| 2017-11-06 13:33:14 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17101215 |
| | ADD: 1020 11TH. ST. |
| | CONT: T. B. D. / TO BE DETERMINED |
| | TEL: 561-822-1437 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 06/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A0.0 LIST THE BUILDING CONSTRUCTION |
| | TYPE AND INDICATES THE AMERICAN LEGION MEETS THERE, AND |
| | THE BUILDING IS OWNED BY THE CITY OF WEST PALM BEACH |
| | (TITLE II). WHAT THE DESIGNER OF RECORD HAS NOT |
| | DECLARED IS THE OCCUPANCY, THIS MAY BE A MIXED USE |
| | BUILDING DEPENDING ON THE FUNCTION OF THE BUILDING, A |
| | BANQUET HALL WITH TABLE AND CHAIRS, USED FOR MEETINGS |
| | WITH CHAIRS ONLY AND OR AS A DANCE HALL OR EVENT HALL |
| | WITH A MIXTURE OF ALL THREE. PLEASE PROVIDE AN |
| | OCCUPANCY TYPE. |
| | |
| | 2014 FBC-B SECTION 302.1. STRUCTURES OR PORTIONS OF |
| | STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO |
| | OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED IN THIS |
| | SECTION. A ROOM OR SPACE THAT IS INTENDED TO BE |
| | OCCUPIED AT DIFFERENT TIMES FOR DIFFERENT PURPOSES |
| | SHALL COMPLY WITH ALL OF THE REQUIREMENTS THAT ARE |
| | APPLICABLE TO EACH OF THE PURPOSES FOR WHICH THE ROOM |
| | OR SPACE WILL BE OCCUPIED. STRUCTURES WITH MULTIPLE |
| | OCCUPANCIES OR USES SHALL COMPLY WITH SECTION 508. |
| | |
| | 2) SHEET A2.0 PROVIDES A TABLE LISTING THE SQUARE FOOT |
| | AREA OF THE ROOMS BUT DOES NOT PROVIDE THE OCCUPANT |
| | LOAD FOR THE ROOMS AND OVERALL TOTAL OCCUPANT LOAD. |
| | OCCUPANT LOADS TO BE USED IN : |
| | |
| | TABLE 1004.1.2 OF THE 2014 FBC-B. A ROOM OR SPACE THAT |
| | IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR |
| | DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE |
| | REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE |
| | PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED |
| | THE MOST RESTRICTIVE WOULD APPLY. |
| | |
| | 2014 FBC-B 201, FLOOR AREA, NET. THE ACTUAL OCCUPIED |
| | AREA NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS |
| | CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS |
| | AND CLOSETS. |
| | |
| | FLOOR AREA, GROSS. THE FLOOR AREA WITHIN THE INSIDE |
| | PERIMETER OF THE EXTERIOR WALLS OF THE BUILDING UNDER |
| | CONSIDERATION, EXCLUSIVE OF VENT SHAFTS AND COURTS, |
| | WITHOUT DEDUCTION FOR CORRIDORS, STAIRWAYS, CLOSETS, |
| | THE THICKNESS OF INTERIOR WALLS, COLUMNS OR OTHER |
| | FEATURES. THE FLOOR AREA OF A BUILDING, OR PORTION |
| | THEREOF, NOT PROVIDED WITH SURROUNDING EXTERIOR WALLS |
| | SHALL BE THE USABLE AREA UNDER THE HORIZONTAL |
| | PROJECTION OF THE ROOF OR FLOOR ABOVE. THE GROSS FLOOR |
| | AREA SHALL NOT INCLUDE SHAFTS WITH NO OPENINGS OR |
| | INTERIOR COURTS. |
| | |
| | 3) SHEET A2.0 SHOWS PROPOSED WORK IN BOTH THE MENS & |
| | WOMENS RESTROOMS. THE COVERSHEET INDICATES A LEVEL 2 |
| | ALTERATION. 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. ALSO UNDER THE |
| | LEVEL II ALTERATIONS OF THE 2014 EXISTING BUILDING CODE |
| | SECTION 806.1 A BUILDING, FACILITY, OR ELEMENT THAT HAS |
| | IS ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE |
| | FLORIDA BUILDING CODE, ACCESSIBILITY. PLEASE NOTE THE |
| | NEW LAYOUT OF BOTH THE MENS AND WOMENS RESTROOMS DOES |
| | NOT COMPLY WITH THE ACCESSIBILITY CODE 604.3.1 SIZE, |
| | 604.3.2 OVERLAP NOR 604.8.1.6. |
| | |
| | 4) SHEET A2.1 DETAILS IN BOTH THE MENS AND WOMENS |
| | RESTROOMS THE MIRRORS ARE SHOWN ABOVE THE MAXIMUM |
| | HEIGHT OF 40 INCHES TO THE BOTTOM EDGE OF THE |
| | REFLECTIVE MIRROR SURFACE. ACCESS. CODE 603.3. |
| | |
| | 5) WHEN THE OCCUPANCY CLASSIFICATION IS GIVEN AND THE |
| | OCCUPANT LOAD IS KNOWN PLEASE REVIEW SECTION 810.1 OF |
| | THE EXISTING BUILDING CODE TO SEE IF THE FIXTURE COUNT |
| | HAS BEEN MET. |
| | |
| | 6) SHEET A2.0 ALSO SHOWS WORK AT THE BAR AREA. SHEET |
| | A2.2 DETAIL # 10 SHOWS THE BAR TOP AT A HEIGHT OF 3?-6? |
| | OR 42 INCHES TALL. PLEASE SHOW A PORTION OF THE BAR |
| | MEETING THE ACCESSIBILITY CODE 226.1 WHERE DINING |
| | SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| | DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| | STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. 902.1 .DINING SURFACES AND WORK SURFACES |
| | SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 |
| | GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED |
| | TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7) SHEET A2.2 SHOWS A NEW EXHAUST HOOD. HOOD AND |
| | SUPPRESSION ARE REVIEWED UNDER SEPARATE PERMITS. |
| | 2801.1 SCOPE. |
| | MECHANICAL APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE |
| | CONSTRUCTED, INSTALLED AND MAINTAINED IN ACCORDANCE |
| | WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE |
| | FLORIDA BUILDING CODE, FUEL GAS. |
| | |
| | 8) SHEET S1.0 THE DESIGN PRESSURES FOR THE COMPONENTS |
| | AND CLADDING ARE LOW AND THE SAME FOR 10SQ. FT. 20 SQ. |
| | FT. AND 30 SQ. FT. 2014 FBC-B TABLE 1609.6.2. & TABLE |
| | R301.2(2). UNTIL THE PRESSURES ARE CORRECTED THE |
| | PRODUCT APPROVALS CANNOT BE EVALUATED. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |