Plan Review Details - Permit 17101280
Plan Review Stops For Permit 17101280
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-06 Cont ID  
Sent By rmcdouga Date 2017-12-06 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2017-12-06 Time 07:03 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-08 Cont ID  
Sent By rmcdouga Date 2017-11-08 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2017-11-08 Time 06:47 Sent To I
Notes
2017-11-08 07:38:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING TO THE TABLES ON SHEET 2, THE ALLOWABLE
 SPAN FOR THE 2 X 7 MANSARD ROOF BEAMS IS 9'-0". THE
 ROOF FRAMING PLAN SHOWS THE 2 X 7 ARE SPANING 10'-0".
 PLEASE CORRECT. FBC-R301.1
  
 2) PLEASE ADVISE THE ENGINEER, MYONGHO KIM P.E. #62565,
 THAT THE "SPECIAL QUALIFICATIONS" DESIGNATION THAT IS
 REQUIRED PURSUANT TO FLORIDA STATUTE 471.0195 IS NOT
 SHOWN ON THE DBPR LICENSE WEBSITE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-06 Cont ID  
Sent By rmcdouga Date 2017-12-06 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2017-12-04 Time 14:46 Sent To  
Notes
2017-12-05 14:46:45RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-08 Cont ID  
Sent By rmcdouga Date 2017-11-08 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2017-10-31 Time 11:29 Sent To  
Notes
2017-11-01 11:29:28ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-07 Cont ID  
Sent By AW Date 2017-11-07 Time   Rev Time 0.00
Received By ajones Date 2017-11-01 Time 15:15 Sent To B
Notes
***NONE***