Plan Review Details - Permit 17110126
Plan Review Stops For Permit 17110126
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2019-02-14 Cont ID  
Sent By jduprey Date 2019-02-14 Time 14:54 Rev Time 0.00
Received By jduprey Date 2019-02-14 Time 13:54 Sent To  
Notes
2019-02-14 13:58:53*PROVISO*
  
 PROVIDE THE REQUIERED TEST REPORTS FOR THE SPECIFIC
 CONDITIONS FOR THIS JOB. THIS CAN PERFORMED ON SITE AND
 CERTIFIED BY AN ENGINEER.
  
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
 .
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2019-02-04 Cont ID  
Sent By shill Date 2019-02-04 Time 08:15 Rev Time 0.00
Received By shill Date 2019-02-04 Time 08:15 Sent To  
Notes
2019-02-04 08:18:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COURTESY REVIEW VIA EMAIL:
  
 1. THE FLOORING SPEC SHEETS (PARKAY FLOORS) DOES NOT
 APPEAR TO BE TESTED TO THE REQUIRED STANDARD, ASTME-84
 (SEE PREVIOUS COMMENT LISTS).
  
 2. THE UNDERLAYMENT TEST REPORTS USED A DROPPED GYPSUM
 CEILING WHICH IS NOT YOUR JOB CONDITION. EITHER PROVIDE
 A TEST REPORT OR A COMPARATIVE ANALYSIS.
  
 3. ASTM E-84 TEST REPORT FOR FLOOR MUFFLER WAS SENT TO
 RICHARD MCCALLA VIA EMAIL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2019-01-04 Cont ID  
Sent By shill Date 2019-01-04 Time 07:11 Rev Time 0.00
Received By shill Date 2019-01-04 Time 07:11 Sent To  
Notes
2019-01-04 07:11:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LISTS: PLEASE DO NOT RESUBMIT WITHOUT
 THIS INFORMATION!! PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE!!
  
 7TH REVIEW - THE TEST REPORTS PROVIDED FOR "MASTERS
 BUILDING PRODUCTS" (STAPLED TO SPEC SHEET FOR
 "SOUNDGUARD") USED AN ASSEMBLY WITH A DROPPED GYPSUM
 CEILING. FLAME SPREAD TEST NOT PROVIDED.
  
 "QUIET WALK PLUS" SPEC SHEET WAS ALSO PROVIDED; NO TEST
 REPORTS WERE PROVIDED WITH THE SPEC SHEET.
  
 PLEASE SEE PREVIOUS SIX COMMENT LISTS REGARDING THE
 THREE TEST REPORTS REQUIRED FOR FLOORING UNDERLAYMENT.
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 THIS INFORMATION CAN BE SENT VIA EMAIL RATHER THAN
 RESUBMITTAL; INCLUDE PERMIT NUMBER AND "FLOORING
 UNDERLAYMENT" IN THE SUBJECT LINE.
  
 2. TILE IS PROPOSED ON 1ST FLOOR, VINYL ON 2ND FLOOR.
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 720.2, SOUND-INSULATING MATERIALS TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25, SMOKE-DEVELOPED
 INDEX NOT MORE THAN 450. (NOTE THAT THIS CODE REFERENCE
 HAS BEEN CORRECTED TO REFLECT COMBUSTIBLE
 CONSTRUCTION).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2018-12-05 Cont ID  
Sent By shill Date 2018-12-05 Time 15:05 Rev Time 0.00
Received By shill Date 2018-12-05 Time 15:05 Sent To  
Notes
2018-12-05 15:05:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LISTS: PLEASE DO NOT RESUBMIT WITHOUT
 THIS INFORMATION!! PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE!!
  
 2. TILE IS PROPOSED ON 1ST FLOOR, VINYL ON 2ND FLOOR.
  
 RESPONSE LETTER STATES THAT THE FLOORING UNDERLAYMENT
 INFO IS ATTACHED, BUT I WAS NOT ABLE TO LOCATE IT.
 PROVIDE THE FOLLOWING TEST REPORTS:
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-09-25 Cont ID  
Sent By shill Date 2018-09-25 Time 18:04 Rev Time 0.00
Received By shill Date 2018-09-25 Time 18:04 Sent To  
Notes
2018-09-25 18:06:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK
  
 2. TILE IS PROPOSED ON 1ST FLOOR, VINYL ON 2ND FLOOR.
  
 RESPONSE LETTER STATES THAT THE FLOORING UNDERLAYMENT
 INFO IS ATTACHED, BUT I WAS NOT ABLE TO LOCATE IT.
 PROVIDE THE FOLLOWING TEST REPORTS:
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-05-13 Cont ID  
Sent By shill Date 2018-05-13 Time 10:14 Rev Time 0.00
Received By shill Date 2018-05-13 Time 10:00 Sent To  
Notes
2018-05-13 10:15:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. A0 INDICATES THE BUILDING TYPE AS IIB. PLEASE ADVISE
 AS TO HOW ENGINEER HAS MADE THIS DETERMINATION. OUR
 RECORDS SHOW TWO RECORDS RESEARCH REQUESTS DONE IN
 2/2017 AND 9/2017, AND THE RECORDS SHOW WOOD FRAME IN
 THIS STRUCTURE. ALSO, THE ROOF PERMIT 98090008 HAS A
 SPECIFICATION FOR A NAILABLE DECK.
  
 THE PREVIOUS REVIEWER RELIED ON THIS INFORMATION WHEN
 DOING THE REVIEW. FOR A COMBUSTIBLE BUILDING, THE FLAME
 SPREAD FOR THE FLOORING UNDERLAYMENT HAS A MORE
 STRINGENT REQUIREMENT OF 25 AS OPPOSED TO 200 FOR TYPE
 I/TYPE II BUILDINGS.
  
 WITHOUT ACCURATE INFORMATION, AN ACCURATE CHECKLIST
 CANNOT BE PROVIDED AT THIS TIME. HAS ENGINEER BEEN TO
 THIS JOB? PROVIDE INFORMATION REGARDING WALL
 CONTRUCTION, FLOOR CONSTRUCTION, ROOF CONSTRUCTION.
  
 2. FLOORING PROPOSED IS NOT CLEAR. PLEASE ADVISE. A
 FLOORING UNDERLAYMENT CANNOT BE REVIEWED UNTIL THE
 FLOOR CONSTRUCTION AND FLOORING PROPOSED IS DETERMINED.
  
 PLEASE NOTE THAT VERY FEW PRODUCTS HAVE THE THREE TESTS
 REQUIRED.
  
 TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC SHEETS
 ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 EXCEPTION IN FBC B 603.1 IS FOR BUILDING TYPE I & II.
 IF THE BUILDING IS III, IV, V, PER FBC B 720.2 FLAME
 SPREAD LESS THAN 25 IS REQUIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-02-23 Cont ID  
Sent By aclange Date 2018-02-23 Time 10:28 Rev Time 0.00
Received By aclange Date 2018-02-23 Time 09:38 Sent To  
Notes
2018-02-23 10:28:39****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 THIRD REVIEW:
  
 SANE COMMENT:
  
 1. PROVIDE TWO COPIES OF THE SOUND PROOFING
 SPECIFICATIONS FOR THE SECOND FLOOR APARTMENTS THAT
 SHOW COMPLIANCE WITH THE FOLLOWING STANDARDS.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09
  
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 NEW COMMENT:
  
 A. ON PAGE A.0 THE BUILDING DEPARTMENT IS SHOWN IN
 HIALEAH GARDE, FL.. PLEASE UPDATE ADDRESS TO 401
 CLEMATIS ST. WEST PALM BEACH, FL 33402 FBC 107.2.1
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By aclange Date 2017-12-27 Time 09:14 Rev Time 0.00
Received By aclange Date 2017-12-27 Time 07:46 Sent To  
Notes
2017-12-27 09:14:03****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 SECOND REVIEW:
  
 1. PROVIDE TWO COPIES OF THE SOUND PROOFING
 SPECIFICATIONS FOR THE SECOND FLOOR APARTMENTS THAT
 SHOW COMPLIANCE WITH THE FOLLOWING STANDARDS.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09
  
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 2. OK ADDRESSED.
  
 3. PERMIT VALUE ADJUSTED PER ESTIMATE SUBMITTED. OK.
  
 4. OK ADDRESSED.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By aclange Date 2017-11-14 Time 12:27 Rev Time 0.00
Received By aclange Date 2017-11-14 Time 10:52 Sent To  
Notes
2017-11-14 12:31:16****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. PROVIDE TWO COPIES OF THE SOUND PROOFING
 SPECIFICATIONS FOR THE SECOND FLOOR APARTMENTS.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2. PERMIT VALUE TOO LOW. ADJUST PERMIT VALUE. FBC 109.3
 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 3. SINCE THE VALUE OF THE PROJECT WILL BE ABOVE $25,000
 A DESIGN PROFESSIONAL IS REQUIRED.
 DESIGN PROFESSIONAL ? REQUIRED
 PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS
 DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE
 PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS 481.
 SEE BELOW:
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 WHERE SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL
 IS AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION
 DOCUMENTS TO BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN REQUIRED BY THE BUILDING OFFICIAL, AND
 MAY REQUIRE ONLY ONE SET OF SUBMITTALS.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
 DESIGN PROFESSIONAL ? EXCEPTIONS
  
 FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
  
 (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
  
 (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
  
 (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING,
 TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY
 ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST;
 OR
  
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF
 A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR
 SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
 4. NOTE SHOWN ON A-3 OTHER AREAS AFFECTED BY THE
 ALTERATION. PROVIDE ADDITIONAL INFORMATION.
 WILL FRAMING, DRYWALL OR INSULATION BE PART OF THIS
 PROJECT? IF SO SHOW ON PLANS THE LOCATION AND EXTENT OF
 THIS WORK. SHOW THE EXTERIOR WORK THAT WILL BE
 COMPLETED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2018-12-20 Cont ID  
Sent By jpearson Date 2018-12-20 Time 11:00 Rev Time 0.00
Received By jpearson Date 2018-12-20 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2018-11-05 Cont ID  
Sent By jpearson Date 2018-11-05 Time 17:09 Rev Time 0.00
Received By jpearson Date 2018-11-05 Time 17:09 Sent To  
Notes
2018-11-05 17:09:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: NEW REVIEW BASED ON DESIGN
 PROFESSIONAL CHANGE. DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION TO JUSTIFY SERVICE
 SIZE. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220 (LOAD CALCULATION FOR MAIN NOT PROVIDED. LOAD
 CALCULATION FOR PANELS DOES NOT MATCH LOADS SPECIFIED
 IN PANEL SCHEDULE ON SHEET E-1. PROVIDE AS PREVIOUSLY
 REQUESTED.)
 2. BASED ON LOADS PROVIDED, SERVICE IS NOT OF
 SUFFICIENT SIZE FOR THE LOAD. PROVIDE CORRECTION. NEC
 215.2, 215.3, 408.30, 408.36 (NOT CORRECTED, SEE NOTE
 1)
 3. BASED ON LOADS PROVIDED, FEEDERS TO FPL ARE NOT
 SIZED PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16)
 (ONCE LOAD IS CALCULATED PROPERLY, SIZE FEEDERS
 APPRORIATELY.)
 4. PROVIDE CALCULATION FOR WIRE SIZE TO METERS/ METER
 BANKS. NEC 220, 215.2, 215.3, 240.21 (NOT PROVIDED.)
 5. PROVIDE METHOD OF TAPPING WIRES TO EACH METER. AS
 SHOWN ON PLAN, THE WIRES WOULD GO TO INDIVIDUAL METERS.
 HOW WOULD THIS BE ACCOMPLISHED? IF A TAP IS TO BE USED,
 TAP RULES DICTATE THAT THE TAPS MUST TERMINTATE IN A
 SINGLE BREAKER OR SET OF FUSES. PROVIDE COMPLIANCE. NEC
 240.21(B)(5); WPB FBC 107.2.1 (NOT CORRECTED.)
 6. SHEET E-1 SHOWS UNIT TYPES A, B, AND C. SHEET E-3
 SHOWS UNIT TYPES A AND B. ATTEMPTED LOAD CALCULATION
 SHOWS 3 TYPES OF UNITS. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1 (NOT CORRECTED.)
 7. PROVIDE ACCURATE SIZED GROUNDING ELECTRODE
 CONDUCTOR. NEC 250.66 (CANNOT BE DETERMINED UNTIL LOAD
 IS CALCULATED PROPERLY.)
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED.)
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9 (NOT PROVIDED.)
 10. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 (NOT PROVIDED.)
 11. PROVIDE SPEC SHEET FOR 4000 VA RANGE SPECIFIED IN
 LOAD CALCULATIONS. NEC 110.3 (NOT PROVIDED. LOAD
 CALCULATION NOW SHOWS 8000 VA FOR RANGE, PANEL SCHEDULE
 SHOWS 4000 VA. PROVIDE CLARIFICATION AND/OR
 CORRECTION.)
  
 BE ADVISED THAT THERE SEEMS TO BE A SUBSTANTIAL AMOUNT
 OF INFORMATION INCORRECT AND/OR MISSING WITH THIS PLAN.
 FUTURE ADDITIONAL COMMENTS ARE POSSIBLE WHEN THE
 INFORMATION ABOVE IS SUPPLIED.
  
 NEW COMMENTS:
  
 12. NEW RISER SHOWS 2 - 500 MCM WIRES TO MAIN
 DISCONNECT FUSED AT 650 AMP. THERE SHOULD BE A MINIMUM
 OF 3 WIRES IN A SINGLE PHASE SERVICE. THIS WIRE SIZE IS
 NOT RATED FOR 650 AMPS. A 650 AMP FUSE IS NOT A
 STANDARD FUSE SIZE PER NEC 240.6, PROVIDE DETAILS.
 PROVIDE SIZE AND AIC RATING OF MAIN DISCONNECT. NEC
 110.3, 215.5, 220.5, 240.6, 310.15; WPB FBC 107.2.1
 13. IT APPEARS THAT THERE IS NOT AN EQUIPMENT GROUNDING
 CONDUCTOR IN THE CONDUITS ON THE LOAD SIDE OF THE
 SERVICE DISCONNECTING MEANS. A GROUNDED CIRCUIT
 CONDUCTOR IS NOT PERMITTED TO FUNCTION AS THE EQUIPMENT
 GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.142(B)
 14. CONDUIT SIZES SPECIFIED FOR FEEDERS IS NOT CODE
 COMPLIANT. PROVIDE CORRECTION. NEC TABLE 1 AND 4,
 INFORMATIVE ANNEX C.
 15. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2018-09-18 Cont ID  
Sent By jpearson Date 2018-09-18 Time 11:13 Rev Time 0.00
Received By jpearson Date 2018-09-18 Time 08:17 Sent To  
Notes
2018-09-18 11:06:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: NEW REVIEW BASED ON DESIGN
 PROFESSIONAL CHANGE. DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION TO JUSTIFY SERVICE
 SIZE. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220
 2. BASED ON LOADS PROVIDED, SERVICE IS NOT OF
 SUFFICIENT SIZE FOR THE LOAD. PROVIDE CORRECTION. NEC
 215.2, 215.3, 408.30, 408.36
 3. BASED ON LOADS PROVIDED, FEEDERS TO FPL ARE NOT
 SIZED PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16)
 4. PROVIDE CALCULATION FOR WIRE SIZE TO METERS/ METER
 BANKS. NEC 220, 215.2, 215.3, 240.21
 5. PROVIDE METHOD OF TAPPING WIRES TO EACH METER. AS
 SHOWN ON PLAN, THE WIRES WOULD GO TO INDIVIDUAL METERS.
 HOW WOULD THIS BE ACCOMPLISHED? IF A TAP IS TO BE USED,
 TAP RULES DICTATE THAT THE TAPS MUST TERMINTATE IN A
 SINGLE BREAKER OR SET OF FUSES. PROVIDE COMPLIANCE. NEC
 240.21(B)(5); WPB FBC 107.2.1
 6. SHEET E-1 SHOWS UNIT TYPES A, B, AND C. SHEET E-3
 SHOWS UNIT TYPES A AND B. ATTEMPTED LOAD CALCULATION
 SHOWS 3 TYPES OF UNITS. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 7. PROVIDE ACCURATE SIZED GROUNDING ELECTRODE
 CONDUCTOR. NEC 250.66
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 10. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 11. PROVIDE SPEC SHEET FOR 4000 VA RANGE SPECIFIED IN
 LOAD CALCULATIONS. NEC 110.3
  
 BE ADVISED THAT THERE SEEMS TO BE A SUBSTANTIAL AMOUNT
 OF INFORMATION INCORRECT AND/OR MISSING WITH THIS PLAN.
 FUTURE ADDITIONAL COMMENTS ARE POSSIBLE WHEN THE
 INFORMATION ABOVE IS SUPPLIED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-05-08 Cont ID  
Sent By jpearson Date 2018-05-08 Time 07:28 Rev Time 0.00
Received By jpearson Date 2018-05-07 Time 13:09 Sent To  
Notes
2018-05-07 17:19:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED USED A DEMAND
 FACTOR FOR EACH UNIT, AND THEN USED THOSE NUMBERS TO
 APPLY A SECOND DEMAND FACTOR FOR MULTI-FAMILY
 DWELLINGS, WHICH IS NOT PERMITTED. ADDITIONALLY, I DO
 NOT SEE ANY HOUSE PANEL LOADS ADDED. WILL THERE BE ANY
 HOUSE LOADS INCLUDING LIGHTING OF EXTERIOR? FBC
 107.2.1; NEC 220.40 (NEC 220.83 CANNOT BE USED FOR THIS
 PROJECT, IT IS ONLY FOR A ONE FAMILY DWELLING WHERE
 LOAD IS TO BE ADDED. PROVIDE ACCURATE LOAD CALCULATION
 AS REQUESTED.)(4TH REVIEW, LOAD CALCULCATION NOT
 CORRECT. MATH FOR EACH COLUMN IS NOT TOTALED CORRECTLY,
 RESULTING IN A FINAL NUMBER THAT IS INCORRECT. IT IS
 RECOMMENDED THAT THE DESIGN PROFESSIONAL MAKE AN
 APPOINTMENT TO MEET WITH PLAN REVIEWER.)
 2. CORRECTED.
 3. BASED ON THE LOADS PROVIDED, THE PROPOSED SERVICE IS
 NOT ADEQUATE FOR THE LOADS. PROVIDE CORRECTION. NEC
 215.2, 215.3, 220.40 (BASED ON MY CALCULATION FROM THE
 LOADS PROVIDED ON PLAN, THE MINIMUM SERVICE WOULD NEED
 TO HAVE A CAPACITY OF AT LEAST 886 AMPS. SERVICE
 DESIGNED IS NOT ADEQUATE FOR THE LOADS SPECIFIED.)(4TH
 REVIEW, LOAD CALCULATION PROVIDED, WHICH IS INCORRECT,
 CALLED FOR A 900 AMP SERVICE, BUT THE PLAN SHOWS AN 800
 AMP SERVICE. THIS ITEM STILL NEEDS CORRECTION.)
 4. PROVIDE ACCURATE RISER DIAGRAM. BASED ON SITE VISIT,
 THE EXISTING MAIN IS 400 AMPS, NOT 800. IS THE PROPOSED
 SERVICE JUST A DISCONNECT, OR DOES IT HAVE BREAKERS
 THAT FEED THE METER STACKS? HOW ARE THE METER STACKS
 FED? IS THERE A GUTTER WITH TAPS? WHAT IS THE PHYSICAL
 LOCATION OF ALL THE METERS? RISER PROVIDED DOES NOT
 HAVE ENOUGH INFORMATION. PROVIDE CLARIFICATION. FBC
 107.2.1; NEC 215.5 (THE KEY PLAN SHOWS THE METER STACKS
 IN 3 LOCATIONS, SO TAP RULES DICTATE THAT THESE TAPS
 MUST TERMINATE IN A SINGLE BREAKER OR SET OF FUSES.
 PROVIDE CORRECTION. NEC 240.21(B)(5) )
 5. CORRECTED.
 6. GROUNDING ELECTRODE CONDUCTOR SPECIFIED IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 250.66 (4TH REVIEW,
 SIZE NOT CORRECT.)
 7. SHOW LOCATION OF SERVICE ON PLAN. FBC 107.2.1 (NOT
 CORRECTED.)(4TH REVIEW. KEY PLAN IS NOT TO SCALE AND
 DIFFICULT TO SEE, PROVIDE AS PREVIOUSLY REQUESTED.
 THERE WERE TWO E-2 SHEETS PROVIDED AND THE SECOND ONE
 SHOWS A FULL LAYOUT OF BUILDING, BUT NEED TO REMANE THE
 SHEET SO THERE ARE NOT DUPLICATES.)
 8. SHOW LOCATION OF NEW CU UNITS ON PLAN. PROVIDE GFCI
 PROTECTED OUTLET FOR SERVICING OF A/C EQUIPMENT PER
 CODE. NEC 210.63; FBC 107.2.1 (4TH REVIEW, NOT PROVIDED
 SATISFACTORILY. NEED FULL PLAN SHOWING BUILDING AND THE
 LOCATIONS OF UNITS. THERE WERE TWO E-2 SHEETS PROVIDED
 AND THE SECOND ONE SHOWS A FULL LAYOUT OF BUILDING, BUT
 DOES NOT SHOW LOCATIONS OF UNITS. NEED TO REMANE THE
 SHEET SO THERE ARE NOT DUPLICATES.)
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. ADDITIONAL PLAN REVIEW FEE ADDED PER PREVIOUS
 COMMENT. PLAN REVIEW FEES NEED TO BE PAID BEFORE
 RESUBMITTAL OF PLANS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-02-28 Cont ID  
Sent By jpearson Date 2018-02-28 Time 08:12 Rev Time 0.00
Received By jpearson Date 2018-02-28 Time 08:12 Sent To  
Notes
2018-02-28 08:12:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED USED A DEMAND
 FACTOR FOR EACH UNIT, AND THEN USED THOSE NUMBERS TO
 APPLY A SECOND DEMAND FACTOR FOR MULTI-FAMILY
 DWELLINGS, WHICH IS NOT PERMITTED. ADDITIONALLY, I DO
 NOT SEE ANY HOUSE PANEL LOADS ADDED. WILL THERE BE ANY
 HOUSE LOADS INCLUDING LIGHTING OF EXTERIOR? FBC
 107.2.1; NEC 220.40 (NEC 220.83 CANNOT BE USED FOR THIS
 PROJECT, IT IS ONLY FOR A ONE FAMILY DWELLING WHERE
 LOAD IS TO BE ADDED. PROVIDE ACCURATE LOAD CALCULATION
 AS REQUESTED.)
 2. CORRECTED.
 3. BASED ON THE LOADS PROVIDED, THE PROPOSED SERVICE IS
 NOT ADEQUATE FOR THE LOADS. PROVIDE CORRECTION. NEC
 215.2, 215.3, 220.40 (BASED ON MY CALCULATION FROM THE
 LOADS PROVIDED ON PLAN, THE MINIMUM SERVICE WOULD NEED
 TO HAVE A CAPACITY OF AT LEAST 886 AMPS. SERVICE
 DESIGNED IS NOT ADEQUATE FOR THE LOADS SPECIFIED.)
 4. PROVIDE ACCURATE RISER DIAGRAM. BASED ON SITE VISIT,
 THE EXISTING MAIN IS 400 AMPS, NOT 800. IS THE PROPOSED
 SERVICE JUST A DISCONNECT, OR DOES IT HAVE BREAKERS
 THAT FEED THE METER STACKS? HOW ARE THE METER STACKS
 FED? IS THERE A GUTTER WITH TAPS? WHAT IS THE PHYSICAL
 LOCATION OF ALL THE METERS? RISER PROVIDED DOES NOT
 HAVE ENOUGH INFORMATION. PROVIDE CLARIFICATION. FBC
 107.2.1; NEC 215.5 (MANY OF THE QUESTIONS IN THIS
 PARAGRAPH ARE NOT ANSWERED WITH YOUR RESPONSE TO ?SEE
 E-1?. PROVIDE DETAILS AS REQUESTED.)
 5. IF METER BANKS ARE ALL TAPPED FROM 800 AMP MAIN,
 PROVIDE LOAD CALCULATION FOR EACH SET OF FEEDERS TO
 CONFIRM THE FEEDER IS SIZED ADEQUATELY. NEC 215.2,
 220.40 (LOAD CALCULATION TO EACH OF THE 8 METER BANKS
 IS NOT CORRECT AND WIRE IS NOT SIZED PROPERLY.)
 6. GROUNDING ELECTRODE CONDUCTOR SPECIFIED IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 250.66
 7. SHOW LOCATION OF SERVICE ON PLAN. FBC 107.2.1 (NOT
 CORRECTED.)
 8. SHOW LOCATION OF NEW CU UNITS ON PLAN. PROVIDE GFCI
 PROTECTED OUTLET FOR SERVICING OF A/C EQUIPMENT PER
 CODE. NEC 210.63; FBC 107.2.1 (NOT PROVIDED)
 9. PROVIDE COPY OF SIGNED CONTRACT FOR ELECTRICAL WORK,
 SHOWING TOTAL VALUE OF ALL WORK INCLUDING MATERIALS AND
 LABOR. THE ESTIMATE PROVIDED IS TOO LOW AND DOES NOT
 REFLECT THE AMOUNT OF WORK REQUIRED FOR THIS PROJECT.
 FBC 109.3 (CONTRACT PROVIDED DOES NOT INCLUDE WORK TO
 SERVICE. PROVIDE CORRECTION)
 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE (SHOW ON PLAN). THIS IS NOT A WIRE, BUT AN
 ACTUAL TERMINATION POINT. SEE CODE. NEC 250.94 (NOT
 SHOWN ON PLAN)
  
 NEW COMMENT:
  
 11. PROVIDE SPECS FOR MECHANICAL EQUIPMENT TO CONFIRM
 STATED DEMAND IS ACCURATE. NEC 110.3, 220; FBC 107.2.1
 12. PLEASE BE ADVISED THAT SOME OF THE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-04 Cont ID  
Sent By jpearson Date 2018-01-04 Time 12:40 Rev Time 0.00
Received By jpearson Date 2018-01-04 Time 12:40 Sent To  
Notes
2018-01-04 12:40:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED USED A DEMAND
 FACTOR FOR EACH UNIT, AND THEN USED THOSE NUMBERS TO
 APPLY A SECOND DEMAND FACTOR FOR MULTI-FAMILY
 DWELLINGS, WHICH IS NOT PERMITTED. ADDITIONALLY, I DO
 NOT SEE ANY HOUSE PANEL LOADS ADDED. WILL THERE BE ANY
 HOUSE LOADS INCLUDING LIGHTING OF EXTERIOR? FBC
 107.2.1; NEC 220.40
 2. PER CODE, FOR DWELLING UNITS, ATTACHED GARAGES, AND
 DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B)
 3. BASED ON THE LOADS PROVIDED, THE PROPOSED SERVICE IS
 NOT ADEQUATE FOR THE LOADS. PROVIDE CORRECTION. NEC
 215.2, 215.3, 220.40
 4. PROVIDE ACCURATE RISER DIAGRAM. BASED ON SITE VISIT,
 THE EXISTING MAIN IS 400 AMPS, NOT 800. IS THE PROPOSED
 SERVICE JUST A DISCONNECT, OR DOES IT HAVE BREAKERS
 THAT FEED THE METER STACKS? HOW ARE THE METER STACKS
 FED? IS THERE A GUTTER WITH TAPS? WHAT IS THE PHYSICAL
 LOCATION OF ALL THE METERS? RISER PROVIDED DOES NOT
 HAVE ENOUGH INFORMATION. PROVIDE CLARIFICATION. FBC
 107.2.1; NEC 215.5
 5. IF METER BANKS ARE ALL TAPPED FROM 800 AMP MAIN,
 PROVIDE LOAD CALCULATION FOR EACH SET OF FEEDERS TO
 CONFIRM THE FEEDER IS SIZED ADEQUATELY. NEC 215.2,
 220.40
 6. GROUNDING ELECTRODE CONDUCTOR SPECIFIED IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 250.66
 7. SHOW LOCATION OF SERVICE ON PLAN. FBC 107.2.1
 8. SHOW LOCATION OF NEW CU UNITS ON PLAN. PROVIDE GFCI
 PROTECTED OUTLET FOR SERVICING OF A/C EQUIPMENT PER
 CODE. NEC 210.63; FBC 107.2.1
 9. PROVIDE COPY OF SIGNED CONTRACT FOR ELECTRICAL WORK,
 SHOWING TOTAL VALUE OF ALL WORK INCLUDING MATERIALS AND
 LABOR. THE ESTIMATE PROVIDED IS TOO LOW AND DOES NOT
 REFLECT THE AMOUNT OF WORK REQUIRED FOR THIS PROJECT.
 FBC 109.3
 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE (SHOW ON PLAN). THIS IS NOT A WIRE, BUT AN
 ACTUAL TERMINATION POINT. SEE CODE. NEC 250.94
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-20 Cont ID  
Sent By jpearson Date 2017-11-20 Time 15:52 Rev Time 0.00
Received By jpearson Date 2017-11-20 Time 15:52 Sent To  
Notes
2017-11-20 15:52:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 3. SHOW ON FLOOR PLAN ALL EXISTING SMOKE ALARMS. IF
 NONE ARE EXISTING, OR NOT TO CODE, SHOW AS NEW
 INSTALLATION. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2018-12-10 Cont ID  
Sent By pleduc Date 2018-12-10 Time   Rev Time 0.00
Received By pleduc Date 2018-12-10 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-09-14 Cont ID  
Sent By pleduc Date 2018-09-14 Time   Rev Time 0.00
Received By pleduc Date 2018-09-13 Time 15:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-04-26 Cont ID  
Sent By pleduc Date 2018-04-26 Time   Rev Time 0.00
Received By pleduc Date 2018-04-25 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-27 Cont ID  
Sent By pleduc Date 2017-12-27 Time   Rev Time 0.00
Received By pleduc Date 2017-12-27 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By pleduc Date 2017-11-13 Time   Rev Time 0.00
Received By pleduc Date 2017-11-09 Time 12:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 07:54 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 07:42 Sent To  
Notes
2019-01-03 07:54:44GAS COMMENTS: APPROVED
  
 PROVISO
 1. PERMIT IS TO BE FOR GAS DEMO ONLY
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2018-09-27 Cont ID  
Sent By jesmith Date 2018-09-27 Time 09:00 Rev Time 0.00
Received By jesmith Date 2018-09-27 Time 09:00 Sent To  
Notes
2018-09-27 09:00:195TH REVIEW:
 PERMIT 17110126
 GAS COMMENTS: APPROVED
  
 PROVISO
 GAS PERMIT IS REQUIRED; PERMIT IS TO BE FOR GAS DEMO
 ONLY
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 14:59 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 14:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 09:02 Rev Time 0.00
Received By gjohnson Date 2018-03-03 Time 09:02 Sent To  
Notes
2018-03-03 09:04:503RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED 2ND
 REQUEST
  
 1. PROVIDE PLAN SHOWING HOW AND WHERE GAS WILL BE
 DEMOED AND CAPPED OFF. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 17:47 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 17:47 Sent To  
Notes
2018-01-18 17:50:001ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLAN SHOWING HOW AND WHERE GAS WILL BE
 DEMOED AND CAPPED OFF. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By gjohnson Date 2017-11-22 Time 12:33 Rev Time 0.00
Received By gjohnson Date 2017-11-22 Time 12:33 Sent To  
Notes
2017-11-22 13:00:331ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. UNDER THE SCOPE OF WORK IT LIST REPLACE A TANK WATER
 HEATER SHT. A-2 SHOWS A TANK WATER HEATER IN THE A UNIT
 AND A TANKLESS IN THE B UNITS PLEASE CLARIFY WHICH TYPE
 OF WATER HEATERS ARE BEING USED HOW MANY ARE BEING
 CHANGED AND IN WHICH APARTMENTS. PER WPB AMEND TO FBC
 107.2.1
  
 2. PROVIDE EXISTING GAS PIPING DIAGRAM SHOWING TYPE OF
 PIPE, SIZE, BTU LOAD, PRESSURE AND APPROXIMATE LENGTH
 OF PIPING. PER FBC FG 402.4.1, 402.4.2. AND WPB AMEND
 TO FBC 107.2.1
  
 3. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDES FOR THE WATER HEATERS. PER FBC FG
 402.2 AND WPB AMEND TO FBC 107.2.1
  
 4. WILL THE EXISTING VENTING BE USED IF SO IT SHALL BE
 INSPECTED PLEASE PLEASE NOTE ON PLAN STATING THIS. PER
 WPB AMEND TO FBC 107.2.1
  
 5. WILL THE NEW WATER HEATERS BE EXACT CHANGE OUT FROM
 EXISTING PLACE NOTE ON PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 6. A DROPTEST AFFIDAVIT ON THE COMPLETE GAS SYSTEM WILL
 BE REQUIRED AT FINAL INSPECTION PLEASE PLACE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2019-02-14 Cont ID  
Sent By jduprey Date 2019-02-14 Time 14:54 Rev Time 0.00
Received By jduprey Date 2019-02-14 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2019-01-04 Cont ID  
Sent By cpuell Date 2019-01-04 Time 14:18 Rev Time 0.00
Received By cpuell Date 2018-12-05 Time 09:24 Sent To  
Notes
2019-01-03 08:10:32TO S. HILL DESK
2019-01-03 07:34:251/2 TO JESMITH DESK / S.HILL
  
  
2018-12-10 11:39:25B11
2018-12-07 09:25:37LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2018-12-05 Cont ID  
Sent By shill Date 2018-12-05 Time 15:06 Rev Time 0.00
Received By shill Date 2018-10-24 Time 16:00 Sent To  
Notes
2018-10-25 16:00:56B20

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-09-27 Cont ID  
Sent By jesmith Date 2018-09-27 Time 09:01 Rev Time 0.00
Received By jesmith Date 2018-08-29 Time 14:17 Sent To  
Notes
2018-09-25 18:09:01ON JERRY SMITH'S DESK
  
2018-09-12 14:17:43B20

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-08-31 Cont ID  
Sent By lmarchan Date 2018-08-31 Time 10:47 Rev Time 0.00
Received By lmarchan Date 2018-08-29 Time 10:37 Sent To  
Notes
2018-08-31 10:37:16B08

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-13 Cont ID  
Sent By shill Date 2018-05-13 Time 10:15 Rev Time 0.00
Received By shill Date 2018-04-20 Time 14:51 Sent To  
Notes
2018-04-23 14:52:12B05

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 09:07 Rev Time 0.00
Received By gjohnson Date 2018-02-12 Time 14:14 Sent To  
Notes
2018-02-13 14:14:46B16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 18:03 Rev Time 0.00
Received By gjohnson Date 2017-12-21 Time 09:33 Sent To  
Notes
2017-12-22 09:34:00B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-22 Cont ID  
Sent By gjohnson Date 2017-11-22 Time 13:00 Rev Time 0.00
Received By gjohnson Date 2017-11-03 Time 10:08 Sent To  
Notes
2017-11-07 10:08:38B06

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2018-12-20 Cont ID  
Sent By ccole Date 2018-12-20 Time 13:23 Rev Time 0.00
Received By ccole Date 2018-12-20 Time 13:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2018-11-08 Cont ID  
Sent By cmontell Date 2018-11-08 Time 13:51 Rev Time 0.00
Received By cmontell Date 2018-11-08 Time 13:10 Sent To  
Notes
2018-11-08 13:32:15MECHANICAL PLAN REVIEW FAIL
  
 1) THE REQUESTED CORRECTED ENERGY COMPLIANCE FORMS WERE
 NOT CORRECTED AND RESUBMITTED.
  
 2) THE AC CALCULATIONS ARE BASING DESIGN CONDITIONS ON
 FT. LAUDERDALE, AND ARE INDICATING TRANE SYSTEMS TO BE
 INSTALLED, HOWEVER RHEEM SYSTEMS ARE SHOWN ON THE PLAN.
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-09-18 Cont ID  
Sent By ccole Date 2018-09-18 Time 13:40 Rev Time 0.00
Received By ccole Date 2018-09-18 Time 13:40 Sent To  
Notes
2018-09-18 13:52:123RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110126
 9/18/18
  
 1) THE REVISED PLAN IS STILL INDICATING A 2" CLEARANCE
 WILL BE PROVIDED AROUND THE AIR HANDLER, HOWEVER 4" IS
 REQUIRED.
  
 2) THE REQUESTED CORRECTED ENERGY COMPLIANCE FORMS WERE
 NOT CORRECTED AND RESUBMITTED.
  
 3) THE AC CALCULATIONS ARE BASING DESIGN CONDITIONS ON
 FT. LAUDERDALE, AND ARE INDICATING TRANE SYSTEMS TO BE
 INSTALLED, HOWEVER RHEEM SYSTEMS ARE SHOWN ON THE PLAN.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-04-27 Cont ID  
Sent By ccole Date 2018-04-27 Time 16:48 Rev Time 0.00
Received By ccole Date 2018-04-27 Time 16:48 Sent To  
Notes
2018-04-27 17:05:032ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110126
 4/27/18
  
 PLAN REVIEW RESULTS
  
 1) THE ENERGY COMPLIANCE FORMS MUST BE THE R405-2014
 VERSIONS, AND MUST BE SIGNED BY THE PERSON WHO PREPARED
 THE FORMS AND BY THE OWNER- SEE SECTION R103.1.1.2
 FBC-14 ENERGY CONSERVATION.
  
 2) M-1: A 4" CLEARANCE IS REQUIRED AROUND THE
 AIRHANDLER- PLEASE CORRECT THE NOTE SPECIFYING 2"-, AND
 VERIFY THE CONDENSATE PIPING IN THE AC CLOSET IS
 NON-COMBUSTIBLE- SECTIONS 602.2 AND 603.1.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By ccole Date 2018-02-22 Time 16:08 Rev Time 0.00
Received By ccole Date 2018-02-22 Time 16:08 Sent To  
Notes
2018-02-22 17:01:592ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110126
 2/22/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGY COMPLIANCE FORMS AND AND AC CALCULATIONS HAVE
 BEEN SUBMIITED FOR FOUR OF THE TWENTY APARTMENTS. THE
 UNITS ARE IDENTIFIED AS MODELS 1 & 2 LOW AND HIGH
 FLOOR, HOWEVER THE REPORT IS NOT INDICATING THAT THESE
 ARE "WORST CASE" CALCULATIONS, THEREFORE CALCULATIONS
 SHALL BE SUBMITTED FOR ALL OF THE APARTMENTS. IF THE
 CALCULATIONS ARE TO BE PERFORMED AS "WORST CASE" THEN
 THE
  
 REPORTS MUST BE LABELED AS SUCH, AND ALSO DEMONSTRATE
 THAT THE MODELS MEET THE PERFORMANCE REQUIREMENTS IN
 EACH OF THE FOUR CARDINAL (NORTH, SOUTH, EAST, AND
 WEST) ORIENTATIONS- SEE SECTION R405.4.2 FBC-14 ENERGY
 CONSERVATION. PLEASE NOTE THE APARTMENT MODEL
 IDENTIFICATIONS ( #1 & 2) IN THE CALCS DO NOT MATCH THE
 (TYPE A & B) IDENTIFICATIONS ON THE PLANS.
  
 2) 2ND REQUEST FOR MINIMUM VENTILATION FOR EACH
 APARTMENT USING EITHER MECHANICAL OR NATURAL MEANS-
 SECTION 401.2. THE RESUBMITTED PLAN INDICATES NATURAL
 FOR APARTMENT TYPE B BUT DOES NOT SHOW THE UNIT
 COMPLIES WITH 402.2- MINIMUM OPERABLE AREA TO THE
 OUTDOORS SHALL BE 4% OF THE FLOOR AREA. CONCERNING TYPE
 A THERE IS NO VENTILATION INDICATED OR CALCULATIONS
 PROVIDED.
  
 3) INDICATE THE DIEMNSIONS OF THE RETURN GRILL IN THE
 KITCHEN/LIVING ROOM OF THE TYPE B MODEL.
  
 4) PROVIDE A COMPLETE AC EQUIPMENT SCHEDULE ON THE PLAN
 FOR THE MODEL A SYSTEM- COOLING AND HEATING CAPACITY,
 SUPPLY CFMS, AND EFFICIENCY RATING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By ccole Date 2018-01-02 Time 13:31 Rev Time 0.00
Received By ccole Date 2018-01-02 Time 12:04 Sent To  
Notes
2018-01-02 14:13:301ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110126
 1/2/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SEE SECTIONS C403.2.1 AND C407.5.2.3 ENERGY
 CONSERVATION.
  
 2) REFER TO SECTION C101.4.5 FBC-14 ENERGY CONSERVATION
 AND SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE
 BUILDING.
  
 3) SHEET M-1: NATURAL OR MECHANICAL VENTILATION IS
 REQUIRED FOR EACH APARTMENT PER SECTION 401.2. PLEASE
 INDICATE WHICH METHOD WILL BE USED AND PROVIDED
 CALCULATIONS AND DETAILS.
  
 4) M-1: NO SUPPLY AND RETURN AIR IS SHOWN FOR THETYPE A
 APARTMENT BEDROOMS 1 & 2, AND NO SUPPLY IS PROVIDED TO
 THE TYPE B KITCHEN/LIVING/DINING ROOMS- SEE SECTION
 601.5 FBC-14 MECHANICAL AND CORRECT.
  
 5) M-1: VERIFY THE AC CLOSET DOORS ARE NON-COMBUSTIBLE
 IN ACCORDANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION CODE, AND SECTION 602.2.1 FBC-14
 MECHANICAL.
  
 6) M-1: AN INCORRECT WIND SPEED OF 160 MPH IS NOTED.
 PLEASE NOTE THAT THE WIND SPEED IN WEST PALM BEACH IS
 170 MPH. CORRECT THE NOTE AND PROVIDE COMPLETE WIND
 LOAD DESIGN CRITERIA INCLUDING THE IMPORTANCE FACTOR,
 EXPOSURE CATEGORY, AND THE LATERAL AND UPLIFT
 PRESSURES.
  
 7) PROVIDE A MECHANICAL SITE PLAN THAT SHOWS THE
 LOCATIONS OF ALL THE CONDENSERS AND THE REFRIGERANT
 PIPING RUNS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 07:58 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 07:50 Sent To  
Notes
2019-01-03 07:58:33PLUMBING COMMENTS: APPROVED
  
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-25 Time 08:32 Rev Time 0.00
Received By jesmith Date 2018-09-25 Time 17:58 Sent To  
Notes
2018-09-25 18:08:46ON JERRY SMITH'S DESK
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 14:59 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 09:05 Rev Time 0.00
Received By gjohnson Date 2018-03-03 Time 09:05 Sent To  
Notes
2018-03-03 09:07:05PLUMBING WILL BE APPROVED WHEN THE GAS IS APPROVED.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 17:45 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 17:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By gjohnson Date 2017-11-22 Time 12:08 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 17:29 Sent To  
Notes
2017-11-22 12:33:311ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE LEGAL DESCRIPTION ON THE PLAN DOES NOT MATCH THE
 LEGAL DESCRIPTION ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. UNDER THE LEGAL DESCRIPTION IT LIST UNIT #602 IS
 THIS THE ONLY APARTMENT THAT IS BEING REMODELED PLEASE
 CLEARLY INDICATE ON THE PLAN WHICH APARTMENTS ARE BEING
 REMODELED. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711