Plan Review Details - Permit 17101137
Plan Review Stops For Permit 17101137
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 09:19 Rev Time 0.00
Received By shill Date 2017-11-14 Time 09:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-06 Cont ID  
Sent By jleahy Date 2017-11-06 Time 16:38 Rev Time 0.00
Received By jleahy Date 2017-11-06 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-31 Cont ID  
Sent By pleduc Date 2017-10-31 Time   Rev Time 0.00
Received By pleduc Date 2017-10-31 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-12-12 Time   Rev Time 0.00
Received By cpuell Date 2017-12-06 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 09:20 Rev Time 0.00
Received By shill Date 2017-10-27 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-19 Cont ID  
Sent By ccole Date 2017-12-19 Time 08:57 Rev Time 0.00
Received By ccole Date 2017-12-12 Time 08:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By ccole Date 2017-11-03 Time 14:10 Rev Time 0.00
Received By ccole Date 2017-11-03 Time 12:28 Sent To  
Notes
2017-11-03 14:24:281ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101137
 PHILLIPS POINTE EAST TOWER
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M0.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 GREENHECK 48 MODEL RGU UPBLAST FAN, AND REFER TO 513
 SMOKE CONTROL SYSTEMS, AND SPECIFICALLY SECTIONS
 513.10, AND 513.10.5. VERIFY THAT THE NEW GREENHECK FAN
 IS RATED AND CERTIFIED BY THE MANUFACTURER FOR THE
 PROBABLE TEMPERATURE RISE, IS UL LISTED AS A POWER
 VENTILATOR FOR SMOKE CONTROL, AND THAT IT IS EQUIPPED
 WITH TWO BELTS (IF THE FAN IS BELT DRIVEN AND NOT
 DIRECT-DRIVE)
  
 2) SHEET M3.1) PROVIDE THE WIND LOAD DESIGN CRITERIA
 PER SECTION 1609 FBC-14 BUILDING.
  
 3) M4.1) THE SHEET TOO FAINT TO READ AND NOT LEGIBLE-
 SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 4) VERIFY THE FAN IS BEING SUPPLIED WITH TWO SOURCES OF
 POWER- PRIMARY FROM THE NORMAL BUILDING SYSTEM, AND
 SECONDARY FROM AN APPROVED STANDBY SOURCE- SECTION
 513.11.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 09:19 Rev Time 0.00
Received By shill Date 2017-11-14 Time 09:19 Sent To  
Notes
2017-12-19 14:09:47MECH DIG/SIGS GOOD- CCOLE- 12/19/17
2017-11-14 09:20:15DIGITAL SIGNATURES OK
 PROVISO: NEW SHEETS SUBMITTED 2ND CYCLE REQUIRE REVIEW
  