Plan Review Details - Permit 17100875
Plan Review Stops For Permit 17100875
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-12-21 Cont ID  
Sent By squinone Date 2017-12-21 Time   Rev Time 0.00
Received By squinone Date 2017-12-21 Time   Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-03 Cont ID  
Sent By tklarge Date 2018-01-03 Time 06:15 Rev Time 0.00
Received By tklarge Date 2017-12-29 Time 10:49 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-27 Cont ID  
Sent By tklarge Date 2017-12-27 Time 14:19 Rev Time 0.00
Received By tklarge Date 2017-12-20 Time 16:32 Sent To I
Notes
2017-12-21 16:32:33RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-21 Cont ID  
Sent By lmarchan Date 2017-12-21 Time 13:19 Rev Time 0.00
Received By lmarchan Date 2017-12-19 Time 06:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-03 Cont ID  
Sent By tklarge Date 2018-01-03 Time 06:15 Rev Time 0.00
Received By tklarge Date 2018-01-03 Time 05:50 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By tklarge Date 2017-12-27 Time 14:18 Rev Time 0.00
Received By tklarge Date 2017-12-27 Time 14:12 Sent To I
Notes
2017-12-27 14:17:481) SHT. P2 - THE GREASE TRAP DETAIL NOTES A 100 GPM
 UNIT BUT THE PLANS SHOW A 50/75 GPM UNIT. CLARIFY.
 2) AN AIR ADMITTANCE VALVE (AAV) CAN BE USED ON A
 GREASE INTERCEPTOR AS LONG AS THEY ARE NOT SUBJECT TO
 POSITIVE PRESSURE PER THE MANUFACTURER (STUDOR) OF THE
 AAV. CONFIRMATION OF THIS WILL NEED TO BE PROVIDED FROM
 SCHIER.
 3) SUBMIT TWO COPIES OF OF THE MANUFACTURER'S
 INSTALLATION GUIDE FOR THIS UNIT. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By tklarge Date 2017-12-19 Time 06:51 Rev Time 0.00
Received By tklarge Date 2017-12-19 Time 06:40 Sent To  
Notes
2017-12-19 06:51:331) SUBMIT TWO SETS OF PLANS AND SPECIFICATIONS FOR THE
 GREASE INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.1.
 2) SUBMIT SIZING CALCULATIONS FOR THE INTERCEPTOR. FBC
 PLUMBING SEC. 1003.2.
 3) SUBMIT TWO COPIES OF A SITE PLAN SHOWING THE
 LOCATION OF THE INTERCEPTOR. WPB AMEEND. TO FBC SEC.
 107.2.1.
 4) A SAMPLING PORT SHALL BE LOCATED ON THE OUTLET OF
 THE GREASE INTERCEPTOR PER WPB STANDARD DRAWING GS-7,
 GS-7.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  