Plan Review Details - Permit 17101256
| Plan Review Stops For Permit 17101256 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-06 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-06 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2017-11-06 11:38:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. PROVIDE THE CORRECT VALUE FOR PROPOSED WORK, | | | INCLUDING ALL TRADES. | | | | | | 2. PROVIDE AN APPLICATION WHICH REFLECTS CORRECT SCOPE | | | OF WORK (RENOVAT EXISTING MEDICAL OFFICE TO REMOVE | | | INTERIOR PARTITION WALLS AND BATHROOM). | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-02 |
Time |
06:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-02 |
Time |
06:26 |
Sent To |
E |
|
| Notes |
| 2017-11-02 06:37:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC 107, I WAS UNABLE TO LOCATE AN INTERIOR | | | RENOVATION PERMIT ASSOCIATED WITH THIS ADDRESS. IS | | | INTERIOR DEMO ASSOCIATED WITH A PENDING PERMIT | | | APPLICATION PROPOSED? IF YES, WHEN WILL THAT | | | APPLICATION BE SUBMITTED? IF ASSOCIATED WITH AN | | | INTERIOR ALTERATION PERMIT APPLICATION, PROVIDE THE | | | PERMIT APPLICATION NUMBER. | | | | | | IF NO ALTERATION IS PROPOSED, PROVIDE PLANS TO SHOW | | | COMPLETE SCOPE OF WORK INCLUDING HOW FBC / FFPC | | | REQUIREMENTS ARE AFFECTED. ONLY A VERY SMALL FLOOR PLAN | | | WITH NO DIMENSIONS WITH A FEW WALLS HIGHLIGHTED | | | (INCLUDING BATHROOM WALLS) WAS PROVIDED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-11-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-17 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-17 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2017-11-17 13:12:10 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. INDICATE ANY | | | ELECTRICAL WORK BEING DELETED. FS 471.003(2)(H); | | | 471.025; FBC 107.2.1, 107.3.5 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-07 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2017-11-07 15:10:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS INSUFFICIENT DETAIL PROVIDE TO COMPLETE A | | | THOROUGH LIFE SAFETY PALN REVIEW. | | | | | | | | | 2) THERE IS NO ADDRESS AND BUSINESS NAME ON THE TITLE | | | BLOCK OF THE SUBMITTED SHEETS. | | | | | | PLEASE PROVIDE | | | | | | | | | 3) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS | | | A COMPLETE FIRE SPRINKLER SYSTEM. | | | | | | ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE | | | FIRE SPRINKLER SYSTEM PROTECTION REVIEWED FOR CODE | | | COMPLIANCE AND SHOP DRAWINGS SUBMITTAL. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP | | | DRAWINGS. | | | | | | | | | 4) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS | | | A FIRE ALARM SYSTEM. | | | | | | ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE | | | FIRE ALARMSYSTEM PROTECTION REVIEWED FOR CODE | | | COMPLIANCE AND SHOP DRAWINGS SUBMITTAL. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP | | | DRAWINGS. | | | | | | | | | 5) ANY PROPOSED WORK AFTER THE REMOVAL OF WALLS SHALL | | | REQUIRE A NEW PERMIT. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-21 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-06 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-02 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-31 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2017-11-01 15:45:03 | ROUTED TO SHILL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-21 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-21 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2017-11-21 16:54:44 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE SCOPE OF PLUMBING WORK . PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
|