Plan Review Details - Permit 17110040
Plan Review Stops For Permit 17110040
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-12-19 Cont ID  
Sent By shill Date 2017-12-19 Time 09:21 Rev Time 0.00
Received By shill Date 2017-12-19 Time 09:21 Sent To  
Notes
2017-12-19 09:24:09****PROVISOS****
 SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION MAY
 BE REQUIRED
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE A DETAIL FOR THE PROPOSED NEW BENCH
 INCLUDING BACK SUPPORT, FBC A 903.
  
 2ND REVIEW, RESPONSE REFERS TO A 7 A202. THIS IS THE
 SERVICE COUNTER DETAIL.
  
 2. A202, FBC A 904, PROVIDE A DETAIL FOR THE SERVICE
 COUNTER. CUSTOMER SIDE NOT TO EXCEED 2'6".
  
 3. PER ARCHITECT, UNIT 109 (SHEET A205) HAS BEEN
 REVIEWED UNDER A DIFFERENT PERMIT AND WAS SUBMITTED IN
 ERROR. THIS SHEET HAS BEEN VOIDED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-13 Cont ID  
Sent By shill Date 2017-12-13 Time 14:49 Rev Time 0.00
Received By shill Date 2017-12-13 Time 14:41 Sent To  
Notes
2017-12-13 14:49:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REGARDING ADDRESSES, SOME PAGES STILL HAVE THE
 NUMBERED UNIT DESIGNATIONS SO PLANS DO NOT CORRELATE
 AFTER SOME SHEETS WERE REVISED (A205, A202).
  
 2. SEE ELECTRICAL COMMENTS; IT APPEARS THAT TWO UNITS
 ARE BEING REVISED. A SEPARATE PERMIT IS REQUIRED FOR
 EACH PARCEL ID NUMBER.
  
 2ND REVIEW, NOT ADDRESSED. ARCHITECT'S LETTER REFERS TO
 MEP RESPONSE LETTER, MEP RESPONSE LETTER REFERS TO
 ARCHITECT.
  
 3. PROVIDE A DETAIL FOR THE PROPOSED NEW BENCH
 INCLUDING BACK SUPPORT, FBC A 903.
  
 2ND REVIEW, RESPONSE REFERS TO A 7 A202. THIS IS THE
 SERVICE COUNTER DETAIL.
  
 4. REAR EXIT DOORS, UNITS 106 AND 109, REVISE PLAN TO
 SHOW 18" MANEUVERING CLEARANCE ON THE PULL SIDE, FBC A
 FIGURE 404.2.4.1(A).
  
 2ND REVIEW, ADDRESSED FOR UNIT CU2, NOT FOR UNIT 109.
  
 5. OK
  
 6. A202, FBC A 904, REVISE PLAN TO INCLUDE A DETAIL FOR
 THE SERVICE COUNTER.
  
 2ND REVIEW, DETAIL 7 A202 APPEARS TO HAVE A SERVICE
 COUNTER AT 3'6", WORK AREA AT 2'6". THIS DOES NOT MEET
 REQUIREMENT FOR SERVICE COUNTER.
  
 2ND REVIEW NEW COMMENT:
  
 7. IT APPEARS THAT OLD SHEETS WERE REMOVED FROM THE
 SUBMITTAL. PLEASE NOTE THAT REMOVING OLD SHEETS DELAYS
 PLAN REVIEW TIME. THE PLUMBING SHEETS PASSED, ARE NO
 LONGER AVAILABLE FOR REFERENCE, SO A NEW REVIEW IS
 REQUIRED. PLEASE RETAIN ALL PAGES IN THE SUBMITTAL
 PACKAGE. OLD SHEETS SHOULD BE MARKED "VOID" OR "OLD
 SHEETS". THEY SHOULD NOT BE BOUND WITH THE NEW PAGES,
 BUT SUBMITTED AS A SEPARATE VOLUME. PLEASE CONTACT ME
 WHEN RESUBMITTING IF YOU NEED ASSISTANCE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By shill Date 2017-11-27 Time 08:44 Rev Time 0.00
Received By shill Date 2017-11-27 Time 08:17 Sent To I
Notes
2017-11-27 09:27:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, PLEASE RESOLVE ADDRESSING ISSUE. OUR SYSTEM
 HAS DIFFERENT UNIT NUMBERS THAN ON THE PLAN AND
 APPLICATION, WHICH ALS APPEAR TO DIFFER FROM PROPERTY
 APPRAISER. PLEASE CONTACT [email protected] TO RESOLVE.
  
 2. SEE ELECTRICAL COMMENTS; IT APPEARS THAT TWO UNITS
 ARE BEING REVISED. A SEPARATE PERMIT IS REQUIRED FOR
 EACH PARCEL ID NUMBER.
  
 3. PROVIDE A DETAIL FOR THE PROPOSED NEW BENCH
 INCLUDING BACK SUPPORT, FBC A 903.
  
 4. REAR EXIT DOORS, UNITS 106 AND 109, REVISE PLAN TO
 SHOW 18" MANEUVERING CLEARANCE ON THE PULL SIDE, FBC A
 FIGURE 404.2.4.1(A).
  
 5. A205, DOOR 109B, REVISE PLAN TO SHOW 18" MANEUVERING
 CLEARANCE ON THE PULL SIDE, FBC A FIGURE 404.2.4.1(A).
  
 6. A202, FBC A 904, REVISE PLAN TO INCLUDE A DETAIL FOR
 THE SERVICE COUNTER.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-19 Cont ID  
Sent By jpearson Date 2017-12-19 Time 15:25 Rev Time 0.00
Received By jpearson Date 2017-12-19 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By jpearson Date 2017-11-15 Time 09:52 Rev Time 0.00
Received By jpearson Date 2017-11-15 Time 09:52 Sent To  
Notes
2017-11-15 09:51:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E1.2, LIGHT IN STORAGE CLOSET SHOULD BE
 CONTROLLED AUTOMATICALLY. FBC CE 405.2.2
 2. SHEET E1.6 IS FOR UNIT 110, WHICH IS NOT INCLUDED
 WITH THIS PERMIT NUMBER. ADDITIONALLY, SHEET ER.1 SHOWS
 REVISIONS TO UNITS 107 AND 110, WHICH ARE NOT INCLUDED
 WITH THIS PERMIT NUMBER. REMOVE ALL REVISIONS UNDER
 SEPARATE PERMITS, WHICH SHOULD BE SUBMITTED SEPARATELY.
 FBC 107.2.1, 107.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By pleduc Date 2017-12-13 Time   Rev Time 0.00
Received By pleduc Date 2017-12-12 Time 12:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-07 Cont ID  
Sent By pleduc Date 2017-11-07 Time   Rev Time 0.00
Received By pleduc Date 2017-11-06 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-27 Cont ID  
Sent By gjohnson Date 2017-12-27 Time 13:26 Rev Time 0.00
Received By gjohnson Date 2017-12-07 Time 15:29 Sent To  
Notes
2017-12-11 15:29:19B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-27 Cont ID  
Sent By shill Date 2017-11-27 Time 09:49 Rev Time 0.00
Received By shill Date 2017-11-01 Time 14:56 Sent To  
Notes
2017-11-02 14:54:35B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-11-27 Cont ID  
Sent By shill Date 2017-11-27 Time 09:49 Rev Time 0.00
Received By shill Date 2017-11-27 Time 09:49 Sent To  
Notes
2017-11-27 09:49:50CONFIRMED ON PLAN (LS.1 DATED 11/13/06) THAT MEZZANINES
 WERE PERMITTED AS COMMERCIAL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-18 Cont ID  
Sent By ccole Date 2017-12-18 Time 07:44 Rev Time 0.00
Received By ccole Date 2017-12-15 Time 17:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-09 Cont ID  
Sent By ccole Date 2017-11-09 Time 15:45 Rev Time 0.00
Received By ccole Date 2017-11-09 Time 12:53 Sent To  
Notes
2017-11-09 16:06:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110040
 11/9/2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SEQUENCE OF OPERATION FOR EF-3- SEE
 SECTION 501.4
  
 2) SHOW THE LOCATION OF THE NEW DRYER AND SUBMIT A CUT
 SHEET. INDICATE GAS-FIRED OR ELECTRIC APPLIANCE,
 PROVIDE DRYER EXHAUST DUCT DETAILS AND SHOW THE DUCT
 RUN AND TERMINATION LOCATION. PLEASE NOTE THAT A GAS
 PIPING ISOMETRIC DRAWING AND COMBUSTION AIR
 CALCULATIONS ARE REQUIRED FOR A GAS DRYER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-27 Cont ID  
Sent By gjohnson Date 2017-12-27 Time 13:26 Rev Time 0.00
Received By gjohnson Date 2017-12-27 Time 13:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-16 Cont ID  
Sent By gjohnson Date 2017-11-16 Time 17:39 Rev Time 0.00
Received By gjohnson Date 2017-11-16 Time 14:07 Sent To  
Notes
***NONE***