Plan Review Details - Permit 17101170
Plan Review Stops For Permit 17101170
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-20 Cont ID  
Sent By cthroop Date 2017-11-20 Time 16:32 Rev Time 0.00
Received By cthroop Date 2017-11-20 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By cthroop Date 2017-11-14 Time 07:06 Rev Time 0.00
Received By cthroop Date 2017-11-08 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-20 Cont ID  
Sent By jpearson Date 2017-11-20 Time 13:41 Rev Time 0.00
Received By jpearson Date 2017-11-20 Time 13:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 10:04 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 10:04 Sent To B
Notes
2017-11-07 10:04:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 5. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.6
 6. PROVIDE SPEC SHEET FOR ULTRA THIN LED LIGHTS STATED
 ON PLAN. NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-20 Cont ID  
Sent By cthroop Date 2017-11-20 Time 16:32 Rev Time 0.00
Received By cthroop Date 2017-11-16 Time 11:32 Sent To I
Notes
2017-11-20 11:33:05RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By cthroop Date 2017-11-14 Time 07:06 Rev Time 0.00
Received By cthroop Date 2017-10-27 Time 14:11 Sent To I
Notes
2017-10-30 14:11:58ROUTED TO ELECTRICAL INBOX