Plan Review Details - Permit 17101256
Plan Review Stops For Permit 17101256
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-06 Cont ID  
Sent By shill Date 2017-11-06 Time 11:36 Rev Time 0.00
Received By shill Date 2017-11-06 Time 11:36 Sent To  
Notes
2017-11-06 11:38:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE THE CORRECT VALUE FOR PROPOSED WORK,
 INCLUDING ALL TRADES.
  
 2. PROVIDE AN APPLICATION WHICH REFLECTS CORRECT SCOPE
 OF WORK (RENOVAT EXISTING MEDICAL OFFICE TO REMOVE
 INTERIOR PARTITION WALLS AND BATHROOM).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By shill Date 2017-11-02 Time 06:26 Rev Time 0.00
Received By shill Date 2017-11-02 Time 06:26 Sent To E
Notes
2017-11-02 06:37:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, I WAS UNABLE TO LOCATE AN INTERIOR
 RENOVATION PERMIT ASSOCIATED WITH THIS ADDRESS. IS
 INTERIOR DEMO ASSOCIATED WITH A PENDING PERMIT
 APPLICATION PROPOSED? IF YES, WHEN WILL THAT
 APPLICATION BE SUBMITTED? IF ASSOCIATED WITH AN
 INTERIOR ALTERATION PERMIT APPLICATION, PROVIDE THE
 PERMIT APPLICATION NUMBER.
  
 IF NO ALTERATION IS PROPOSED, PROVIDE PLANS TO SHOW
 COMPLETE SCOPE OF WORK INCLUDING HOW FBC / FFPC
 REQUIREMENTS ARE AFFECTED. ONLY A VERY SMALL FLOOR PLAN
 WITH NO DIMENSIONS WITH A FEW WALLS HIGHLIGHTED
 (INCLUDING BATHROOM WALLS) WAS PROVIDED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By jpearson Date 2017-11-17 Time 13:12 Rev Time 0.00
Received By jpearson Date 2017-11-17 Time 13:12 Sent To  
Notes
2017-11-17 13:12:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. INDICATE ANY
 ELECTRICAL WORK BEING DELETED. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By pleduc Date 2017-11-07 Time   Rev Time 0.00
Received By pleduc Date 2017-11-07 Time 12:14 Sent To  
Notes
2017-11-07 15:10:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDE TO COMPLETE A
 THOROUGH LIFE SAFETY PALN REVIEW.
  
  
 2) THERE IS NO ADDRESS AND BUSINESS NAME ON THE TITLE
 BLOCK OF THE SUBMITTED SHEETS.
  
 PLEASE PROVIDE
  
  
 3) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS
 A COMPLETE FIRE SPRINKLER SYSTEM.
  
 ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE
 FIRE SPRINKLER SYSTEM PROTECTION REVIEWED FOR CODE
 COMPLIANCE AND SHOP DRAWINGS SUBMITTAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP
 DRAWINGS.
  
  
 4) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS
 A FIRE ALARM SYSTEM.
  
 ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE
 FIRE ALARMSYSTEM PROTECTION REVIEWED FOR CODE
 COMPLIANCE AND SHOP DRAWINGS SUBMITTAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP
 DRAWINGS.
  
  
 5) ANY PROPOSED WORK AFTER THE REMOVAL OF WALLS SHALL
 REQUIRE A NEW PERMIT.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2017-11-06 Time 11:36 Sent To  
Notes
2017-11-06 11:40:04B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-02 Cont ID  
Sent By shill Date 2017-11-02 Time 06:38 Rev Time 0.00
Received By shill Date 2017-10-31 Time 15:44 Sent To  
Notes
2017-11-01 15:45:03ROUTED TO SHILL

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 16:53 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 15:29 Sent To  
Notes
2017-11-21 16:54:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SCOPE OF PLUMBING WORK . PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  