| 2017-11-13 09:25:52 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17101133 |
| | W. P. B. PERMIT: 16110007 |
| | ADD: 901 45TH ST. |
| | CONT: PROVINCIAL SOUTH DBA PSI ROOFING |
| | TEL: 954-791-7663X225 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. NOV. 13/ 2017 |
| | ACTION: DENIED |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | |
| | |
| | 1) 2ND REQUEST. PLEASE NOTE UNDER THE ORIGINAL PERMIT |
| | THE ONLY STRUCTURAL SHEETS THAT WERE SUBMITTED ARE |
| | S-000, S-100 & S-101. WE HAVE NO RECORDS OF A SHEET |
| | S-102. PLEASE SUBMIT SHEET S-102 AS A REVISION NOTE |
| | ADDITIONAL REVIEW AND ASSOCIATED COST. 107.2.1.3 |
| | ADDITIONAL DATA. |
| | |
| | 2) 2ND REQUEST. PLEASE NOTE THE PLANS DRAWINGS APRON |
| | ROOF DETAIL DUEL CONCRETE/ STEEL SUBSTRATE DO NOT HAVE |
| | WHO THE AUTHOR OF THE PLANS IS, IF THE CONTRACTOR, |
| | WHICH ROOFING OR THE CGC, IS THIS OUT OF THE SCOPE OF |
| | THE CONTRACTING LICENSING LAWS? IF NOT THE QUALIFIER |
| | WILL NEED TO PRINT THEIR NAME, SIGN THEIR NAME AND |
| | LICENSE NUMBER, OTHERWISE A DESIGN PROFESSIONAL WILL |
| | NEED TO SIGN AND SEAL THE PLAN. PLEASE NOT IF THE |
| | CONTRACTOR TAKES RESPONSIBILITY FOR THE PLANS THEN IT |
| | WILL NEED TO BE REVIEWED BY THE DESIGN PROFESSIONAL AND |
| | SHOP DRAWING STAMP OF APPROVAL APPLIED. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDIVIDUAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN |
| | CODE 61G16.003(1) ARCHITECTS. |
| | |
| | 3) 2ND REQUEST. PLEASE NOTE THE STRUCTURAL ENGINEER OF |
| | RECORD HAS NOT REVIEWED THE SHOP DRAWINGS APRON ROOF |
| | DETAIL DUEL CONCRETE/ STEEL SUBSTRATE NOR HAVE THEY |
| | REVIEWED THE ROOFING PRODUCT APPROVAL AND AFFIXED THEIR |
| | SHOP DRAWING STAMP OF APPROVAL. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |