Plan Review Details - Permit 17110089
Plan Review Stops For Permit 17110089
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 13:32 Rev Time 0.00
Received By shill Date 2018-09-15 Time 13:32 Sent To  
Notes
2018-09-15 13:32:50FL STATE PRODUCT APPROVAL 14218-R9

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By shill Date 2017-11-21 Time 14:36 Rev Time 0.00
Received By shill Date 2017-11-21 Time 14:36 Sent To  
Notes
2017-11-21 14:36:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DOCUMENT NAMED 088000-2.0 REVIEWED GLASS YKK
 YHS501.PDF WAS PREPARED BY AN ENGINEER BUT IS NOT
 DIGITALLY SIGNED AND SEALED. IT IS NOT CLEAR IF THIS IS
 ASSOCIATED WITH A PRODUCT APPROVAL. IF IT IS A PART OF
 A PRODUCT APPROVAL, UPLOAD THIS DOCUMENT WITH THE COVER
 SHEET AND THE PRODUCT PROPOSED INDICATED.
  
 2. DOCUMENT 088000-1.1B REVIEWED GLAZING NOA DRAWING IS
 DIGITALLY SIGNED AND SEALED BUT HAS AN "INVALID"
 DIGITAL SIGNATURE, POSSIBLY BECAUSE THE DOCUMENT WAS
 ALTERED AFTER IT WAS DIGITALLY SIGNED AND SEALED.
  
 THIS DOCUMENT APPEARS TO BE THE SAME DOCUMENT AS THE
 EVALUATION REPORT ASSOCIATED WITH THE PRODUCT APPROVAL.
 IF THIS IS A PART OF THE PRODUCT APPROVAL, THIS SHOULD
 NOT BE SIGNED AND SEALED. EACH PRODUCT APPROVAL SHOULD
 BE UPLOADED IN ITS ENTIRETY AS ONE DOCUMENT, AND
 PRODUCT APPROVALS SHOULD NOT BE ORIGINAL SIGNED &
 SEALED DOCUMENTS.
  
 3. THE COVER SHEET FOR FL14218-R9 WAS SUBMITTED, BUT
 THE EVALUATION REPORT AN INSTALLATION INSTRUCTIONS WERE
 NOT ATTACHED TO THE COVER SHEET. THE EVALUATION REPORT
 AND INSTALLATION INSTRUCTIONS (AVAILABLE AS A LINK FROM
 THE COVER PAGE AT WWW.FLORIDABUILDING.ORG) IS REQUIRED
 FOR REVIEW AND INSPECTIONS.
  
 4. AS IT IS NOT CLEAR IF ONE PRODUCT IS BEING PROPOSED
 OR TWO. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED
 STOREFRONT. IF MORE THAN ONE PRODUCT IS PROPOSED, THE
 PLAN SHOULD INDICATE WHICH PRODUCT GOES IN EACH
 LOCATION. NOTE THAT NO DOORS WERE SUBMITTED; DO ANY OF
 THE STOREFRONT OPENINGS INCLUDE STOREFRONT DOORS? IF
 YES, PLEASE SUBMIT AT THIS TIME.
  
 PLEASE CONTACT ME IF YOU NEED ADDITIONAL GUIDANCE AS TO
 HOW TO RESOLVE COMMENTS.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-21 Cont ID  
Sent By shill Date 2017-11-21 Time 14:36 Rev Time 0.00
Received By shill Date 2017-11-09 Time 11:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 13:32 Rev Time 0.00
Received By shill Date 2018-09-15 Time 13:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By shill Date 2017-11-21 Time 14:36 Rev Time 0.00
Received By shill Date 2017-11-21 Time 14:36 Sent To  
Notes
2017-11-21 14:36:52SEE BUILDING REVIEW