Plan Review Details - Permit 17100879
Plan Review Stops For Permit 17100879
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-10 Cont ID  
Sent By shill Date 2018-01-10 Time 06:47 Rev Time 0.00
Received By shill Date 2018-01-10 Time 06:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By shill Date 2017-10-24 Time 10:13 Rev Time 0.00
Received By shill Date 2017-10-24 Time 10:13 Sent To  
Notes
2017-10-24 10:14:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SHEET A401B, DETAILS 1B, 9, THE BATHROOM ENTRY DOOR
 WAS REMOVED; HOW DOES ONE ENTER THE ROOM? FBC 107.
  
 2. A403, THE ELEVATION DETAIL AND FLOOR PLAN (DETAIL 1)
 APPEAR TO CONFLICT. WHEN SCALED, 8" IS SHOWN FROM
 TOILET TO COUNTER, 21" SHOWN IN DETAIL 11.
  
 3. CIVIL,LANDSCAPE, AND IRRIGATION SHEETS WERE
 SUBMITTED. PLEASE COORDINATE WITH ENGINEERING, ZONING,
 AND PLUMBING. IT APPEARS THAT THESE SHEETS SHOULD BE
 SUBMITTED AS REVISIONS TO THE PERMITS ASSOCIATED WITH
 THE WORK, FBC 107.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-03 Cont ID  
Sent By jleahy Date 2018-01-03 Time 08:30 Rev Time 0.00
Received By jleahy Date 2018-01-03 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-09 Cont ID  
Sent By jleahy Date 2017-11-09 Time 16:15 Rev Time 0.00
Received By jleahy Date 2017-11-09 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-10 Cont ID  
Sent By shill Date 2018-01-10 Time 06:50 Rev Time 0.00
Received By shill Date 2017-12-18 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2017-12-08 Cont ID  
Sent By hmoser Date 2017-12-08 Time 12:55 Rev Time 0.00
Received By hmoser Date 2017-10-23 Time 16:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-12-08 Cont ID  
Sent By hmoser Date 2017-12-08 Time 12:55 Rev Time 0.00
Received By hmoser Date 2017-12-08 Time 12:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-09 Cont ID  
Sent By tklarge Date 2018-01-09 Time 11:41 Rev Time 0.00
Received By tklarge Date 2018-01-09 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By tklarge Date 2017-11-01 Time 09:19 Rev Time 0.00
Received By tklarge Date 2017-10-30 Time 09:29 Sent To  
Notes
2017-10-31 04:58:141) SHT. C 103 - IDENTIFY IN THE NARRATIVE THE SPECIFIC
 CHANGES THAT HAVE BEEN MADE TO THIS DRAWING. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) IRRIGATION SHEETS I101 & I102 - IDENTIFY IN THE
 NARRATIVE THE SPECIFIC CHANGES THAT HAVE BEEN MADE TO
 THESE DRAWINGS.WPB AMEND. TO FBC SEC. 107.2.1.A
 REVISION APPLICATION SHOULD BE SUBMITTED UNDER THE
 IRRIGATION PERMIT.
 3) SHT. A101C - SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 TOILET ROOM #168. SHOW THE WIDTH OF THE LAVATORY
 COUNTERTOP, AND SHOW THE REQUIRED CLEAR FLOOR SPACE FOR
 THE WATER CLOSET AND THE LAVATORY AND THE DIMENSIONS OF
 EACH CLEAR FLOOR SPACE.COMPLY WITH 2010
 FBC-ACCESSIBILITY SECS. 604.3.1, 606.2.
 4) SHT.A103A - SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 TOILET ROOM #838. SHOW THE WIDTH OF THE LAVATORY
 COUNTERTOP, AND SHOW THE REQUIRED CLEAR FLOOR SPACE FOR
 THE WATER CLOSET AND THE LAVATORY AND THE DIMENSIONS OF
 EACH CLEAR FLOOR SPACE.COMPLY WITH 2010
 FBC-ACCESSIBILITY SECS. 604.3.1, 606.2.
 5) SHT.A104A - SHOW THE WIDTH OF THE LAVATORY
 COUNTERTOP IN TOILET ROOM #938..
 6) SHT.A401A - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 7) SHT. A401B - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 8)SHT. A401B - ADA BATH - SHOW THE REQUIRED 60 INCHES
 WIDE BY 56 INCHES DEEP CLEAR FLOOR SPACE FOR THE WATER
 CLOSET PER THE FBC- ACCESSIBILITY SEC.233.3,809.4,
 604.3.
 9) SHT. A401C - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 10) SHT. A402 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN. .
 11) SHT. A403 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 12) SHT. A404 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 13) SHT. A405 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 14) SHT. A406 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 15) SHT. A407 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 16) SHT. A408 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 17) SHT. A410 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 18) SHT. A412 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER
 THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7
 (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE
 PLAN.
 19) SHT. P101C - BREAKROOM #167 - THE CONDENSATE WASTE
 CANNOT DISCHARGE TO THE HAND SINK/SANITARY SYSTEM PER
 CITY OF WPB CODE OF ORDINANCES CHAPT. 90, SEC. 90-126
 (B) (5).
 20) SHT. P502 - THE DRAWING SHOWS THE DELETION OF TWO
 RECIRCULATING PUMPS FOR THE HOT WATER RECIRCULATION
 SYSTEM AND THE BOOSTER PUMP BEING USED TO SERVE THE
 RECIRCULATION SYSTEM. THE WATER HEATER/STORAGE TANK
 DETAIL STILL SHOWS A RECIRCULATION PUMP NEAR THE
 AQUASTAT. SHOULD THIS BE IDENTIFIED AS THE BOOSTER
 PUMP? CLARIFY.
 21) PLEASE CLARIFY WITH A NARRATIVE AS TO HOW THE
 INSTALLATION OF A BOOSTER PUMP THAT WILL OPERTE WHEN
 THE PRESURE FALLS BELOW 100 PSI WILL MEET THE INTENT OF
 COMPLYING WITH 2010 FBC-PLUMBING SEC.607.2 FOR
 MAINTAINING THE TEMPERATURE IN ACCORDANCE WITH THE 2010
 FBC-ENERGY CODE SEC. 504. THE PREVIOUS RECIRCULATING
 PUMPS WERE WIRED TO AN AQUASTAT WHEREAS THE BOOSTER
 PUMP APPEARS TO BE WIRED TO PRESSURE SENSORS. I AM
 CONFUSED. PLEASE CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-07 Cont ID  
Sent By eschneid Date 2017-11-07 Time 17:08 Rev Time 1.00
Received By eschneid Date 2017-11-07 Time 17:08 Sent To  
Notes
***NONE***