Plan Review Details - Permit 17110021
Plan Review Stops For Permit 17110021
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 17:26 Rev Time 0.00
Received By shill Date 2018-06-16 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-27 Cont ID  
Sent By jwitmer Date 2018-02-27 Time 14:44 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 13:44 Sent To  
Notes
2018-02-27 14:43:062014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110021
 ADD: 3200 N. CONGRESS AVE.
 CONT: SOBEL CO.
 TEL: 954-410-9239
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. FEB.27/ 2018
  
 ACTION: BUILDING PROVISO
  
 1) ROOFING PRODUCT APPROVALS ARE TO BE SUBMITTED UNDER
 THE ROOFING SUB-PERMIT. 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 2) 2014 W. P. B. ADMINISTRATION 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By jwitmer Date 2017-12-05 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2017-12-05 Time 11:59 Sent To  
Notes
2017-12-05 16:18:272014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110021
 ADD: 3200 N. CONGRESS AVE.
 CONT: SOBEL CO.
 TEL: 954-410-9239
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. DEC. 05/ 2017
 ACTION: DENIED
  
 1) SHEET A-0.0.0.1:
  
 1A) PLEASE NOTE THE CITY CONVERTED FROM NGVD 29 TO NAVD
 88 AND THE NEW FEMA FLOOD MAPS ON OCT. 12/ 2017. IN
 DOING SO ALL ELEVATIONS SHOULD BE GIVEN IN NAVD 88.
 ELEVATIONS ON THIS PLAN ARE IN NAVD. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) SHEET A-0.0.0.1 UNDER THE HEADING BUILDING CODE
 DATA REFERENCES THE 2014 FBC-RESIDENTIAL CODE AND MAKES
 REFERENCE TO THE RESIDENTIAL CODE 28 TIMES. THIS
 STRUCTURE IS NOT A RESIDENTIAL DWELLING AND ALL
 REFERENCES TO THE CODE SHOULD BE TO THE 2014 FBC-B AND
 AN OCCUPANCY TYPE PROVIDED.
 2014 FBC-B SECTION 302.1. STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED IN THIS SECTION.
  
 1C) UNDER THE APPLICABLE CODES THE REFERENCE IS MADE TO
 THE FBC-RESIDENTIAL CODE, PLEASE CORRECT TO THE 2014
 FBC-B.
  
 1D) THE PLAN DOES NOT PROVIDE WHAT THE MINIMUM TYPE OF
 CONSTRUCTION THIS STRUCTURE WAS DESIGNED TOO, SEE 2014
 FBC-B TABLE 503 & TABLE 601.
  
 2) SHEET A1.3.04 FRONT ENTRY SIGNS, MONUMENT SIGNS ARE
 NOT PART OF THIS PERMIT AND WOULD REQUIRE A SEPARATE
 REVIEW AND ASSOCIATED FEES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.1 REQUIRED. ANY CONTRACTOR, OWNER,
 OR AGENT AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE
 489 WHO INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR,
 MOVE, DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING
 OR STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER,
 REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT RESISTANT
 COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR
 FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD
 RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS
 REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE
 DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT.
  
 3A) SHEET A-2.1.01 IS THE ELEVATIONS OF THE GUARD
 HOUSE. THERE IS A COVER SHEET LISTING THE PRODUCT
 APPROVALS TO BE USE FOR THIS STRUCTURE, I BELIEVE THIS
 IS A GENERIC COVER SHEET FOR THE PRODUCT APPROVALS
 SINCE THERE IS A AMARR GARAGE DOOR (NOA 13-0503.06) AND
 A FIXED WINDOW (NOA 14-0908.18) FIXED WINDOW THAT DO
 NOT APPEAR IN EITHER THE FLOOR PLAN OR ELEVATIONS.
 PLEASE UPDATE TO THE CURRENT COMPONENTS AND CLADDING
 FOR THE STRUCTURE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED, DISCREPANCY IN THE PROVIDED INFORMATION.
  
 3B) THE ELEVATIONS ON SHEET A-2.1.0.1 SHOW ROOF TILE
 BUT THEY DOES NOT INDICATE IF THE O?HAGINS CLOCKED VENT
 TILE, OFF RIDGE VENT IS TO BE INSTALLED ON THIS
 BUILDING? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4A) DISCREPANCY IN PLANS. SHEET A-2.1.01 AND A-6.1.01
 THE TOP OF THE WINDOW DOES NOT MATCH UP. SHEET A-2.1.01
 SECTION # 2 THE TOP OF THE WINDOW IS 7 FEET 6 INCHES
 OFF OF FINISH FLOOR, WHEREAS SHEET A-6.1.01 DETAIL W1
 THE TOP OF THE WINDOW ELEVATION IS 7FEET 10 ? INCHES.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 4B) PLEASE REVIEW SHEET S-2.00 THE L2 ROOF PLAN
 INDICATES THE USE OF A RBB-1 BEAM. THE TOP OF THE BEAM
 TO BE AT ELEVATION 10 FOOT 6 INCHES. THE BEAM SCHEDULE
 INDICATES THIS BEAM RBB-1 TO BE 1 FOOT 4 INCHES IN
 DEPTH, IN THE COMMENTS IT INDICATES A 16 INCH BOND BEAM
 NO STIRRUPS. OVER THE WINDOW AND DOOR OPENINGS AGAIN
 THE BEAM DESIGNATION OF RBB-1 NO STIRRUPS? IT WOULD
 APPEAR THIS IS A MISTAKE? IT ALSO APPEARS THERE IS A
 NEED OF A LINTEL TO FILE IN THE APPROXIMATE 14 INCH
 VERTICAL GAP? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED? LINTEL SCHEDULE FOUND ON S1.00 BUT NO MENTION
 OF LINTELS ON SHEET S-2.00.
  
 4C) SHEET S-2.00 CMU WALL SCHEDULE MARK MW-1 INDICATES
 THE VERTICAL STEEL EVERY 4 FEET ON CENTER, THE SCHEDULE
 NOR THE DETAIL INDICATE IF CORNER CELLS ARE TO BE FILED
 OR MASONRY CELLS NEXT TO WALL OPENINGS REQUIRE VERTICAL
 REINFORCEMENT AND CELLS FILED? STEEL REINFORCEMENT
 CONFORMING TO ACI 318.
  
 4D) L1 THE GROUND FLOOR PLAN SHOWS TO COLUMNS C1 TO BE
 A 18 X 18 INCH COLUMN AND THE FOUNDATION SCHEDULE
 INDICATES THE MARK AS TE-1 AND THE WIDTH OF THE
 FOUNDATION IS ONLY 16 INCHES WIDE? THE COLUMN IS WIDER
 THAN THE FOUNDATION. 1901.2 REINFORCED CONCRETE.
 STRUCTURAL CONCRETE SHALL BE DESIGNED AND CONSTRUCTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF THIS CHAPTER AND
 ACI 318.
  
 SHEET S-2.00 THE COMPONENTS AND CLADDING PRESSURES ARE
 IN VULT, PLEASE CONVERT TO VASD SINCE ALL OF THE
 PRODUCT APPROVALS ARE IN VASD. 2014 FBC-B 1609.3.1 WIND
 SPEED CONVERSION VULT TO VASD.
  
 5) SHEET A-2.1.01 AND A-6.1.01 BOTH INDICATE THE USE OF
 A LOUVERED SHUTTER BUT NO PRODUCT APPROVAL HAS BEEN
 SUBMITTED. THE PLANS DO NOT STATE IF THIS LOUVER HAS TO
 BE LOWERED IN HIGH WIND EVENTS AND IF THE SHUTTER/
 LOUVER WAS TESTED IN THE OPEN POSITION?
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (C) WALL LOUVERS
 (E) SHUTTERS
  
