Plan Review Details - Permit 17101133
Plan Review Stops For Permit 17101133
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-12-07 Cont ID  
Sent By jwitmer Date 2017-12-07 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2017-12-07 Time 16:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-13 Cont ID  
Sent By jwitmer Date 2017-11-13 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2017-11-13 Time 09:10 Sent To  
Notes
2017-11-13 09:25:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17101133
 W. P. B. PERMIT: 16110007
 ADD: 901 45TH ST.
 CONT: PROVINCIAL SOUTH DBA PSI ROOFING
 TEL: 954-791-7663X225
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 13/ 2017
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) 2ND REQUEST. PLEASE NOTE UNDER THE ORIGINAL PERMIT
 THE ONLY STRUCTURAL SHEETS THAT WERE SUBMITTED ARE
 S-000, S-100 & S-101. WE HAVE NO RECORDS OF A SHEET
 S-102. PLEASE SUBMIT SHEET S-102 AS A REVISION NOTE
 ADDITIONAL REVIEW AND ASSOCIATED COST. 107.2.1.3
 ADDITIONAL DATA.
  
 2) 2ND REQUEST. PLEASE NOTE THE PLANS DRAWINGS APRON
 ROOF DETAIL DUEL CONCRETE/ STEEL SUBSTRATE DO NOT HAVE
 WHO THE AUTHOR OF THE PLANS IS, IF THE CONTRACTOR,
 WHICH ROOFING OR THE CGC, IS THIS OUT OF THE SCOPE OF
 THE CONTRACTING LICENSING LAWS? IF NOT THE QUALIFIER
 WILL NEED TO PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, OTHERWISE A DESIGN PROFESSIONAL WILL
 NEED TO SIGN AND SEAL THE PLAN. PLEASE NOT IF THE
 CONTRACTOR TAKES RESPONSIBILITY FOR THE PLANS THEN IT
 WILL NEED TO BE REVIEWED BY THE DESIGN PROFESSIONAL AND
 SHOP DRAWING STAMP OF APPROVAL APPLIED.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDIVIDUAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003(1) ARCHITECTS.
  
 3) 2ND REQUEST. PLEASE NOTE THE STRUCTURAL ENGINEER OF
 RECORD HAS NOT REVIEWED THE SHOP DRAWINGS APRON ROOF
 DETAIL DUEL CONCRETE/ STEEL SUBSTRATE NOR HAVE THEY
 REVIEWED THE ROOFING PRODUCT APPROVAL AND AFFIXED THEIR
 SHOP DRAWING STAMP OF APPROVAL.
  
 4) COMPLIED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By jwitmer Date 2017-10-31 Time 11:45 Rev Time  
Received By jwitmer Date 2017-10-31 Time 07:15 Sent To  
Notes
2017-10-31 11:42:132014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17101133
 W. P. B. PERMIT: 16110007
 ADD: 901 45TH ST.
 CONT: PROVINCIAL SOUTH DBA PSI ROOFING
 TEL: 954-791-7663X225
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 31/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE UNDER THE ORIGINAL PERMIT THE ONLY
 STRUCTURAL SHEETS THAT WERE SUBMITTED ARE S-000, S-100
 & S-101. WE HAVE NO RECORDS OF A SHEET S-102. PLEASE
 SUBMIT SHEET S-102 AS A REVISION NOTE ADDITIONAL REVIEW
 AND ASSOCIATED COST. 107.2.1.3 ADDITIONAL DATA.
  
 2) PLEASE NOTE THE PLANS DRAWINGS APRON ROOF DETAIL
 DUEL CONCRETE/ STEEL SUBSTRATE DO NOT HAVE WHO THE
 AUTHOR OF THE PLANS IS, IF THE CONTRACTOR, WHICH
 ROOFING OR THE CGC, IS THIS OUT OF THE SCOPE OF THE
 CONTRACTING LICENSING LAWS? IF NOT THE QUALIFIER WILL
 NEED TO PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, OTHERWISE A DESIGN PROFESSIONAL WILL NEED TO
 SIGN AND SEAL THE PLAN. PLEASE NOT IF THE CONTRACTOR
 TAKES RESPONSIBILITY FOR THE PLANS THEN IT WILL NEED TO
 BE REVIEWED BY THE DESIGN PROFESSIONAL AND SHOP DRAWING
 STAMP OF APPROVAL APPLIED.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003(1) ARCHITECTS.
  
 3) PLEASE NOTE THE STRUCTURAL ENGINEER OF RECORD HAS
 NOT REVIEWED THE SHOP DRAWINGS APRON ROOF DETAIL DUEL
 CONCRETE/ STEEL SUBSTRATE NOR HAVE THEY REVIEWED THE
 ROOFING PRODUCT APPROVAL AND AFFIXED THEIR SHOP DRAWING
 STAMP OF APPROVAL.
  
 4) COMPLIED. PLEASE NOTE THE ROOFING APPROVAL NOA
 14-0220.08 SUB-SYSTEM TPO DECK TYPE 2 PAGES 58&59HAVE
 HIGHLIGHTED FASTENING OPTION # 3 WITH A MAXIMUM DESIGN
 PRESSURE OF -67.5 PSF AND LIMITATION # 7 ALLOWING FOR
 ENHANCED FASTENING FOR ROOF ZONE # 3.
  
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-12-07 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-06 Time 09:57 Sent To  
Notes
2017-12-07 09:57:45RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-13 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-06 Time 10:16 Sent To  
Notes
2017-11-07 10:17:07RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-31 Cont ID  
Sent By   Date 2017-10-31 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-27 Time 11:14 Sent To  
Notes
2017-10-30 11:14:46JWITMER