Plan Review Details - Permit 17101162
Plan Review Stops For Permit 17101162
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-04-12 Cont ID  
Sent By skennedy Date 2018-04-12 Time 12:28 Rev Time 0.00
Received By skennedy Date 2018-04-12 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-04-05 Cont ID  
Sent By aclange Date 2018-04-05 Time 07:38 Rev Time 0.00
Received By aclange Date 2018-04-05 Time 07:17 Sent To  
Notes
2018-04-05 07:38:34****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. ONE SET OF PLANS IS COMPLETED. THE SECOND SET IS
 MISSING ARCHITECT'S SIGNATURES AND SEALS ON THE
 FOLLOWING PAGES.
  
 IC1.0, IC1.1, LS1.1, A1.1, A6.1, A8.1, A9.0 AND A9.1.
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED.
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 16:20 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 15:20 Sent To  
Notes
2018-03-23 16:20:07****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 THIRD REVIEW:
  
 REPEATED COMMENT FROM LAST REVIEW AND ADDITIONAL
 COMMENTS REGARDING THE COLLATING THE PLANS.
  
 A. TWO COMPLETE SETS OF PLANS NOT PROVIDED.
  
 B. PAGES NOT IN INDEX. AD 1.1, E 2.2, P 1.1
  
 C. BOTH SETS HAVE DUPLICATED ELECTRICAL PAGES.
  
 D. BOTH SETS HAVE DUPLICATED MECHANICAL PAGES.
  
 E. ONE SET MISSING A 6.1, A 8.1, A 9.0 AND A 9.1
  
 F. PAGE E 3.1 NOT PROVED BOTH SETS.
  
 G. PUT TOGETHER TWO COMPLETE SETS OF PLANS FOR REVIEW.
 ADD THE MISSING PAGES TO THE INDEX. ORGANIZE THE PAGES
 IN THE ORDER OF THE INDEX.
  
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 4X FEES PLAN REVIEW FEE
  
 F.S. 553.80 (2) (B)
  
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 PREVIOUS COMMENTS:
  
 COMPLETE SETS OF PLANS NOT PROVIDED.
 ONLY ONE SET OF THE FOLLOWING PAGES FOUND.
 IC1.0, IC1.1, LS 1.1, A1.1, A6.1, A8.1, A9.0 AND A9.1
  
 SUBMIT A MINIMUM OF TWO SETS OF PLANS FOR REVIEW. FBC
 107.1
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By aclange Date 2018-02-22 Time 10:05 Rev Time 0.00
Received By aclange Date 2018-02-22 Time 08:45 Sent To P
Notes
2018-02-22 10:02:14****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 SECOND REVIEW:
  
 PREVIOUS COMMENTS ADDRESSED.
  
 NEW COMMENT:
  
 COMPLETE SETS OF PLANS NOT PROVIDED.
 ONLY ONE SET OF THE FOLLOWING PAGES FOUND.
 IC1.0, IC1.1, LS 1.1, A1.1, A6.1, A8.1, A9.0 AND A9.1
  
 SUBMIT A MINIMUM OF TWO SETS OF PLANS FOR REVIEW. FBC
 107.1
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By aclange Date 2017-10-31 Time 10:42 Rev Time 0.00
Received By aclange Date 2017-10-31 Time 08:05 Sent To  
Notes
2017-10-31 10:44:23****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. PERMIT VALUE HAS BEEN REVISED TO INCLUDE ALL SUB
 CONTRACTORS . IT NOW IS $201,800.
  
 2. INCLUDED IN THE BUILDING DATA IS THE LEVEL OF
 ALTERATION AS "REPAIRS". SEE EXISTING BUILDING CODE
 SECTIONS 503 AND 504 FOR LEVEL 1 AND 2 ALTERATIONS.
 SHOW HOW COMPLIANCE WITH THE SELECTED LEVEL OF
 ALTERATION WILL BE SELECTED.
  
 3. A) A1.1 LEGEND NOTE, NEW WALL SEE A.0.3 FOR
 PARTITION DETAILS. PAGE A0.3 NOT PROVIDED WITH THESE
 PLANS.
 B) A1.1 LEGEND NOTE, SEE A7.1 FOR DOOR SCHEDULE. PAGE
 A7.1 NOT PROVIDED WITH THESE PLANS.
  
 4. PROVIDE AN EVALUATION REPORT FOR THE CLOSED CELL
 INSULATION USED. SHOW HOW THIS PRODUCT WILL BE IN
 COMPLIANCE IN TYPE I CONSTRUCTION FBC 2603.5 AND FBC
 2605.1. ALSO FOR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEXES. FBC 2605.5.4.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-04-09 Cont ID  
Sent By jpearson Date 2018-04-09 Time 10:55 Rev Time 0.00
Received By jpearson Date 2018-04-09 Time 10:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By jpearson Date 2018-02-22 Time 15:48 Rev Time 0.00
Received By jpearson Date 2018-02-22 Time 15:48 Sent To  
Notes
2018-02-22 15:47:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SET OF CORRECTED PLANS PROVIDED, PROVIDE 2
 COMPLETE SETS. FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By jpearson Date 2017-12-04 Time 10:09 Rev Time 0.00
Received By jpearson Date 2017-12-04 Time 09:57 Sent To  
Notes
2017-12-04 10:09:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ON SHEET E2.1, THERE IS A BLOCK NOTE REFERENCING THE
 2017 FBC ENERGY CONSERVATION. THIS PERMIT APPLICATION
 WAS SUBMITTED PRIOR TO THE EFFECTIVE DATE OF THAT CODE
 AND THAT CODE WILL NOT BE USED FOR THIS PROJECT.
 THEREFORE, PROVIDE DETAILS OF ALL EXISTING LIGHTING
 CONTROLS. PROVIDE THE ADDITIONAL LIGHTING CONTROLS
 STIPULATED IN THE ENERGY CONSERVATION CODE. IF NOT TO
 CURRENT CODE, SHOW AS NEW INSTALLATIONS. FBC EC
 405.2.2; FBC 2014 PREFACE.
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 5. THERE IS NO POWER PLAN INCLUDED IN THIS PLAN. THE
 SCOPE OF WORK STATES THAT WORK WILL BE COMPLETED ON
 WALLS THAT ARE DAMAGED, BUT DOES NOT EXPLAIN ANY
 ELECTRICAL IN THESE WALLS TO BE REPAIRED. PROVIDE
 DETAILS OF ANY ELECTRICAL IN WALLS TO BE REPAIRED,
 NOTING COMPLIANCE WITH NEC 517.13 WHERE APPLICABLE. FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2018-04-12 Cont ID  
Sent By pleduc Date 2018-04-12 Time   Rev Time 0.00
Received By pleduc Date 2018-04-12 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2018-04-10 Cont ID  
Sent By pleduc Date 2018-04-10 Time   Rev Time 0.00
Received By pleduc Date 2018-04-09 Time 16:17 Sent To  
Notes
2018-04-10 12:34:083RD RESPONSE
  
  
 THESE PLANS CONTINUE TO BE UNORGANIZED.
  
 PREVIOUS COMMENTS:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE NOT ORGANIZED IN ANYWAY OR
 REASONABLE FASHION THAT CAN BE DETERMINED AS A SET.
  
 THE SHEETS ARE NOT IN ANY KIND OF ORDER. THE SHEETS ARE
 NOT STAPLED OR SEPARATED SO NO SETS CAN BE DEFINED FROM
 ONE OR THE OTHER OR EVEN THREE.
  
 THERE IS ONE SET THAT IS STAPLED WITH A FIRE STAMP ON
 IT BUT IT MAY A VOIDED SET. THIS SHEET MAY HAVE BEEN
 PASSED BY FIRE WITH A PROVISO BUT ALL OTHER DEPARTMENTS
 FAILED IT.
  
  
 2) PLEASE REVIEW AND MAKE COMPLETE ORGANIZED SETS
 SEPARATED FROM EACH OTHER. PLACE VOID ON ANY SHEETS OR
 SETS ACCORDINGLY.
  
  
 ADDITIONAL COMMENTS:
  
  
 3) SHEET A0.0 ON ONE SET HAS CLOUD REVISIONS, ON THE
 OTHER SET IT IS THE ORIGINAL WITH NO REVISION CLOUDS
 AND AN OLD FIRE PREVENTION STAMP.
  
 4) SHEET M2.1 ON ONE SET HAS NEW CLOUD REVISIONS AND
 NEW ENGINEER STAMP, ON THE OTHER SET IT HAS OLD
 REVISION CLOUDS, AN OLD DATED ENGINEER STAMP.
  
 5) SHEET M2.2 ON ONE SET HAS NEW CLOUD REVISIONS AND
 NEW ENGINEER STAMP, ON THE OTHER SET IT HAS OLD
 REVISION CLOUDS, AN OLD DATED ENGINEER STAMP.
  
 6) SHEET E0.1 ON ONE SET HAS NEW CLOUD REVISIONS AND
 NEW ENGINEER STAMP, ON THE OTHER SET IT HAS OLD
 REVISION CLOUDS, AN OLD DATED ENGINEER STAMP.
  
 7) SHEET E1.1 ON ONE SET HAS NEW CLOUD REVISIONS AND
 NEW ENGINEER STAMP, ON THE OTHER SET IT HAS OLD
 REVISION CLOUDS, AN OLD DATED ENGINEER STAMP.
  
 8) SHEET E2.1 ON ONE SET HAS NEW CLOUD REVISIONS AND
 NEW ENGINEER STAMP, ON THE OTHER SET IT HAS OLD
 REVISION CLOUDS, AN OLD DATED ENGINEER STAMP.
  
 PLEASE ENSURE THAT EACH PAGE OF THE SUBMITTED SETS ARE
 EQUAL AND REFLECT THE CURRENT STATE OF UPDATED
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2018-03-20 Cont ID  
Sent By pleduc Date 2018-03-20 Time   Rev Time 0.00
Received By pleduc Date 2018-03-20 Time 11:07 Sent To  
Notes
2018-03-20 11:48:242ND RESPONSE
  
 THE PREVIOUS COMMENTS WERE NOT ADDRESSED.
  
 THSES PLANS CONTINUE TO BE UNORGANIZED.
  
 PREVIOUS COMMENTS:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE NOT ORGANIZED IN ANYWAY OR
 RESONABLE FASHION THAT CAN BE DETERMINED AS A SET.
  
 THE SHEETS ARE NOT IN ANY KIND OF ORDER. THE SHEETS ARE
 NOT STAPLED OR SEPARATED SO NO SETS CAN BE DEFINED FROM
 ONE OR THE OTHER OR EVEN THREE.
  
 THERE IS ONE SET THAT IS STAPLED WITH A FIRE STAMP ON
 IT BUT IT MAY A VOIDED SET. THIS SHEET MAY HAVE BEEN
 PASSED BY FIRE WITH A PROVISO BUT ALL OTHER DEPARTMENTS
 FAILED IT.
  
  
 2) PLEASE REVIEW AND MAKE COMPLETE ORGANIZED SETS
 SEPARATED FROM EACH OTHER. PLACE VOID ON ANY SHEETS OR
 SETS ACCORDINGLY.
  
  
 ADDITIONAL COMMENTS:
  
  
 3) THERE IS ONLY 1 LIFE SAFETY SHEET, BUT TWO APPARENT
 SETS
  
 4) THERE ARE ONLY 1 IC 1 & IC 1.1 SHEETS, BUT TWO
 APPARENT SETS.
  
 5) WITH THE TWO SETS, IF YOU WERE TO TURN EACH SET ONE
 AT A TIME, THEY DO NOT MATCH.
  
 6) A LIFE SAFETY REVIEW CAN NOT BE COMPLETED BECAUSE I
 DO NOT KNOW WHAT SHEETS ARE SUPPOSED TO COMPRISE A SET
 AND WHAT MAY OR MAY NOT BE MSSING.
  
 7) PLEASE CORRECT AND ENSURE THE SETS MATCH.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-02-01 Cont ID  
Sent By pleduc Date 2018-02-01 Time   Rev Time 0.00
Received By pleduc Date 2018-02-01 Time 11:47 Sent To  
Notes
2018-02-01 13:41:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE NOT ORGANIZED IN ANYWAY OR
 RESONABLE FASHION THAT CAN BE DETERMINED AS A SET.
  
 THE SHEETS ARE NOT IN ANY KIND OF ORDER. THE SHEETS ARE
 STAPLED OR SEPARATED SO NOT SETS CAN BE DEFINED FROM
 ONE OR THE OTHER OR EVEN THREE.
  
 THERE IS ONE SET THAT IS STAPLED WITH A FIRE STAMP ON
 IT BUT IT MAY A VOIDED SET. THIS SHEET MAY HAVE BEEN
 PASSED BY FIRE WITH A PROVISO BUT ALL OTHER DEPARTMENTS
 FAILED IT.
  