 6) THE SUBMITTED ROOFING APPROVAL ENTEGRA PLANTATION
 ROOF TILE, MIAMI-DADE NOA 15-0721.04 NEITHER THE
 CONTRACTOR NOR THE DESIGNER OF RECORD HAS INDICATED THE
 TYPE OF FASTENING SYSTEM FOR THIS PRODUCT, TO RESIST
 THE MOMENT OF OVERTURNING, IF NAIL, SCREW, OR FOAM. IF
 FOAM IS TO BE USED PLEASE ALSO SUPPLY THE PRODUCT
 APPROVAL FOR THE UNDERLAYMENT AND FOR THE FOAM.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-28 Cont ID  
Sent By jpearson Date 2018-02-28 Time 09:06 Rev Time 0.00
Received By jpearson Date 2018-02-28 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By jpearson Date 2017-12-06 Time 13:36 Rev Time 0.00
Received By jpearson Date 2017-12-06 Time 10:55 Sent To  
Notes
2017-12-06 13:36:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANEL IS ADEQUATE. NEC
 110.9, 110.10
 2. FEED FROM METER CAN TO INTERIOR PANEL IS NOT
 PERMITTED TO EXTEND FURTHER THAN 8 FEET (TOTAL
 CONDUCTOR LENGTH) FROM THE METER CAN WITHOUT A MEANS OF
 DISCONNECT. PROVIDE CORRECTION. NEC 230.70
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. PLAN DOES NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2018-02-23 Cont ID  
Sent By M Date 2018-02-23 Time   Rev Time 1.00
Received By mgonzale Date 2018-02-23 Time   Sent To I
Notes
2018-02-23 17:41:46DEVELOPMENT REVIEW THRU ENGINEERING DEPT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By shill Date 2017-12-13 Time 10:08 Rev Time 0.00
Received By shill Date 2017-12-13 Time 10:08 Sent To  
Notes
2017-12-13 10:08:31SUBMIT PERMIT APPLICATION DIRECTLY TO THE ENGINEERING
 DEPARTMENT
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 CONTACT ENGINEERING FOR MORE INFORMATION
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By pleduc Date 2018-02-26 Time   Rev Time 0.00
Received By pleduc Date 2018-02-26 Time 12:30 Sent To  
Notes
2018-02-26 16:53:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROVIDE ONE 10LB ABC FIRE EXTINGUISHERS MOUNTED PER
 NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013
 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-06 Cont ID  
Sent By pleduc Date 2017-11-06 Time   Rev Time 0.00
Received By pleduc Date 2017-11-06 Time 12:29 Sent To  
Notes
2017-11-06 13:44:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROVIDE ONE 10LB ABC FIRE EXTINGUISHERS MOUNTED PER
 NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013
 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-06-29 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-26 Time 15:46 Sent To  
Notes
2018-06-27 15:46:18RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-25 Cont ID  
Sent By cpuell Date 2018-06-25 Time 10:27 Rev Time 0.00
Received By cpuell Date 2018-05-23 Time 13:34 Sent To  
Notes
2018-05-24 13:35:06C20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-12 Cont ID  
Sent By cpuell Date 2018-03-12 Time 15:57 Rev Time 0.00
Received By cpuell Date 2018-01-31 Time 09:47 Sent To  
Notes
2018-02-02 09:47:12C26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-08 Cont ID  
Sent By cpuell Date 2018-01-08 Time 15:05 Rev Time 0.00
Received By cpuell Date 2017-11-01 Time 15:39 Sent To  
Notes
2017-11-02 15:39:45C24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-02-27 Cont ID  
Sent By jwitmer Date 2018-02-27 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 13:45 Sent To  
Notes
2018-02-27 14:28:27PALM BEACH COUNTY IMPACT FEE OFFICE
 3200 N. CONGRESS/ GUARD HOUSE/ NEW CONSTRUCTION
 RECEIPT NO.: 2018-0123-156
 TRACKING NO.: MU-2018-001666-0000
 FEES PAID: $1,941.52
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By jwitmer Date 2017-12-05 Time 16:17 Rev Time 0.00
Received By jwitmer Date 2017-12-05 Time 11:59 Sent To  
Notes
2017-12-05 16:17:35IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-06-29 Cont ID  
Sent By ccole Date 2018-06-29 Time 12:04 Rev Time 0.00
Received By ccole Date 2018-06-29 Time 12:04 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-06-11 Cont ID  
Sent By ccole Date 2018-06-11 Time 17:13 Rev Time 0.00
Received By ccole Date 2018-06-11 Time 17:01 Sent To  
Notes
2018-06-11 17:30:563RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110021
 6/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGY FORM C402-2014 IS FOR
 ALTERATIONS, RENOVATED BUILDINGS, OR BUILDING SYSTEMS.
 THE PROPOSED PROJECT IS A NEW BUILDING SO THE
 ENERGYGAUGE OR COMCHECK SOFTWARE MUST BE USED TO SHOW
 COMPLIANCE FOR A NEW FINISHED BUILDING- SECTION
 C101.5.1 FBC-14 ENERGY CONSERVATION.
  
 2) SHEET M1: THE O/A SCHEDULE INDICATES MECHANICAL
 VENTILATION FOR THE BUILDING HOWEVER NO OUTDOOR AIR HAS
 BEEN PROVIDED MECHANICALLY. IF THE INTENTION IS TO USE
 NATURAL VENTILATION PLEASE SEE SECTION 402 AND PROVIDE
 A CALCULATION USING THE OPERABLE OPENINGS.
  
 3) ELECTRONIC SIGNATURES ARE NOT ACCEPTABLE FOR USE ON
 HARD COPY PAPER PLANS- SECTION 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE. AS PREVIOUSLY REQUESTED THE
 CONTRACTOR OF RECORD SHALL PROVIDE HIS "SIGNATURE" (NOT
 AN ENGINEER'S SEAL AND SIGNATURE) ON THE PLANS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
  
 RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC-14.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 13:53 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 13:53 Sent To  
Notes
2018-02-28 13:59:022ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110021
 11/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PREVIOUS (1ST) REVIEW COMMENTS HAVE NOT BEEN
 ADDRESSED- SEE BELOW.
  
  
 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110021
 11/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE
 CARRIER HP SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION, SECTION 312.1 FBC-14 MECHANICAL.
  
 2) PROVIDE ENERGY CALCULATIONS- SECTIONS C101, C101.5,
 AND C401.2 FBC-14 ENERGY CONSERVATION.
  
 3) M1: SIGNATURE ON THE PLAN REQUIRED. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE
 FBC-14.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By ccole Date 2017-11-29 Time 10:28 Rev Time 0.00
Received By ccole Date 2017-11-29 Time 10:27 Sent To  
Notes
2017-11-29 10:38:531ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110021
 11/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE
 CARRIER HP SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION, SECTION 312.1 FBC-14 MECHANICAL.
  
 2) PROVIDE ENERGY CALCULATIONS- SECTIONS C101, C101.5,
 AND C401.2 FBC-14 ENERGY CONSERVATION.
  
 3) M1: SIGNATURE ON THE PLAN REQUIRED. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE
 FBC-14.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-02-28 Cont ID  
Sent By gjohnson Date 2018-02-28 Time 07:48 Rev Time 0.00
Received By gjohnson Date 2018-02-28 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 18:21 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 18:14 Sent To  
Notes
2017-11-29 18:33:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC:
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 606 LAVATORIES AND SINKS
  
 606.1 GENERAL.
 LAVATORIES AND SINKS SHALL COMPLY WITH 606.
  
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2. A CLEAN OUT IS REQUIRED AT THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER WHICH IS 30" OUT
 FROM BUILDING 15' DOES NOT COMPLY WITH THE REQUIREMENT
 PLEASE CLARIFY. PER FBC PL 708.3.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-02-27 Cont ID  
Sent By jwitmer Date 2018-02-27 Time 14:44 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 14:43 Sent To  
Notes
2018-02-27 14:44:412014 FBC- BUILDING PLAN REVIEW (ROOFING)
 W. P. B. PERMIT: 17110021
 ADD: 3200 N. CONGRESS AVE.
 CONT: SOBEL CO.
 TEL: 954-410-9239
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. FEB.27/ 2018
  
 ACTION: BUILDING PROVISO
  
 1) ROOFING PRODUCT APPROVALS ARE TO BE SUBMITTED UNDER
 THE ROOFING SUB-PERMIT. 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 2) 2014 W. P. B. ADMINISTRATION 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-22 Cont ID  
Sent By jroach Date 2018-06-22 Time 15:23 Rev Time 0.00
Received By jroach Date 2018-06-22 Time 15:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-03-12 Cont ID  
Sent By jroach Date 2018-03-12 Time 13:33 Rev Time 0.00
Received By jroach Date 2018-03-12 Time 13:33 Sent To  
Notes
2018-03-12 13:36:09ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.08.2018
 PERMIT NO.: 17110021
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A FORMAL
 SITE PLAN REVIEW APPLICATION SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION. THE SITE PLAN REVIEW APPLICATION
 SHALL INCLUDE A FINAL SITE PLAN AND LANDSCAPE PLANS FOR
 THE ENTIRE ENTRANCEWAY. ALL ZONING COMMENTS WILL BE
 MADE DURING THE SITE PLAN REVIEW PROCESS.
  
 2. PLEASE CLARIFY WHERE THE ATTENDANT OF THE GUARDHOUSE
 WILL PARK.
  
 3. PLANS WERE INCLUDED IN THE PACKAGE PERTAINING TO THE
 MODEL DWELLINGS...PLEASE REMOVE SUCH SHEETS AS THEY ARE
 TO BE COVERED UNDER SEPARATE PERMIT.
  
 4. PLANS WERE INCLUDED IN THE PACKAGE PERTAINING TO AN
 ENTRANCE SIGN...PLEASE REMOVE SUCH SHEETS AS THEY ARE
 TO BE COVERED UNDER SEPARATE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By JR Date 2018-01-08 Time 14:51 Rev Time 0.00
Received By jroach Date 2017-11-06 Time 16:08 Sent To  
Notes
2018-01-08 14:53:17ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.08.2018
 PERMIT NO.: 17110021
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A FORMAL
 SITE PLAN REVIEW APPLICATION SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION. THE SITE PLAN REVIEW APPLICATION
 SHALL INCLUDE A FINAL SITE PLAN AND LANDSCAPE PLANS FOR
 THE ENTIRE ENTRANCEWAY. ALL ZONING COMMENTS WILL BE
 MADE DURING THE SITE PLAN REVIEW PROCESS.
  
 2. PLEASE CLARIFY WHERE THE ATTENDANT OF THE GUARDHOUSE
 WILL PARK.
  
 3. PLANS WERE INCLUDED IN THE PACKAGE PERTAINING TO THE
 MODEL DWELLINGS...PLEASE REMOVE SUCH SHEETS AS THEY ARE
 TO BE COVERED UNDER SEPARATE PERMIT.
  
 4. PLANS WERE INCLUDED IN THE PACKAGE PERTAINING TO AN
 ENTRANCE SIGN...PLEASE REMOVE SUCH SHEETS AS THEY ARE
 TO BE COVERED UNDER SEPARATE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved