Plan Review Details - Permit 17101193
Plan Review Stops For Permit 17101193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 18:42 Rev Time 0.00
Received By rmcdouga Date 2018-07-30 Time 14:09 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-03-16 Time   Rev Time 0.00
Received By jwitmer Date 2018-03-16 Time 08:54 Sent To  
Notes
2018-03-16 12:25:342014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101193
 ADD: 325 S. LAKESIDE CT. / 3 FLOORS OF RENOVATION
 CONT: BEACON CONSTRUCTION GROUP
 TEL: 561-845-5130
 E-MAIL: ROGER@BEACONCONSTRUCTION GROUP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: FRI. MARCH 16/ 2018
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SEMI-COMPLIED. WITH THE EXCEPTION OF THE STUDIO
 APARTMENT ALL OF THE OTHER NEW SHOWER COMPARTMENTS ARE
 IN THE TENANT SEPARATION WALL WITH ANOTHER R-2 UNIT ON
 THE OTHER SIDE OF THE WALL. PLEASE SHOW HOW COMPLIANCE
 WITH:
  
 2014 FBC-B SECTION 420.2 IS ACHIEVED AS WELL AS 2509.2.
 FOR SECTION 2509.2 SEE 1ST ROUND OF COMMENTS.
  
 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS
 IN THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND WALLS SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 708.
  
 FBC-B SECTION 708.3 FIRE-RESISTANCE RATING. FIRE
 PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR.
  
 THE PRESCRIPTIVE METHOD FOR FIRE RESISTANCE SHOULD
 QUOTE THE SECTION FOR EXAMPLE INTERIOR WALL PER
 721.1(2) 14-1.2. THIS WOULD BE GOOD FOR THE ? DRYWALL
 BUT ALSO PROVIDE A WALL DETAIL FOR THE CEMENT BACKER
 BOARD AS WELL. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1ST ROUND OF COMMENTS. SHEET A-1 UNDER THE SCOPE OF
 WORK, COMMENT # 9 INDICATES THE REMOVAL AND REPLACEMENT
 OF TUB. THE PLANS DOES NOT INDICATE THE TUB SURROUND TO
 BE REWORKED BUT THE REMOVAL OF THE TUB, THEY USUALLY
 NEED REPLACEMENT. IF SO THEY WILL NEED TO COMPLY WITH
 2014 FBC-B SECTION;
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS.
  
 4) 2ND REQUEST. PLEASE NOTE THE PLANS INDICATE THE
 INSTALLATION OF SUPER SAM 125. PLEASE SUPPLY THE ACTUAL
 TEST REPORTS WHERE SUPER SAM 125 HAS BEEN TESTED ON
 WOOD FLOOR JOIST AND WITH THE CONFIGURATION OF ONE ?
 INCH TONGUE AND GROOVE PLYWOOD DECKING. THE PLANS ALSO
 ONLY SHOW ONLY 1 LAYER OF ? INCH DRYWALL ON THE
 CEILING. WE WILL NEED TO SEE TEST REPORTS FOR BOTH THE
 STRUCTURE-BORNE SOUND TESTED IN ACCORDANCE WITH ASTM E
 492 AND AIR-BORNE SOUND TESTED IN ACCORDANCE WITH ASTM
 E 90.
 THE SUPER SAM 125 FLAME SPREAD TEST IS ACCEPTABLE.
  
 1ST ROUND OF COMMENTS. SHEET A-1 UNDER THE SCOPE OF
 WORK, COMMENT # 7 INDICATES THE INSTALLATION OF TILE
 OVER EXISTING WOOD FLOORING. NOTE FOR THE 2ND AND 3RD
 FLOOR UNITS WILL NEED TO PROVIDE SOUND UNDERLAYMENT
 BEFORE THE TILE IS INSTALLED. FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS. PLEASE PROVIDE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) SHEET A-2. NEW COMMENT HAS TO DEAL WITH THE FLOOR/
 CEILING ASSEMBLY ON THE 2ND AND 3RD FLOORS. THE PLAN
 DOES NOT CALL OUT ANY UL ASSEMBLY OR GYPSUM FLOOR
 CEILING ASSEMBLY. USING THE 2014 FBC-B UNDER THE
 PRESCRIPTIVE FIRE RESISTANCE METHOD AND TABLE
 721.1(3)13-1.4 WITH A DOUBLE WOOD FLOOR SYSTEM, JOIST
 AT 16 INCHES ON CENTER WITH ? INCH TYPE X DRYWALL.
  
 2014 FBC-B SECTION 420 GROUP R-1, R-2, R-3 & I-1.
 ? 420.3 HORIZONTAL SEPARATION.
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
  
 FBC-B 711.3 FIRE-RESISTANCE RATING. HORIZONTAL
 ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDING AND HORIZONTAL ASSEMBLIES SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING SHALL BE A MINIMUM OF 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION. EXCEPTION: DWELLING
 UNIT AND SLEEPING UNIT SEPARATIONS IN BUILDINGS OF TYPE
 IIB, IIIB AND VB CONSTRUCTION SHALL HAVE
 FIRE-RESISTANCE RATINGS OF NOT LESS THAN 1/2 HOUR IN
 BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1.
  
 6) SHEET A-2. NEW COMMENT. SEE DETAIL #2 INDICATES A
 DROPPED SOFFIT BUT THERE IS NO FIRE RATING AT THE FLOOR
 / CEILING ASSEMBLY. 718.2 FIREBLOCKING. IN COMBUSTIBLE
 CONSTRUCTION, FIREBLOCKING SHALL BE INSTALLED TO CUT
 OFF CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND
 HORIZONTAL) AND SHALL FORM AN EFFECTIVE BARRIER BETWEEN
 FLOORS.
  
 7) 2014 EXISTING BUILDING CODE 804.4.1.6 GROUP R-2. A
 FIRE ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF
 GROUP R-2 APARTMENT BUILDINGS AS REQUIRED BY THE
 FLORIDA FIRE PREVENTION CODE FOR EXISTING GROUP R-2
 OCCUPANCIES.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By jwitmer Date 2017-11-17 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2017-11-17 Time 11:59 Sent To  
Notes
2017-11-17 13:26:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101193
 ADD: 325 S. LAKESIDE CT. / 3 FLOORS OF RENOVATION
 CONT: CILAS CONCRETE CONSTRUCTION
 TEL: 561-689-3429
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: FRI. NOV. 17/ 2017
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD HAS NOT PROVIDED HOW CODE
 COMPLIANCE WAS DEVELOPED. PLEASE REVIEW THE 2014
 FBC-EXISTING BUILDING CODE SECTION 301.1. THE REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE
 METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS
 SELECTED BY THE APPLICANT. SECTIONS 301.1.1 THROUGH
 301.1.3 SHALL NOT BE APPLIED IN COMBINATION WITH EACH
 OTHER.
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) THE VALUE OF THE PROJECT IS EXTREMELY LOW IF THE
 VALUE OF THE SUB-CONTRACTORS IS INCLUDED IN THE SCOPE
 OF WORK. THE VALUE IS STILL LOW FOR THE BUILDING
 CONTRACTORS WORK.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 3) SHEET A-1 UNDER THE SCOPE OF WORK, COMMENT # 9
 INDICATES THE REMOVAL AND REPLACEMENT OF TUB. THE PLANS
 DOES NOT INDICATE THE TUB SURROUND TO BE REWORKED BUT
 THE REMOVAL OF THE TUB, THEY USUALLY NEED REPLACEMENT.
 IF SO THEY WILL NEED TO COMPLY WITH 2014 FBC-B SECTION;
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS.
  
 4) SHEET A-1 UNDER THE SCOPE OF WORK, COMMENT # 7
 INDICATES THE INSTALLATION OF TILE OVER EXISTING WOOD
 FLOORING. NOTE FOR THE 2ND AND 3RD FLOOR UNITS WILL
 NEED TO PROVIDE SOUND UNDERLAYMENT BEFORE THE TILE IS
 INSTALLED. FOR TILE, STONE, MARBLE, VINYL AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS.
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-02 Cont ID  
Sent By ppetty Date 2018-04-02 Time 08:43 Rev Time 0.00
Received By ppetty Date 2018-04-02 Time 08:43 Sent To  
Notes
2018-04-02 08:42:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: PASS
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6.CORRECTED
 7. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By jpearson Date 2017-12-05 Time 15:02 Rev Time 0.00
Received By jpearson Date 2017-12-05 Time 12:50 Sent To I
Notes
2017-12-05 15:02:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. IT APPEARS THAT 2 DIFFERENT METHODS WERE
 COMBINED TO PROVIDE CALCULATION, WHICH IS NOT TO
 COMPLIANT WITH CODE. ALSO, WILL THERE BE A HOUSE PANEL
 ON THIS SERVICE? THIS LOAD SHOULD BE INCLUDED. BASED ON
 CURRENT CONFIGURATION, IT APPEARS THAT ONE OF THE 400
 AMP MAINS WILL BE OVERLOADED. PROVIDE CORRECTION AS
 NEEDED. NEC 215.2, 220; FBC 107.2.1
 2. FEEDERS FROM METER CENTER TO INDIVIDUAL UNIT PANELS
 REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION. NEC 250.122
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 4. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD BE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13; FBC RE3702.10
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. PROVIDE NOTE FOR AFCI PROTECTION PER NEC 210.12:
 "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION." NEC 210.12
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-25 Cont ID  
Sent By pleduc Date 2018-06-25 Time   Rev Time 0.00
Received By pleduc Date 2018-06-25 Time 12:57 Sent To  
Notes
2018-06-25 16:01:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A FIRE ALARM SYSTEM IS REQUIRED AND IS INDICATED ON
 SHEET E 1. THE FIRE ALARM SYSTEM SHALL COMPLY WITH THE
 APPLICABLE CODE, INCLUDING NFPA 72.
  
 PER NFPA 101, CHAPTER 31, EXISTING APARTMENT
 OCCUPANCIES.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PER NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
 9.6.1.2 FIRE DETECTION, ALARM, AND COMMUNICATIONS
 SYSTEMS
 INSTALLED TO MAKE USE OF AN ALTERNATIVE PERMITTED BY
 THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE
 PROVISIONS
 OF THIS CODE APPLICABLE TO REQUIRED SYSTEMS.
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED,
 TESTED, AND MAINTAINED IN ACCORDANCE WITH THE
 APPLICABLE
 REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL CODE, AND
 NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN
 APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE
 CONTINUED IN USE.
  
 PER NFPA 72, CHAPTER 8,
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE
 SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND
 LEVEL OF AT
 LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5
 DB
 ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
 LEAST
 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA,
 WHICHEVER IS
 GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE
 PARTITION, IS LOCATED BETWEEN THE NOTIFICATION
 APPLIANCE AND
 THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED
 WITH THE
 BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
 18.4.5.3* EFFECTIVE JANUARY 1, 2014, AUDIBLE APPLIANCES
 PROVIDED
 FOR THE SLEEPING AREAS TO AWAKEN OCCUPANTS SHALL
 PRODUCE A LOW
 FREQUENCY ALARM SIGNAL THAT COMPLIES WITH THE
 FOLLOWING:
 (1) THE ALARM SIGNAL SHALL BE A SQUARE WAVE OR PROVIDE
 EQUIVALENT
 AWAKENING ABILITY.
 (2) THE WAVE SHALL HAVE A FUNDAMENTAL FREQUENCY OF 520
 HZ
 ? 10 PERCENT.
  
  
 2) FIRE ALARM SHOP DRAWING SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT FORE APPROVAL PRIOR TO ANY WORK BEEING
 DONE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-19 Cont ID  
Sent By pleduc Date 2018-03-19 Time   Rev Time 0.00
Received By pleduc Date 2018-03-19 Time 11:18 Sent To  
Notes
2018-03-19 12:05:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A FIRE ALARM SYSTEM IS REQUIRED AND IS INDICATED ON
 SHEET E 1. THE FIRE ALARM SYSTEM SHALL COMPLY WITH THE
 APPLICABLE CODE, INCLUDING NFPA 72.
  
 PER NFPA 101, CHAPTER 31, EXISTING APARTMENT
 OCCUPANCIES.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PER NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
 9.6.1.2 FIRE DETECTION, ALARM, AND COMMUNICATIONS
 SYSTEMS
 INSTALLED TO MAKE USE OF AN ALTERNATIVE PERMITTED BY
 THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE
 PROVISIONS
 OF THIS CODE APPLICABLE TO REQUIRED SYSTEMS.
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED,
 TESTED, AND MAINTAINED IN ACCORDANCE WITH THE
 APPLICABLE
 REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL CODE, AND
 NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN
 APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE
 CONTINUED IN USE.
  
 PER NFPA 72, CHAPTER 8,
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE
 SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND
 LEVEL OF AT
 LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5
 DB
 ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
 LEAST
 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA,
 WHICHEVER IS
 GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE
 PARTITION, IS LOCATED BETWEEN THE NOTIFICATION
 APPLIANCE AND
 THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED
 WITH THE
 BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
 18.4.5.3* EFFECTIVE JANUARY 1, 2014, AUDIBLE APPLIANCES
 PROVIDED
 FOR THE SLEEPING AREAS TO AWAKEN OCCUPANTS SHALL
 PRODUCE A LOW
 FREQUENCY ALARM SIGNAL THAT COMPLIES WITH THE
 FOLLOWING:
 (1) THE ALARM SIGNAL SHALL BE A SQUARE WAVE OR PROVIDE
 EQUIVALENT
 AWAKENING ABILITY.
 (2) THE WAVE SHALL HAVE A FUNDAMENTAL FREQUENCY OF 520
 HZ
 ? 10 PERCENT.
  
  
 2) FIRE ALARM SHOP DRAWING SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT FORE APPROVAL PRIOR TO ANY WORK BEEING
 DONE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By pleduc Date 2017-11-02 Time   Rev Time 0.00
Received By pleduc Date 2017-11-01 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2018-06-21 Time 15:36 Sent To  
Notes
2018-06-22 15:36:42C22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2018-03-12 Time 15:33 Sent To  
Notes
2018-03-13 15:33:33C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-05 Cont ID  
Sent By jpearson Date 2017-12-05 Time 15:02 Rev Time 0.00
Received By jpearson Date 2017-10-30 Time 14:43 Sent To  
Notes
2017-10-31 14:43:20C12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-11-17 Cont ID  
Sent By jwitmer Date 2017-11-17 Time 13:26 Rev Time  
Received By jwitmer Date 2017-11-17 Time 12:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-07-20 Cont ID  
Sent By ccole Date 2018-07-16 Time 07:46 Rev Time 0.00
Received By ccole Date 2018-07-12 Time 07:17 Sent To  
Notes
2018-07-16 07:49:36MECHANICAL PROVISO:
  
 VERIFY IN FIELD:
  
 1) PERMANENT ACCESS TO ROOFTOP CONDENSERS .
  
 2) ROOFTOP CONDENSERS LOCATED A MINIMUM OF 10' FROM
 ROOF EDGE OR PROVIDE 42" HIGH GUARD
  
 CCOLE- 7/20/18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-22 Cont ID  
Sent By ccole Date 2018-03-22 Time 15:29 Rev Time 0.00
Received By ccole Date 2018-03-22 Time 15:29 Sent To  
Notes
2018-03-22 15:46:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17101193
 3/22/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH THE
 RESIDENTIAL PROVISIONS OF THE FBC-14 ENERGY
 CONSERVATION CODE. THE SUBMITTED FORM C402-2017 CAN NOT
 BE USED TO SHOW COMPLIANCE. PLEASE SEE SECTION R101.5.1
 FOR ACCEPTED COMPLIANCE MATERIALS, AND SECTION R405.4.2
 EXCEPTION WHICH PROVIDES COMPLIANCE INFORMATION FOR
 MULTIFAMILY UNITS AND MODEL HOMES.
  
 2) THE AC COOLING AND HEATING SYSTEMS SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J. THE
 SUBMITTED CALCULATIONS ARE NOT IN COMPLIANCE. PLEASE
 NOTE THAT
  
 3) INDICATE HOW THE APARTMENTS WILL BE VENTILATED AND
 PROVIDE CALCULATIONS USING EITHER NATURAL OR MECHANICAL
 VENTILATION- SEE SECTIONS 401.2, 402.2, AND TABLE
 403.3.
  
 4) AC CLOSETS ARE CONSIDERED PLENUM CHAMBERS PER
 SECTION R403.2.2, AND SHALL BE CONSTRUCTED WITH
 NON-COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 602.2.1. THE WOOD LOUVERED DOOR ENCLOSING THE CLOSET
 CANNOT BE USED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By ccole Date 2017-11-28 Time 17:11 Rev Time 0.00
Received By ccole Date 2017-11-28 Time 17:08 Sent To  
Notes
2017-11-28 17:25:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101193
 11/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL WITH
 CORRESPONDING DRAWINGS AND DETAILS. CLARIFY IF ANY
 ALTERATIONS ARE PROPOSED FOR THE EXISTING HVAC SYSTEMS,
 OR IF ANY NEW GAS APPLIANCES OR EQUIPMENT ARE TO BE
 INSTALLED.
  
 2) CLARIFY IF A NEW RANGE HOOD IS TO BE INSTALLED WITH
 THE NEW COOKING APPLIANCES=- SEE SECTION 504 AND
 PROVIDE DETAILS. PLEASE NOTE THAT EXHAUST VENTILATION
 FOR THE KITCHEN IS REQUIRED IN ACCORDANCE WITH TABLE
 403.3.
  
 3) PROVIDE EXHAUST FOR THE NEW DRYERS PER SECTION 504.
 SHOW THE TYPE AND SIZE OF EXHAUST DUCTS, EXHAUST RUNS,
 TERMINATION LOCATIONS WITH CLEARANCE DISTANCE
 DIMENSIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2018-04-06 Time 15:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 18:44 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 18:12 Sent To  
Notes
2017-11-29 18:47:211ST REVIEW: FBC 2014 5TH EDITION
  
  
 PLUMBING COMMENTS:
  
 1.IS THE WASHER AND DRYER EXISTING IF IT IS NEW PLEASE
 PROVIDE ISOMETRIC DIAGRAMS FOR SANITARY AND WATER. PER
 WPB AMEN TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2018-07-16 Cont ID  
Sent By LL Date 2018-07-16 Time 17:13 Rev Time 0.00
Received By shill Date 2018-07-16 Time 17:13 Sent To  
Notes
2018-07-16 17:14:12STRUCTURAL AND INTERIOR ONLY
 ZONING WAS ADDED AT APPLICANT'S REQUEST
  
  