  
 2) PLEASE REVIEW AND MAKE COMPLETE ORGANIZED SETS
 SEPARATED FROM EACH OTHER. PLACE VOID ON ANY SHEETS OR
 SETS ACCORDINGLY.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By wjolin Date 2017-11-02 Time 12:50 Rev Time 0.00
Received By wjolin Date 2017-11-02 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-12 Cont ID  
Sent By spalmer Date 2018-04-12 Time 12:35 Rev Time 0.00
Received By spalmer Date 2018-03-16 Time 14:59 Sent To  
Notes
2018-03-19 15:00:29C26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-28 Cont ID  
Sent By gjohnson Date 2018-02-28 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2018-02-28 Time 15:33 Sent To  
Notes
2018-01-31 12:53:45C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-04 Cont ID  
Sent By aclange Date 2017-12-04 Time 10:23 Rev Time 0.00
Received By aclange Date 2017-10-27 Time 14:04 Sent To  
Notes
2017-10-30 14:04:37C20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-12 Cont ID  
Sent By skennedy Date 2018-04-12 Time 12:28 Rev Time 0.00
Received By skennedy Date 2018-04-12 Time 12:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-02-20 Cont ID  
Sent By ccole Date 2018-02-20 Time 10:44 Rev Time 0.00
Received By ccole Date 2018-02-20 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-18 Cont ID  
Sent By ccole Date 2017-11-18 Time 11:49 Rev Time 0.00
Received By ccole Date 2017-11-18 Time 11:49 Sent To  
Notes
2017-11-18 12:17:411ST REVIEW FBC-2014 MECHANICAL CODE, GUIDELINES FOR
 DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES-2010
 PERMIT #17101162
 11/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.1: PROVIDE THE CURRENT CODE OR STANDARD
 USED TO ESTABLISH THE VENTILATION REQUIREMENTS AND
 PRESSURE RELATIONSHIPS SHOWN IN THE AIR SUMMARY TABLE.
  
 2) M2.1, M2.2, & M3.1: PLEASE LABEL THE DRESSING ROOMS
 T140A & T140B ON THE PLANS. PLEASE NOTE THAT EXHAUST
 VENTILATION SYSTEMS ARE REQUIRED FOR THE DRESSING ROOMS
 AND LOCKER ROOM PER TABLE 403.3 FBC-14.
  
 3) M3.1: PLEASE CLARIFY WHY EXHAUST VENTILATION IS
 PROVIDED FOR X-RAY ROOMS 2 & 3 BUT NOT FOR X-RAY 1, AND
 THE SAME FOR WAITING ROOM T1070 BUT NOT FOR ANY OF THE
 OTHER WAITING ROOMS.
  
 4) PROVIDE A SUBMITTAL FOR THE NEW DUCT INSULATION WITH
 APPROVAL SIGNATURE BY THE DEWIGN PROFESSIONAL OF
 RECORD. THE PRODUCT DATA SHALL INDICATE THE MATERIAL IS
 LISTED AND LABELED AS HAVING A FLAME SPREAD OF NOT MORE
 THAN 25 AND SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723-
 SECTION 602.2.1 MATERIALS WITHIN PLENUMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-11 Cont ID  
Sent By skennedy Date 2018-04-11 Time 09:33 Rev Time 0.00
Received By skennedy Date 2018-04-11 Time 09:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-02-28 Cont ID  
Sent By gjohnson Date 2018-02-28 Time 15:26 Rev Time 0.00
Received By gjohnson Date 2018-02-28 Time 15:26 Sent To  
Notes
2018-02-28 15:32:562ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 2ND REQUEST1. PROVIDE PLUMBING PLAN THE CLEARLY SHOWS
 THE SCOPE OF ALL PLUMBING WORK TO BE DONE. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT AD1.1 KEY NOTE #7 REMOVE SINK AND TOILET SHT.
 A1.1 DOES NOT LIST THE SINK AND TOILET THAT WAS REMOVED
 ON SHT AD1.1 THE PLUMBING APPLICATION STATES MULTIPLE
 MOP SINKS, SINKS AND WATER CLOSETS I DON'T SEE THAT ON
 THE PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 15:11 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 13:51 Sent To  
Notes
2017-11-29 15:16:541ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING PLAN THE CLEARLY SHOWS THE SCOPE OF
 ALL PLUMBING WORK TO BE DONE. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  