Plan Review Details - Permit 17101264
Plan Review Stops For Permit 17101264
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-15 Cont ID  
Sent By aclange Date 2018-03-15 Time 08:42 Rev Time 0.00
Received By aclange Date 2018-03-15 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-20 Cont ID  
Sent By shill Date 2017-11-20 Time 10:37 Rev Time 0.00
Received By aclange Date 2017-11-20 Time 09:04 Sent To  
Notes
2017-11-20 10:39:59****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. ALL ELEVATIONS SUBMITTED ARE SHOWN AS "EAST
 ELEVATIONS". PLEASE UPDATE AS NEEDED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2. SEE BEAM/COLUMN INSPECTION FROM 8/8/17. EXTERIOR
 WALLS, BEAMS AND COLUMNS SHOWN AS EXISTING HAVE BEEN
 REMOVED AND REPLACED. PLEASE PROVIDE A REVISION TO
 INCLUDE THE EXTERIOR WALLS AS NEED. REVISE PERMIT VALUE
 TO INCLUDE THIS AND ANY OTHER NEW WORK THAT WAS NOT
 INCLUDED AS PART OF THE ORIGINAL PERMIT.
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3. NOTE: SIGNS SHALL BE UNDER A SEPARATE PERMIT.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By jleahy Date 2017-11-14 Time 17:54 Rev Time 0.00
Received By jleahy Date 2017-11-14 Time 17:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-15 Cont ID  
Sent By aclange Date 2018-03-15 Time 08:43 Rev Time 0.00
Received By aclange Date 2018-02-21 Time 15:04 Sent To  
Notes
2018-02-22 15:04:59RESUB ROUTED TO AJONES VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-13 Cont ID  
Sent By gjohnson Date 2017-11-22 Time 06:28 Rev Time 0.00
Received By shill Date 2017-10-31 Time 09:58 Sent To  
Notes
2017-11-02 09:58:59C07

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By ccole Date 2017-11-14 Time 16:28 Rev Time 0.00
Received By ccole Date 2017-11-14 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-21 Cont ID  
Sent By tklarge Date 2017-11-21 Time 15:53 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 15:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-14 Cont ID  
Sent By ajones Date 2018-03-14 Time 12:00 Rev Time 0.00
Received By ajones Date 2018-03-14 Time 12:00 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By ajones Date 2017-12-06 Time 11:26 Rev Time 0.00
Received By ajones Date 2017-11-06 Time 16:00 Sent To  
Notes
2017-12-06 11:28:23SEE BUILDING COMMENTS ABOUT EXISTING WALLS/COUIMNS BE
 REMOVED.
  
 ANGELLA VANN
 561-822-1441
 [email protected]