| 2017-11-02 10:41:43 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17101173 |
| | ADD: 1156 ELIZABETH AVE. |
| | CONT: KEMKON PROPERTIES INC. |
| | TEL: 561-512-7637 |
| | E-MAIL: [email protected] |
| | [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. NOV. 02/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) CREATION OR EXTENSION OF NONCONFORMITY. PLEASE NOTE |
| | THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE DOES |
| | NOT SHOW THE SAME SQUARE FOOTAGE FOR THIS BUILDING AS |
| | THE SUBMITTED DEPICTED PLANS. THE FOOT PRINT OF THE |
| | BUILDING RECORDED WITH THE PROPERTY APPRAISERS OFFICE |
| | WOULD BE THE SAME IF THE KITCHEN WAS NOT THERE. IN |
| | REVIEWING P. B. COUNTY AERIAL PHOTOGRAPHY IN 2006 |
| | EXTERIOR WALLS OF AN ADDITION WERE ERECTED. THEN IN |
| | 2009 THE P. B. COUNTY AERIAL PHOTOGRAPHS SHOW A |
| | FINISHED ROOF. I HAVE REVIEWED THE PERMIT RECORDS FOR |
| | BOTH ADDRESSES 1156 ELIZABETH AVE. AND 1177 CLARE AVE |
| | AND FOUND NO RECORDS FOR AN ADDITION AT THIS ADDRESS. |
| | IN REVIEWING THE CITY PERMIT RECORDS UNDER PERMIT |
| | 06082252 FOR 1177 CLARE AVE. THERE WAS A SURVEY THAT |
| | DIDN?T SHOW ANY ADDITION OR CURRENT KITCHEN. THE SURVEY |
| | SHOWED THE SAME FOOTPRINT AS THE PALM BEACH COUNTY |
| | PROPERTY APPRAISERS OFFICE. THE ILLEGAL ADDITION WILL |
| | BE TREATED AS NEW WORK AND NEED TO MEET THE REGULATIONS |
| | OF THE 2014 FBC-B. |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| | OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| | NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| | STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| | OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | SINCE THE ADDITION WAS NOT PERMITTED IT IS CONSIDERED |
| | NEW WORK. 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2) PLEASE INCREASE THE VALUE OF THE PERMIT TO INCLUDE |
| | THE UNPERMITTED WORK IS NOT REFLECTED IN THE PERMIT |
| | VALUE THE INCREASE IN SQUARE FOOT AREA OF 16 X 41 = 656 |
| | SQ. FEET @ A VALUE OF 105.82 A SQUARE FOOT. NOTE THIS |
| | VALUE IS TAKEN FROM THE AUGUST 2006 IBC EVALUATION |
| | TABLES FOR RESTAURANT TYPE VB CONSTRUCTION OR A DOLLAR |
| | AMOUNT OF $59,894.12 DOLLARS. 4 TIMES THE PERMIT FEE |
| | WOULD BE ASSESSED AGAINST THIS PERMIT. |
| | |
| | 3) PLEASE NOTE THIS BUILDING (ADDRESSES 1156 ELIZABETH |
| | AVE) IS IN A FLOOD ZONE. THERE IS IN THE P. B. COUNTY |
| | PROPERTY APPRAISERS OFFICE FOR THIS ADDRESS 3 BUILDINGS |
| | IMPROVEMENT VALUE, NO LAND, OF $770,273.00/ 17217 SQ. |
| | FT. = $44.74 DOLLARS PER SQ. FT. BUILDING # 2 TOTAL SQ. |
| | FT. 1300 X $44.74.00 = $58,162.00 DOLLARS OF |
| | IMPROVEMENT VALUE FOR BUILDING # 2. |
| | |
| | BUILDING # 2 IMPROVEMENT VALUE $58,162.00 |
| | |
| | ILLEGAL ADDITION VALUE OF: $59,894.00 |
| | PERMIT RENOVATION VALUE OF: $75,000.00 |
| | TOTAL VALUE: $134,894.00 SUBSTANTIAL IMPROVEMENT |
| | |
| | PLEASE NOTE THE ORIGINAL BUILDING WAS BUILT IN 1935 |
| | PRE-FIRM. IF NO WORK COULD OCCURRED MAKING THE BUILDING |
| | MEET THE SUBSTANTIAL IMPROVEMENT. |
| | THE ILLEGAL ADDITION IS VALUE IS WORTH MORE THAN THE |
| | VALUE OF THE BUILDING # 2. WITH THE PROPOSED PERMIT |
| | VALUE AND ILLEGAL ADDITION THE SUBSTANTIAL IMPROVEMENT |
| | VALUE IS 4 TIMES THE VALUE TO MEET SUBSTANTIAL |
| | IMPROVEMENT. |
| | |
| | SUBSTANTIAL IMPROVEMENT DESK REFERENCE, PAGE 6-9, TABLE |
| | 6-1A. |
| | TYPE OF WORK, LATERAL ADDITION, SUBSTANTIAL ADDITION, |
| | STRUCTURALLY CONNECTED, BOTH THE ADDITION AND BUILDING |
| | WILL NEED TO COMPLY. |
| | |
| | SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR |
| | FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR, |
| | RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE |
| | CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR |
| | EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT |
| | OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF |
| | NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE. |
| | |
| | PLEASE NOTE PERMITS APPLIED FOR AFTER OCT. 11/2017 WILL |
| | NEED TO HAVE A FINISH FLOOR 2 FEET ABOVE THE BASE |
| | FLOOD. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD |
| | PREVENTION & CONTROL |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE |
| | AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF |
| | PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016, |
| | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| | |
| | PLEASE ALSO NOTE THAT ON THE DATE OCT. 12TH/ 2017 THE |
| | CITY ADOPTED THE NEW FLOOD ORDINANCE, THE NEW FLOOD |
| | MAPS WENT INTO AFFECT WITH THE NAV88 NOMENCLATURE AND 2 |
| | FOOT FREEBOARD REQUIREMENT. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, |
| | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| | |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. W. |
| | P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 3) PLEASE NOTE IN AUGUST 2016 THE ASSISTANT BUILDING |
| | OFFICIAL MR. STEVEN KENNEDY REQUEST FOR DETERMINATION |
| | TO RESOLVE THE OUTSTANDING/ EXPIRED PERMITS FOR THIS |
| | SITE ADDRESS, 1156 ELIZABETH AVE. AND 1177 CLARE. |
| | PLEASE NOTE IF ACTION IS NOT TAKEN IMMEDIATELY TO |
| | RESOLVE THE UNPERMITTED WORK AND EXPIRED PERMITS WE |
| | WILL TURN THIS MATTER OVER TO CODE ENFORCEMENT AND THEN |
| | TO THE SPECIAL MASTER FOR A HEARING. |
| | |
| | 4) PLEASE EITHER PROVIDE A EXISTING FLOOR PLAN OR A |
| | INTERIOR DEMO PLAN TO VIEW WHAT IS EXISTING AND WHAT IS |
| | PROPOSED NEW WORK, THIS MAY TIE IN WITH EXPIRED |
| | PERMITS? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) PLEASE SEE THE 2014 FLORIDA ENERGY CODE, |
| | DEFINITIONS: RENOVATED BUILDING. A RESIDENTIAL OR |
| | NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT |
| | VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER |
| | HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, |
| | PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 |
| | PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. |
| | THIS BUILDING WILL NEED TO SHOW COMPLIANCE, 2014 ENERGY |
| | CODE C101.5. COMMERCIAL BUILDINGS SHALL MEET THE |
| | COMMERCIAL PROVISIONS. |
| | C401.1 SCOPE. |
| | THE REQUIREMENTS CONTAINED IN THIS CHAPTER ARE |
| | APPLICABLE TO COMMERCIAL BUILDINGS, OR PORTIONS OF |
| | COMMERCIAL BUILDINGS. |
| | |
| | C401.2 APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | C401.2.1 APPLICATION TO EXISTING BUILDINGS. |
| | ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING |
| | BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. SECTIONS C402, C403, C404 AND C405; OR |
| | 2. ANSI/ASHRAE/IESNA 90.1. |
| | |
| | 6) PLEASE PROVIDE CHANGE IN GRADE THROUGH THE FLOOR |
| | PLAN TO SHOW COMPLIANCE WITH: 2014 ACCESS. CODE 206.4.1 |
| | PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY |
| | 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL |
| | PUBLIC ENTRANCES SHALL COMPLY WITH 404. SHEET 1.0A |
| | SHOWS A NEW DOORWAY LEADING TO THE EXTERIOR OF THE |
| | BUILDING, THE PLAN DOES NOT DECLARE THE USAGE OF THE |
| | INTERIOR AREA JUST INSIDE OF THE DOORWAY, IS THIS AREA |
| | OPEN TO THE PUBLIC AS AN EXIT? |
| | |
| | 7) THE LIFE SAFETY SHEET 1.0A DOES NOT SHOW COMPLIANCE |
| | WITH THE 2014 FBC-ACCESSIBILITY CODE; |
| | 7A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 7B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 7C) DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, |
| | BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF |
| | WORK SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 7D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 7D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 8) SHEET A.0A) SHOWS THE EXISTING RESTROOMS, PLEASE |
| | NOTE WE HAVE NO PERMITS PULLED FOR EITHER ADDRESS 1156 |
| | ELIZABETH OR 1177 CLARE SHOWING ACCESSIBLE TOILET |
| | UPGRADES. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (10.) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | |
| | 9) THE PLANS ARE LACKING DETAILS FOR NEW WINDOW AND |
| | DOOR OPENINGS: |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | SOIL CONDITIONS/ANALYSIS |
| | TERMITE PROTECTION |
| | DESIGN LOADS |
| | WIND REQUIREMENTS |
| | BUILDING ENVELOPE |
| | STRUCTURAL CALCULATIONS (IF REQUIRED) |
| | FOUNDATION |
| | FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, |
| | INCLUDING LOWEST FLOOR |
| | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT |
| | MATERIALS |
| | WALL SYSTEMS |
| | FLOOR SYSTEMS |
| | ROOF SYSTEMS |
| | |
| | 10) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 13) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |