AN APPROVED
 MATERIAL FOR USE AS UNDERGROUND SANITARY LINES PIPING
 SHALL COMPLY WITH 1 OF THE MATERIALS FOUND IN
 FBC PL TABLE 702.2 AND 702.3
  
 2. PREVIOUS COMMENT #17 NOT COMPLIED PROVIDE PIPING
 DETAIL FOR GREASE INTERCEPTOR SHOWING CLEANOUTS AND
 TEST PORT. PER WPB AMEND TO FBC 107.2.1
  
 3. THE MANUFACTURE SPEC FOR THE GREASE INTERCEPTOR DOES
 NOT MEET THE WPB REQUIREMENTS FOR GREASE INTERCEPTORS
 PLEASE SEE CITY OF WEST PALM BEACH PUBLIC WORKS DEPT.
 STANDARD DETAIL G-7 IT CAN BY FOUND ONLINE.
  
 4. ON THE GREASE ISOMETRIC A VENT IS REQUIRED BETWEEN
 THE MOP SINK AND THE FLOOR DRAIN UPSTREAM OF IT. PER
 FBC PL 901.2.1
  
 5. A SOLIDS SEPARATOR SHALL BE REQUIRED FOR THE
 DISPOSAL SINK. PER FBC PL 1003.3.2 FOOD WASTE GRINDERS.
 WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER.
  
 6. ON THE SANITARY ISOMETRIC THE TOILET AND FLOOR DRAIN
 IN THE MENS BATHROOM SHALL BE VENTED WITH THE LAVATORY
 BEFORE IT CONNECTS WITH THE BUILDING DRAIN. PER FBC PL
 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 07:50 Rev Time 0.00
Received By jgomez Date 2017-11-28 Time 14:57 Sent To  
Notes
2017-11-29 09:08:111ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ACCESSIBILITY PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING: FBC ACC
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE.VERTICAL GRAB BARS ARE NOT APPROVED.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION,
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THIS IS
 UNCLEAR ON THE PLAN
  
 2. SHT. 110-A1.0 ON THE FLOOR PLAN IT APPEARS THE CLEAR
 FLOOR SPACE FOR THE WATER CLOSET IN WOMENS BATHROOM IS
 ENCROACHING OVER INTO THE KITCHEN WHERE THE 3 COMP SINK
 IS LOCATED PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE LABEL THE CLEAR FLOOR SPACE IN BATHROOMS. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHT 120-A1.1 ON THE ENLARGED KITCHEN PLAN THE ICE
 CUBER B4 IS NOT LABELED PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 5. SHT. 120-A1.1 K10 IS THE HOT FOOD TABLE ELECTRIC OR
 GAS IT DOES NOT INDICATE ON THE EQUIPMENT SCHEDULE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT. 120-A1.1 K21 IS NOT LISTED ON THE EQUIPMENT
 SCHEDULE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. 190-P1.0 ON THE WATER ISOMETRIC THE AIR
 CHAMBERS ARE NOT APPROVED THEY SHALL COMPLY WITH FBC PL
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 8. SHT. 190-P1.0 ON THE WATER ISOMETRIC IT SHOWS THE
 TANKLESS WATER HEATER ABOVE THE MOP AND HAND SINK ON
 THE FLOOR PLAN IT SHOWS ABOVE THE 3 COMP SINK PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. 190-P1.0 ON THE WATER ISOMETRIC PLEASE SHOW
 SIZE OF ALL DROPS. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. 190-P1.0 ON THE WATER ISOMETRIC VALVES ARE
 REQUIRED AT EACH DROP AND THE MAIN FEED COMING INTO THE
 BUILDING .PER FBC PL 606.1 LOCATION OF FULL-OPEN
 VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS: 2. ON THE WATER DISTRIBUTION SUPPLY PIPE AT
 THE ENTRANCE INTO THE STRUCTURE. 5. ON THE TOP OF EVERY
 WATER DOWN-FEED PIPE IN OCCUPANCIES OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 11. SHT. 190-P1.0 ON THE WATER ISOMETRIC A BACK FLOW IS
 REQUIRED ON THE SUPPLY FOR ICE MACHINES, BEVERAGE
 DISPENSERS AND WATER FILTERS. PER FBC PL 608.3,
 608.16.1 AND 608.16.10
  
 12. SHT. 190-P1.0 THE NOTE UNDER PLUMBING GENERAL NOTES
 STATES THE GREASE WASTE PIPE SHALL BE CPVC BUT THE
 ISOMETRIC SHOWS THE BRANCH PIPING AS PVC PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 13. THE 3 COMP SINK SHALL BE INDIRECTLY WASTED TO FLOOR
 SINK. PER FBC PL 802.1.1
  
 14. THE BRANCH DRAIN FOR THE DRINKING FOUNTAIN SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM
 GROUPS. PER FBC PL 912.1
  
 15. THE GLASS WASHER IN BAR AREA, THE FLOOR DRAINS IN
 THE BATHROOMS AND DRAINS FROM THE ICE MACHINES SHALL
 NOT DISCHARGE INTO THE GREASY WASTE SYSTEM. PER FBC PL
 1003.2
  
 16. PLEASE PROVIDE SPECIFICATIONS FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 17. PLEASE PROVIDE A PIPING DETAIL FOR GREASE
 INTERCEPTOR SHOWING TWO WAY CLEANOUTS ON INLET AND
 OUTLET ALSO TEST PORT ON OUTLET. PER WPB UTILITIES DEPT
  
 18. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. PER FBC PL 1003.2
  
 19. SHT. 210-P2.1 DETAIL A1 SHOWS A 2" WATER MAIN
 BREAKING DOWN TO 11/2" THE WATER ISOMETRIC ON SHT-P1.0
 ONLY SHOWS A 3/4" MAIN PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 20. IF A WATER FILTER SYSTEM IS BEING USED PLEASE SHOW
 ON WATER ISOMETRIC AND PROVIDE A PIPING DETAIL. PER WPB
 AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-19 Cont ID  
Sent By aaponte Date 2018-06-19 Time 11:13 Rev Time 0.00
Received By aaponte Date 2018-06-19 Time 11:13 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved