| 2017-11-08 08:20:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN |
| | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| | 471.003(2)(H); 471.025; FBC 107.2.1 |
| | 2. WIRE FROM METER CAN TO SERVICE RATED TRANSFER SWITCH |
| | IS REQUIRED TO BE SIZED FOR MAIN BREAKER IN TRANSFER |
| | SWITCH. THE REDUCTIONS IN WIRE SIZE FROM 310.15(B)(7) |
| | CANNOT BE USED FOR THIS BECAUSE THIS ALLOWANCE IS ONLY |
| | FOR THE FEEDER THAT SUPPLIES 100% OF THE LOAD. SIZE |
| | WIRE PER NEC 310.15(B)(16) AND PROVIDE CORRECTION. NEC |
| | 310.15(B)(16); FBC RE TABLE E3603.1, 3704.1 |
| | 3. WIRE FROM SERVICE RATED TRANSFER SWITCH TO PANEL IS |
| | REQUIRED TO BE SIZED FOR MAIN BREAKER IN TRANSFER |
| | SWITCH. THE REDUCTIONS IN WIRE SIZE FROM 310.15(B)(7) |
| | CANNOT BE USED FOR THIS BECAUSE THIS ALLOWANCE IS ONLY |
| | FOR THE FEEDER THAT SUPPLIES 100% OF THE LOAD. SIZE |
| | WIRE PER NEC 310.15(B)(16) AND PROVIDE CORRECTION. NEC |
| | 310.15(B)(16); FBC RE TABLE E3603.1, 3704.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 5. WIRES RUN IN PARALLEL FROM GENERATOR MUST BE A |
| | MINUMUM SIZE OF 1/0 AWG. THIS CONDUIT MUST INCLUDE AN |
| | EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC |
| | 310.10(H)(1), 250.122; FBC RE 3704.6 |
| | 6. PROVIDE SPEC SHEET FOR TRANSFER SWITCH. NEC 110.3; |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |