Plan Review Details - Permit 17100911
Plan Review Stops For Permit 17100911
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-14 Cont ID  
Sent By rmcdouga Date 2018-02-14 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2018-02-14 Time 17:32 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By rmcdouga Date 2017-11-03 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2017-11-03 Time 06:46 Sent To G
Notes
2017-11-03 07:12:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE COMPLETE DIMENSIONED STRUCTURAL DRAWINGS OF
 THE OUT DOOR KITCHEN CABINET. SHOW A FLOOR PLAN VIEW
 WITH DIMENSIONS INCLUDING DEPTH. SHOW THE SPACING OF
 THE #3 REINFORCING BARS AND REINFORCED TIE BEAM AT TOP
 OF THE WALLS. FBC - R 301.2.1
  
 2) SHOW THE DIMENSIONS AND SPECIFY THE REINFORCING FOR
 THE 6" SLAB THAT WILL SUPPORT THE CONCRETE WALLS OF THE
 KITCHEN. FBC - R 301.1
  
 3) SUBMIT TWO SETS OF THE MANUFACTURER'S
 SPECIFICATIONS, LISTING INFORMATION AND INSTALLATION
 INSTRUCTIONS FOR THE GAS GRILL TOP. FBCR - G2404

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-02-14 Cont ID  
Sent By gjohnson Date 2018-02-14 Time 15:45 Rev Time 0.00
Received By gjohnson Date 2018-02-14 Time 15:45 Sent To  
Notes
2018-02-14 15:46:30GAS PROVISO:
 1. PROVIDE DOCUMENTATION SHOWING EXISTING SYSTEM BTU
 LOAD CAPACITY.
 2. CONNECTION SHALL BE PER MANUFACTURE INSTALLATION
 GUIDE AND APPROVED FOR USE WITH NATURAL GAS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By gjohnson Date 2017-11-07 Time 13:57 Rev Time 0.00
Received By gjohnson Date 2017-11-07 Time 13:57 Sent To  
Notes
2017-11-07 14:15:351ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. PROVIDE DETAIL SHOWING GAS CONNECTION BETWEEN GRILL
 AND EXISTING GAS. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-14 Cont ID  
Sent By rmcdouga Date 2018-02-14 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2018-01-31 Time 15:15 Sent To  
Notes
2018-02-01 15:16:11RESUB ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-07 Cont ID  
Sent By gjohnson Date 2017-11-07 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2017-10-23 Time 10:11 Sent To  
Notes
2017-10-24 10:11:27ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2018-02-09 Cont ID  
Sent By pgreilic Date 2018-02-09 Time 09:17 Rev Time 0.00
Received By pgreilic Date 2018-02-07 Time 10:38 Sent To G
Notes
2018-02-09 11:14:17PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-10-31 Time   Rev Time 0.00
Received By ajones Date 2017-10-26 Time 11:35 Sent To  
Notes
***NONE***