Plan Review Details - Permit 17101134
Plan Review Stops For Permit 17101134
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 08:25 Rev Time 0.00
Received By shill Date 2017-11-14 Time 08:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-06 Cont ID  
Sent By jleahy Date 2017-11-06 Time 16:37 Rev Time 0.00
Received By jleahy Date 2017-11-06 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-31 Cont ID  
Sent By pleduc Date 2017-10-31 Time   Rev Time 0.00
Received By pleduc Date 2017-10-31 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-12-12 Time   Rev Time 0.00
Received By cpuell Date 2017-12-06 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 08:27 Rev Time 0.00
Received By shill Date 2017-10-27 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-12 Cont ID  
Sent By ccole Date 2017-12-12 Time 08:56 Rev Time 0.00
Received By ccole Date 2017-12-12 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By ccole Date 2017-11-03 Time 11:53 Rev Time 0.00
Received By ccole Date 2017-11-03 Time 11:36 Sent To  
Notes
2017-11-03 12:10:121ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101134
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO 513 SMOKE CONTROL SYSTEMS, AND SPECIFICALLY
 SECTIONS 513.10, AND 513.10.5. VERIFY THAT THE NEW
 GREENHECK TFI-FS FAN IS RATED AND CERTIFIED BY THE
 MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE, IS UL
 LISTED AS A POWER VENTILATOR FOR SMOKE CONTROL, AND
 THAT IT IS EQUIPPED WITH TWO BELTS.
  
 2) SHEET M3.1) PROVIDE THE WIND LOAD DESIGN CRITERIA
 PER SECTION 1609 FBC-14 BUILDING.
  
 3) M4.1) THE SHEET IS TOO FAINT TO READ AND NOT
 LEGIBLE- SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 4) VERIFY THE FAN IS BEING SUPPLIED WITH TWO SOURCES OF
 POWER- PRIMARY FROM THE NORMAL BUILDING SYSTEM, AND
 SECONDARY FROM AN APPROVED STANDBY SOURCE- SECTION
 513.11.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 08:26 Rev Time 0.00
Received By shill Date 2017-11-14 Time 08:26 Sent To  
Notes
2017-12-19 14:11:38MECH DIG/SIGS GOOD-
 CCOLE-12/19/17
2017-11-14 08:26:52SIGNATURES OK
 PROVISO - ANY NEW SHEETS SUBMITTED REQUIRE NEW REVIEW
  
  