| 2017-10-27 13:20:32 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | INFORMATION: THERE IS INDICATION OF A CERTIFIED FIRE |
| | ALARM CONTRACTOR THAT IS DOING THE WORK. THOUGH A TBD |
| | PERMIT CAN BE PASSED AND HELD FOR A QUALIFING |
| | CONTRACTOR THERE ARE OTHER CONCERNS WITH THIS PLAN SET |
| | THAT NEED TO BE ADDRESSED. |
| | |
| | |
| | 1) THESE ARE NOT SHOP DRAWINGS. |
| | |
| | PER NFPA 13 |
| | |
| | 3.3.238 SHOP DRAWINGS. DOCUMENTS THAT PROVIDE |
| | INFORMATION |
| | PERTAINING TO THE SYSTEM, SUCH AS PROPERTY LOCATION, |
| | SCALED |
| | FLOOR PLANS, EQUIPMENT WIRING DETAILS, TYPICAL |
| | EQUIPMENT INSTALLATION |
| | DETAILS, RISER DETAILS, CONDUIT/CONDUCTOR SIZE AND |
| | ROUTING INFORMATION, AND OTHER INFORMATION NECESSARY |
| | FOR THE |
| | INSTALLER TO COMPLETE THE FIRE ALARM INSTALLATION. |
| | |
| | 10.18 DOCUMENTATION. |
| | 10.18.1 APPROVAL AND ACCEPTANCE. |
| | 10.18.1.1 THE AUTHORITY HAVING JURISDICTION SHALL BE |
| | NOTIFIED |
| | PRIOR TO INSTALLATION OR ALTERATION OF EQUIPMENT OR |
| | WIRING. |
| | 10.18.1.2* AT THE AUTHORITY HAVING JURISDICTION?S |
| | REQUEST, COMPLETE |
| | INFORMATION REGARDING THE SYSTEM OR SYSTEM ALTERATIONS, |
| | INCLUDING SPECIFICATIONS, TYPE OF SYSTEM OR SERVICE, |
| | SHOP DRAWINGS, |
| | INPUT/OUTPUT MATRIX, BATTERY CALCULATIONS, AND |
| | NOTIFICATION |
| | APPLIANCE CIRCUIT VOLTAGE DROP CALCULATIONS, SHALL BE |
| | SUBMITTED |
| | FOR APPROVAL. |
| | |
| | GENERAL. SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHOULD |
| | PROVIDE |
| | BASIC INFORMATION AND SHOULD PROVIDE THE BASIS FOR THE |
| | RECORD DRAWINGS REQUIRED ELSEWHERE IN THIS CODE. |
| | CONTENT. SHOP DRAWINGS SHOULD INCLUDE, TO AN EXTENT |
| | COMMENSURATE |
| | WITH THE EXTENT OF THE WORK BEING PERFORMED, FLOOR PLAN |
| | DRAWINGS, RISER DIAGRAMS, CONTROL PANEL WIRING |
| | DIAGRAMS, POINT-TOPOINT |
| | WIRING DIAGRAMS, CONDUIT, CONDUCTOR ROUTING, TYPICAL |
| | WIRING |
| | DIAGRAMS, AND OTHER INFORMATION AS DESCRIBED HEREIN. |
| | ALL SHOP DRAWINGS SHOULD BE DRAWN ON SHEETS OF UNIFORM |
| | SIZE AND SHOULD INCLUDE THE FOLLOWING INFORMATION: |
| | (1) NAME OF PROTECTED PREMISES, OWNER, AND OCCUPANT |
| | (WHERE |
| | APPLICABLE) |
| | (2) NAME OF INSTALLER OR CONTRACTOR |
| | (3) LOCATION OF PROTECTED PREMISES |
| | (4) DEVICE LEGEND IN ACCORDANCE WITH NFPA 170, STANDARD |
| | FOR |
| | FIRE SAFETY AND EMERGENCY SYMBOLS |
| | (5) DATE OF ISSUE AND ANY REVISIONS |
| | |
| | |
| | |
| | 2) THERE IS INSUFFICIENT DETAILS OF THE SYSTEM AND IT'S |
| | COMPONENTS INDICATED. |
| | |
| | PLEASE PROVIDE SYSTEM DETAILS |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATIONS OF A RISER DIAGRAM WITH ALL |
| | DEVICES, CIRCUITS, POWER CONNECTIONS AND INTERFACES. |
| | |
| | FIRE ALARM SYSTEM RISER DIAGRAMS SHOULD INCLUDE THE |
| | FOLLOWING |
| | INFORMATION: |
| | (1) GENERAL ARRANGEMENT OF THE SYSTEM IN BUILDING |
| | CROSS-SECTION |
| | (2) NUMBER OF RISERS |
| | (3) TYPE AND NUMBER OF CIRCUITS IN EACH RISER |
| | (4) TYPE AND NUMBER OF FIRE ALARM SYSTEM COMPONENTS/ |
| | DEVICES ON EACH CIRCUIT, ON EACH FLOOR OR LEVEL |
| | (5) TYPE AND QUANTITY OF CONDUCTORS AND CONDUIT (IF |
| | USED) FOR |
| | EACH CIRCUIT |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 4) THERE ARE NO VOLTAGE DROP CALCULATIONS. |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | 5) THERE ARE NO BATTERY CALCULATIONS. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 6) THERE ARE DEVICE/EQUIPMENT SPECIFICATION SHHEETS. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |