Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By jwitmer Date 2017-11-03 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2017-11-03 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By jwitmer Date 2017-10-26 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2017-10-26 Time 07:02 Sent To  
Notes
2017-10-26 07:31:502014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100966 (ROOF)
 PRIME BUILD PER.: 16080183
 ADD: 518 S. DIXIE HWY.
 CONT: RED APPLE ROOFING
 TEL: 954-797-1274
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. OCT. 26/2017
 ACTION: DENIED
  
 1) THERE IS A PRIME ROOFING PERMIT AND DESIGNER OF
 RECORD FOR THIS PROJECT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) PLEASE HAVE THE DESIGNER OF RECORD DECLARE IF THERE
 IS A ROOF ZONE 3 WHICH WOULD REQUIRE ENHANCED
 FASTENING. PLANS DO NOT IDENTIFY FINISH ROOF ELEVATION
 NOR THE FINISH PARAPET HEIGHT.
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By   Date 2017-11-03 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-30 Time 12:49 Sent To  
Notes
2017-10-31 12:49:18RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-26 Cont ID  
Sent By   Date 2017-10-26 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-24 Time 12:49 Sent To  
Notes
2017-10-25 12:50:11JWITMER


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved