Plan Review Details - Permit 17101066
Plan Review Stops For Permit 17101066
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-02-23 Cont ID  
Sent By rmcdouga Date 2018-02-23 Time 12:53 Rev Time 0.00
Received By rmcdouga Date 2018-02-23 Time 12:53 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-02-20 Cont ID  
Sent By rmcdouga Date 2018-02-20 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2018-02-20 Time 17:36 Sent To  
Notes
2018-02-20 19:00:30ROOFING MATERIAL: POLYGLASS MODIFIED BITUMEN FL1654-20
  
 THE RAS117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THIS PRODUCT APPROVAL IS NOT A MIAMI-DADE NOTICE OF
 ACCEPTANCE. THIS IS A FLORIDA (DBPR) PRODUCT APPROVAL.
 IN ORDER TO AVOID CONFUSION, REMOVE THE NOA FROM THE FL
 1654-R20 FROM THE ENGINEER'S LETTER. FBC 107.2.1
  
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 INCORRECTLY SPECIFIED AS SHEET 17 OF 58. THE SYSTEM
 NUMBER IS SPECIFIED ON THE ENGINEER'S LETTER AS W-94,
 WHICH IS LOCATED ON PAGE 18 OF 55. FBC 107.2.1
  
 3) THE REQUIRED UPLIFT PRESSURES FOR THE ROOF ZONES IS
 NOT SPECIFIED ON THE ENGINEER'S LETTER. THE WIND SPEED,
 EXPOSURE CATEGORY AND MEAN ROOF HEIGHT ARE ALSO NOT
 PROVIDED. FBC-R301.2.1
  
 4) THE W-94 ROOFING SYSTEM HAS A MAXIMUM DESIGN
 PRESSURE OF -67.5 PSF. THE LETTER STATES THAT THE
 MAXIMUM DESIGN PRESSURE IS -60 PSF. FBC 107.2.1
  
 5) THE W-94 ROOFING SYSTEM IS A PROPRIETARY SYSTEM AND
 REQUIRES POLYGLASS APP BASE FOR THE BASE SHEET. THE
 OTHERS LISTED IN THE LETTER CAN NOT BE USED WITH THIS
 SYSTEM. FBC 107.2.1
  
 6) THIS SYSTEM REQUIRES FOUR (4) EQUALLY SPACED
 STAGGERED CENTER ROWS AND THE LETTER ONLY SPECIFIES
 THREE (3). FBC 107.2.1
  
 7) THE PERIMETER AND CORNER AREA FASTENING DOES NOT
 SPECIFY THE LAP OR THE NUMBER OF CENTER ROWS. FBC
 107.2.1
  
 8) SUBMIT TWO SETS OF THE ACTUAL RAS 117 CALCULATIONS
 THAT WERE USED TO DETERMINE THE ENHANCED FASTENING. FBC
 107.2.1.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-01 Cont ID  
Sent By rmcdouga Date 2018-02-01 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2018-02-01 Time 17:02 Sent To I
Notes
2018-02-01 18:24:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 FBC 107.2.1
 THE RAS 117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THE SYSTEM NUMBER FROM THE FLORIDA PRODUCT APPROVAL
 (FL1654-R20) IS NOT SPECIFIED.
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 NOT SPECIFIED.
 3) THE UPLIFT PRESSURE FOR ROOF ZONE 3 IS NOT CORRECT.
 IT SHOULD BE -95.7 PSF FOR THIS PROJECT.
 4) I COULD NOT FIND ANY SYSTEMS THAT HAVE A MAXIMUM
 DESIGN PRESSURE OF -60 PSF WITH FASTENER SPACINGS OF
 10"OC AT THE 4" LAP AND 6"OC IN THREE EQUALLY SPACED
 STAGGERED ROWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By rmcdouga Date 2017-11-02 Time 17:58 Rev Time 0.00
Received By rmcdouga Date 2017-11-02 Time 07:42 Sent To  
Notes
2017-11-02 17:58:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ENERGY FORM R402 - 2014 IS REQUIRED TO BE SIGNED AND
 DATED BY THE PREPARER AND THE OWNER/AGENT CERTIFYING
 COMPLIANCE WITH THE ENERGY CODE. FBC ENERGY
 CONSERVATION SECTION R103.
  
 2) INDICATE THE SYSTEM NUMBER AND MAXIMUM DESIGN
 PRESSURE FOR THE ROOF COVERING THAT WILL BE USED ON THE
 PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED BITUMEN
 ROOF SYSTEM. FBC 107.2.1
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED ENHANCED
 FASTENING CALCULATIONS FROM A FLORIDA LICENSED ENGINEER
 FOR THE POLYGLASS MODIFIED BITUMEN ROOF SYSTEM. SEE
 NOTE 8 ON PAGE 2 OF 55 OF THE PRODUCT APPROVAL. FBC -
 R301.2.1
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-31 Cont ID  
Sent By jpearson Date 2018-01-31 Time 11:11 Rev Time 0.00
Received By jpearson Date 2018-01-31 Time 06:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By jpearson Date 2017-11-17 Time 11:14 Rev Time 0.00
Received By jpearson Date 2017-11-17 Time 11:14 Sent To I
Notes
2017-11-17 11:14:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOW # 6 WIRE FEEDING A 125 AMP PANEL.
 PROVIDE CORRECTION FOR WIRE SIZE, # 6 IS NOT RATED FOR
 125 AMPS. NEC 310.15(B)(16); FBC RE 3705.1
 2. RISER DIAGRAM SHOWS 2 PANELS, PROVIDE PANEL SCHEDULE
 FOR EACH. NEC 408.4; FBC 107.2.1
 3. RISER DIAGRAM SHOWS THE INTERSYSTEM BONDING
 TERMINATION POINT LOCATED AT SUB-PANEL. THIS SHOULD BE
 AT MAIN SERVICE. PROVIDE CORRECTION. FBC RE 3609.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-23 Cont ID  
Sent By rmcdouga Date 2018-02-23 Time 13:12 Rev Time 0.00
Received By rmcdouga Date 2018-02-21 Time 14:15 Sent To  
Notes
2018-02-22 14:15:28RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-20 Cont ID  
Sent By rmcdouga Date 2018-02-20 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-02-15 Time 13:17 Sent To  
Notes
2018-02-16 13:17:48RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-01 Cont ID  
Sent By rmcdouga Date 2018-02-01 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 15:34 Sent To  
Notes
2018-01-09 15:35:04R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-17 Cont ID  
Sent By jpearson Date 2017-11-17 Time 11:14 Rev Time 0.00
Received By jpearson Date 2017-10-25 Time 12:43 Sent To  
Notes
2017-10-27 12:43:11R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By rmcdouga Date 2018-02-26 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2018-02-26 Time 16:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By rmcdouga Date 2017-11-02 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2017-11-02 Time 07:44 Sent To  
Notes
2017-11-02 07:45:39BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-31 Cont ID  
Sent By hmoser Date 2018-01-31 Time 13:38 Rev Time 0.00
Received By hmoser Date 2018-01-31 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By rmcdouga Date 2017-11-02 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2017-11-02 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By rmcdouga Date 2017-11-02 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2017-11-02 Time 10:00 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-02-23 Cont ID  
Sent By rmcdouga Date 2018-02-23 Time 12:56 Rev Time 0.00
Received By rmcdouga Date 2018-02-23 Time 12:56 Sent To  
Notes
2018-02-23 13:07:14FL16709-R4, CERTAINTEED MODIFIED BITUMEN ROOF SYSTEM,
 PAGES 13-14

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-02-20 Cont ID  
Sent By rmcdouga Date 2018-02-20 Time 17:49 Rev Time 0.00
Received By rmcdouga Date 2018-02-20 Time 17:49 Sent To  
Notes
2018-02-20 18:51:15ROOFING MATERIAL: POLYGLASS MODIFIED BITUMEN FL1654-20
  
 THE RAS117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THIS PRODUCT APPROVAL IS NOT A MIAMI-DADE NOTICE OF
 ACCEPTANCE. THIS IS A FLORIDA (DBPR) PRODUCT APPROVAL.
 IN ORDER TO AVOID CONFUSION, REMOVE THE NOA FROM THE FL
 1654-R20 FROM THE ENGINEER'S LETTER. FBC 107.2.1
  
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 INCORRECTLY SPECIFIED AS SHEET 17 OF 58. THE SYSTEM
 NUMBER IS SPECIFIED ON THE ENGINEER'S LETTER AS W-94,
 WHICH IS LOCATED ON PAGE 18 OF 55. FBC 107.2.1
  
 3) THE REQUIRED UPLIFT PRESSURES FOR THE ROOF ZONES IS
 NOT SPECIFIED ON THE ENGINEER'S LETTER. THE WIND SPEED,
 EXPOSURE CATEGORY AND MEAN ROOF HEIGHT ARE ALSO NOT
 PROVIDED. FBC-R301.2.1
  
 4) THE W-94 ROOFING SYSTEM HAS A MAXIMUM DESIGN
 PRESSURE OF -67.5 PSF. THE LETTER STATES THAT THE
 MAXIMUM DESIGN PRESSURE IS -60 PSF. FBC 107.2.1
  
 5) THE W-94 ROOFING SYSTEM IS A PROPRIETARY SYSTEM AND
 REQUIRES POLYGLASS APP BASE FOR THE BASE SHEET. THE
 OTHERS LISTED IN THE LETTER CAN NOT BE USED WITH THIS
 SYSTEM. FBC 107.2.1
  
 6) THIS SYSTEM REQUIRES FOUR (4) EQUALLY SPACED
 STAGGERED CENTER ROWS AND THE LETTER ONLY SPECIFIES
 THREE (3). FBC 107.2.1
  
 7) THE PERIMETER AND CORNER AREA FASTENING DOES NOT
 SPECIFY THE LAP OR THE NUMBER OF CENTER ROWS. FBC
 107.2.1
  
 8) SUBMIT TWO SETS OF THE ACTUAL RAS 117 CALCULATIONS
 THAT WERE USED TO DETERMINE THE ENHANCED FASTENING. FBC
 107.2.1.3

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By rmcdouga Date 2018-02-01 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2018-02-01 Time 18:24 Sent To  
Notes
2018-02-01 18:32:12ROOFING MATERIAL: POLYGLASS MODIFIED BITUMEN FL1654-20
  
 THE RAS117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THE SYSTEM NUMBER FROM THE FLORIDA PRODUCT APPROVAL
 (FL1654-R20) IS NOT SPECIFIED.
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 NOT SPECIFIED.
 3) THE UPLIFT PRESSURE FOR ROOF ZONE 3 IS NOT CORRECT.
 IT SHOULD BE -95.7 PSF FOR THIS PROJECT.
 4) I COULD NOT FIND ANY SYSTEMS THAT HAVE A MAXIMUM
 DESIGN PRESSURE OF -60 PSF WITH FASTENER SPACINGS OF
 10"OC AT THE 4" LAP AND 6"OC IN THREE EQUALLY SPACED
 STAGGERED ROWS.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-22 Cont ID  
Sent By llouie Date 2018-01-22 Time 16:03 Rev Time 0.00
Received By llouie Date 2018-01-22 Time 15:34 Sent To  
Notes
2018-01-22 16:04:08SCOPE OF WORK DOES NOT EXCEED 50% OF THE VALUE OF THE
 STRUCTURE.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-15 Cont ID  
Sent By LL Date 2017-11-15 Time   Rev Time 0.00
Received By llouie Date 2017-11-06 Time 16:02 Sent To  
Notes
2017-11-15 16:24:44SCOPE OF WORK DOES NOT EXCEED 50% OF THE VALUE OF THE
 STRUCTURE.